Hydrastep 2468CB & 2468CD Manual

Remote Display Options 24683B, C & D

Indication

Fault

Analysis and Corrective Action

 

 

 

Flickering Display

Corruption of signal

Most probably caused by bad shielding (screening) of the remote

 

data

display cabling or by bad shield connections to ground.

 

 

Check shielding and shield connections. Ensure that only one

 

 

end of the cable shield is connected to ground.

 

 

If several remote displays are ‘daisy chained’ together then a

 

 

termination resistor may be required on the end display. (See

 

 

Section 4.4.3 in this chapter.)

 

 

 

Chequered

Wrong setting of

Refer to Section 2.3 in Chapter 2 and ensure that the switch is set

pattern on red

‘Number of

correctly. If the display still shows a chequered pattern then a

and green LED

Electrodes’ switch

circuit fault exists on the 2468 display board. Remove this board

display

on 2468 display

and fit a serviceable replacement.

 

board.

 

On/off pattern on

Wrong setting of

As above.

red and green

‘Number of

 

LEDs.

Electrodes’ switch

If a fault is not found, check the link setting on the 24683BB and

 

on 2468 display

reset the links if necessary.

 

board, or wrong

 

 

setting of links LK1,

 

 

LK2, LK3 and LK4

 

 

on the 24683BB

 

 

decoding pcb.

 

Indication not

 

As above.

displayed for

As above.

lower electrodes.

 

 

Each electrode

 

 

represented by

 

 

only one LED

As above.

As above.

when 16 or less

 

 

 

electrodes are

 

 

used.

 

 

LEDs display an

 

 

irregular

As above.

As above.

red/green

 

 

 

pattern.

 

 

Table 4.1 (cont.) - Fault Analysis and Correction Chart

24685034

4-15

Page 133
Image 133
Emerson 2468CD, 2468CB manual 4-15, Flickering Display