Opto-isolated Output Board Option

3C.3.1 CONFIGURING THE OPTO-ISOLATED OUTPUT BOARD

WARNING Mains voltages are present in this instrument when power is connected. De-energise before opening front cover.

Gain access to the printed circuit board assemblies inside the Hydrastep 2468 enclosure as follows:

1.Isolate the 2468 electronics enclosure from its power supplies.

2.Gain access to the output PCB and set the relevant switches for the required function.

3c.3.1.1 Electrode/Opto-Output Selection (Opto-1, Opto-2, Opto-3 & Opto-4 Outputs) - SW1 to SW4

Four identical switches are provided, one for each output (but see SW6) each having four sets of contacts. This allows coded selection of any one of 16 electrodes for each switch in the case of the single input card. When dual input cards are fitted, odd numbered electrodes feed into one input card with the even numbered electrodes being fed into the other input card. Each input card then offers any mounted output card the choice from its electrode inputs, with the resultant selectivity as shown in Table 3c.1.

Switch SW1, SW2, SW3 or SW4 Settings for

 

Electrode Selection

 

 

Opto 1 to Opto 4 respectively

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Switch Contacts

 

One Input

Two Input Cards

 

 

 

 

 

 

 

 

 

1

 

2

3

 

4

Card

Odd I/P Card

Even I/P Card

 

 

 

 

 

 

 

 

 

On

 

On

On

 

On

1

1

2

 

 

 

 

 

 

 

 

 

Off

 

On

On

 

On

2

3

4

On

 

Off

On

 

On

3

5

6

 

 

 

 

 

 

 

 

 

Off

 

Off

On

 

On

4

7

8

 

 

 

 

 

 

 

 

 

On

 

On

Off

 

On

5

9

10

 

 

 

 

 

 

 

 

 

Off

 

On

Off

 

On

6

11

12

 

 

 

 

 

 

 

 

 

On

 

Off

Off

 

On

7

13

14

Off

 

Off

Off

 

On

8

15

16

 

 

 

 

 

 

 

 

 

On

 

On

On

 

Off

9

17

18

 

 

 

 

 

 

 

 

 

Off

 

On

On

 

Off

10

19

20

 

 

 

 

 

 

 

 

 

On

 

Off

On

 

Off

11

21

22

 

 

 

 

 

 

 

 

 

Off

 

Off

On

 

Off

12

23

24

On

 

On

Off

 

Off

13

25

26

 

 

 

 

 

 

 

 

 

Off

 

On

Off

 

Off

14

27

28

 

 

 

 

 

 

 

 

 

On

 

Off

Off

 

Off

15

29

30

 

 

 

 

 

 

 

 

 

Off

 

Off

Off

 

Off

16

31

32

 

 

 

 

 

 

 

 

 

Table 3c.1 - Electrode selections for opto-isolated outputs Opto 1 to Opto 4

Example: Single Input Board - Electrode 13 selected.

Dual Input Boards: Odd input board - Electrode 25 selected Manual backgroundManual background Even input board - Electrode 26 selected. OFF