Hydrastep 2468CB and 2468CD Manual | Delay Relay Output Board Option |
3B.4 COMPONENT REPLACEMENT
The delay relay board contains no replaceable circuit components, failure of the board requires replacement of the entire board. The only component that can be replaced is the nylon spacers.
3B.4.1 REPLACEMENT OF NYLON SPACERS
WARNING Mains voltages are present in this instrument when power is connected.
The replacement of nylon spacers fitted to the output board requires access to the non- component side of the PCB.
Note: Spacers will only be fitted on the output board if a second output board is to be fitted or has been fitted.
The spacers are secured in their holes by nut and nylon washer. To carry out a spacer replacement, the output board has to be removed from the input board. The procedure adopted is:
1.Isolate the 2468 electronic enclosure from the power supply.
2.Gain access to the PCBs and undo sufficient connections for the removal of the output board containing the defective spacer.
3.Remove the output board(s) by applying pressure
to the upper
4.Undo the nut and washer securing the faulty
spacer and extract it from its hole, see inset diagram.
5. Fit the new spacer in position, align correctly on the board and secure firmly using the M4 nut and nylon washer.
6.Refit the PCB(s) into the enclosure,
the PCB(s) as required and close the enclosure cover.
3B.4.2 PARTS LIST - DELAY RELAY OUTPUT BOARD 24680509
The following list items are available as spare parts:
Item Description | Mobrey Part | Item Description | Mobrey Part | |
Number | Number | |||
|
| |||
Electrical: |
| Mechanical: |
| |
Delay relay PCB assembly: | 24680509B | Spacer, nylon 15.9 LG | 412012080 | |
Socket 5K2 free | 351508100 | Washer, nylon | 411999910 | |
Nut, M4 | 410031020 | |||
Socket 5K3 free | 351503100 | |||
|
| |||
|
|
|
|
24685034 |
|