Opto-isolated Output Board Option

Hydrastep 2468CB & 2468CD Manual

3c.3.2.5 ‘Two out of Four’ Opto-output Alarm System

In the following diagrams (5A & 5B)  indicate the electrode channel selected for each opto-output. A fully functioning system (NO FAULTS) will perform a low level trip at electrode level 3. For a high level trip, using electrode channels 11, 12, 9 and 10 respectively and switch SW5 set for W, a healthy system would trip at level 10.

Case A - Opto-output circuit normally open circuit, short circuit one pair to trip

PL 2

TR2

3

1

 

 

2

 

 

3

Opto-output 1

 

4

TR4

1

5

 

 

6

 

7

Opto-output 2

8

Odd Electrodes

 

(RH Input Board)

 

TR2 4

Opto-output 1

TR4 2

Opto-output 2

Even Electrodes (LH Input Board)

PL 2

1

Note:

External power must

 

be applied as shown.

 

 

2

 

See specification for

 

power requirements

3

 

 

4

 

+ VE

 

 

5

 

To alarm

 

annunciator

 

 

or tripping

6

 

device

7

 

- VE

 

 

8

 

 

(Switch SW5 is set to S for low level alarms and set to W for high level alarms)

Case B - Opto-output circuit normally short circuit, open circuit one in each pair to trip

PL 2

TR2

3

1

 

 

2

 

 

3

Opto-output 1

 

4

TR4

1

5

 

 

6

 

7

Opto-output 2

8

Odd Electrodes

 

(RH Input Board)

 

TR2 4

Opto-output 1

TR4 2

Opto-output 2

Even Electrodes (LH Input Board)

PL 2

Note:

External power must

1be applied as shown. See specification for

2power requirements

3

 

4

+ VE

 

5

To alarm

annunciator

 

or tripping

6

device

7

- VE

 

8

 

(Switch SW5 is set to W for low level alarms and set to S for high level alarms)

3c-12

24685034

Page 114
Image 114
Emerson 2468CB, 2468CD manual 3c-12