Remote Display Options 24683B, C & D | Hydrastep 2468CB & 2468CD Manual |
4.4.5CONNECTING THE DISPLAY CABLES TO HYDRASTEP 2468
WARNING: Mains voltages are present in the 2468 Hydrastep unit when power is connected.
The connection procedure is:
1.Ensure a
2.Gain access to the display board in the 2468. The cable from the remote display requires connecting to connectors PL3 and PL7 on PCB 24680515.
3.Enter the cable through the gland port in the 2468 enclosure (if this is applicable) and ensure a
4.Prepare the cable ends, fit identity sleeves on the leads and connect them to their respective terminals. See the example in Figure 4.5.
5.Ensure that the cable screen is grounded at the gland plate.
| 24685034 |