3B.5 SPECIFICATION

Outputs:

4 x Alarm/Trip Relays

 

 

Relay Contact Rating:

ac

dc

 

Maximum voltage:

250V

125V

 

Maximum current:

8A

8A

 

Maximum switching power:

1500VA

240W

(30V)

 

 

65W

(60V)

 

 

25W

(125V)

For type nA safety:

 

100mA at 30Vdc

Maximum initial contact resistance: 30mΩ

 

 

Time Delay:

Disabled or 0.8 ± 0.8s to 24.2s ± 0.8s