Hydrastep 2468CB & 2468CD Manual | Remote Display Options 24683B, C & D |
4.5SYSTEM OPERATION
When the system is brought on line check for complete agreement between the remote display and the Hydrastep level indicator display.
4.6FAULT ANALYSIS AND CORRECTIVE ACTION
Indication | Fault | Analysis and Corrective Action |
|
|
|
No display of odd LEDs | Loss of power to | Check that the wiring to connector PL1 in the remote |
(including bottom half of | remote display unit. | display unit is correct. |
fault LED. |
| With a suitable meter, check that the supply voltage is |
|
| |
|
| present at the remote display unit connector. Ensure that |
|
| the voltage is in the range 14V through 45Vdc. |
|
| If the unit is locally powered and no voltage is present |
|
| check the voltage at the local power source. |
|
| If the unit is powered from the 2468 electronics unit check |
|
| the voltage between pins 5 and 8 of PL3 on the display |
|
| board (24680502) of that unit. A voltage of less than |
|
| 14Vdc indicates the possibility of a short circuit in the |
|
| power lines or a fault on the display board. Disconnect |
|
| connector SK3 from the display PCB in the 2468 |
|
| electronics unit and |
|
| and 8 of PL3. If the voltage is less than 18Vdc then the |
|
| display board in the 2468 electronics unit may be faulty. |
|
| Replace this board with a serviceable item and check for |
|
| the correct voltage between pins 5 and 8 of PL3. |
|
|
|
No display of even | Loss of power to | Check that the wiring to connector PL2 in the remote |
LEDs (including top half | remote display unit. | display unit is correct. |
of fault LED). |
| With a suitable meter, check that the supply voltage is |
|
| |
|
| present at the remote display unit connector. Ensure that |
|
| the voltage is in the range 14V through 45Vdc. |
|
| If the unit is locally powered and no voltage is present |
|
| check the voltage at the local power source. |
|
| If the unit is powered from the 2468 electronics unit check |
|
| the voltage between pins 5 and 8 of PL7 on the display |
|
| board (24680502) of that unit. A voltage of less than |
|
| 14Vdc indicates the possibility of a short circuit in the |
|
| power lines or a fault on the display board. Disconnect |
|
| connector SK3 from the display PCB in the 2468 |
|
| electronics unit and |
|
| and 8 of PL7. If the voltage is less than 18Vdc then the |
|
| display board in the 2468 electronics unit may be faulty. |
|
| Replace this board with a serviceable item and check for |
|
| the correct voltage between pins 5 and 8 of PL7. |
|
|
|
Table 4.1 - Fault Analysis and Correction Chart
24685034 |
|