Emerson 2468CB, 2468CD 2-24, Indication, Faults, Analysis and Corrective Action, State 1 contd

Models: 2468CD 2468CB

1 186
Download 186 pages 11.63 Kb
Page 44
Image 44

2468CB & 2468CD Dual Power Supply Version

Hydrastep 2468CB and 2468CD Manual

Indication

Fault(s)

Analysis and Corrective Action

 

 

 

State 1 (contd.)

Incorrect wiring,

Check ac voltage on electrodes with a true r.m.s.

 

broken connection

voltmeter. A voltage of less than 0.1V ac indicates a fault

 

or damaged cable

condition.

 

assembly

If wiring to the electrode is correct and the electrode

 

Affected

gives a voltage reading of greater than 0.1V ac and a

 

electrode(s)

fault is still indicated, carry out the following procedure:

 

alternate between

1. Remove both conductors from the suspect electrode.

 

water and steam.

With the conductors isolated from each other, the

 

 

level display should show the electrode as

 

 

alternating between water and steam (green and

 

 

red).

 

 

2. With the conductors touching each other, the level

 

 

display should show electrode as being in steam.

 

 

The above procedure checks the electrode wiring. If the

 

 

display does not show the correct results, then check for

 

 

a break in either of the suspect electrode conductors.

 

 

Carry out repair to any faulty connection or substitute a

 

 

new conductor or cable assembly in place of the

 

 

defective item.

 

 

 

 

Dirt on electrode

If the wiring checks carried out as described above have

 

Affected

not located a fault, then dirt on an electrode insulator may

 

be the cause of the problem giving an effective short-

 

electrode(s)

 

circuit to ground.

 

alternate between

 

Check the electrodes for dirt over the external insulator

 

water and steam.

 

 

and clean with a cloth as required.

 

 

Checking for dirt on the internal insulator of the electrode

 

 

requires the draining of the water column (refer to Part 2

 

 

of this manual for the correct procedure).

 

 

Once the water column is drained, check the ac voltage

 

 

on each electrode using a true r.m.s. voltmeter. Any

 

 

electrode showing a voltage of less than 3V ac needs

 

 

cleaning or replacement. Electrodes must be removed

 

 

from the column for inspection and cleaning.

 

 

Note: The electrode insulator can be cleaned using a

 

 

clean cloth

 

Internal fault

If the wiring checks carried out as described above have

 

 

not located a fault, then it is possible an internal fault

 

 

exists.

 

 

1. Disconnect the electrode cable sockets from the

 

 

input board.

 

 

2. Make up four 10-way sockets (six or eight sockets

 

 

required for systems with more than 16 points) with

 

 

wire links connecting the following pins on each

 

 

socket; 1-2, 4-5, 6-7, 9-10.

Table 2.3 - Fault analysis/corrective action chart (continued)

2-24

24685034

Page 44
Image 44