Emerson 2468CB, 2468CD manual 4.4.5CONNECTING THE DISPLAY CABLES TO HYDRASTEP, 4-12

Models: 2468CD 2468CB

1 186
Download 186 pages 11.63 Kb
Page 130
Image 130

Remote Display Options 24683B, C & D

Hydrastep 2468CB & 2468CD Manual

4.4.5CONNECTING THE DISPLAY CABLES TO HYDRASTEP 2468

WARNING: Mains voltages are present in the 2468 Hydrastep unit when power is connected. De-energise before opening the front cover.

The connection procedure is:

1.Ensure a stress-free cable run between the remote display unit and Hydrastep 2468.

2.Gain access to the display board in the 2468. The cable from the remote display requires connecting to connectors PL3 and PL7 on PCB 24680515.

3.Enter the cable through the gland port in the 2468 enclosure (if this is applicable) and ensure a stress-free run inside the enclosure.

4.Prepare the cable ends, fit identity sleeves on the leads and connect them to their respective terminals. See the example in Figure 4.5.

5.Ensure that the cable screen is grounded at the gland plate.

4-12

24685034

Page 130
Image 130