Hydrastep 2468CB & 2468CD Manual | Remote Display Options 24683B, C & D |
Indication | Fault | Analysis and Corrective Action |
|
|
|
Flickering Display | Corruption of signal | Most probably caused by bad shielding (screening) of the remote |
| data | display cabling or by bad shield connections to ground. |
|
| Check shielding and shield connections. Ensure that only one |
|
| end of the cable shield is connected to ground. |
|
| If several remote displays are ‘daisy chained’ together then a |
|
| termination resistor may be required on the end display. (See |
|
| Section 4.4.3 in this chapter.) |
|
|
|
Chequered | Wrong setting of | Refer to Section 2.3 in Chapter 2 and ensure that the switch is set |
pattern on red | ‘Number of | correctly. If the display still shows a chequered pattern then a |
and green LED | Electrodes’ switch | circuit fault exists on the 2468 display board. Remove this board |
display | on 2468 display | and fit a serviceable replacement. |
| board. |
|
On/off pattern on | Wrong setting of | As above. |
red and green | ‘Number of |
|
LEDs. | Electrodes’ switch | If a fault is not found, check the link setting on the 24683BB and |
| on 2468 display | reset the links if necessary. |
| board, or wrong |
|
| setting of links LK1, |
|
| LK2, LK3 and LK4 |
|
| on the 24683BB |
|
| decoding pcb. |
|
Indication not |
| As above. |
displayed for | As above. | |
lower electrodes. |
|
|
Each electrode |
|
|
represented by |
|
|
only one LED | As above. | As above. |
when 16 or less |
| |
|
| |
electrodes are |
|
|
used. |
|
|
LEDs display an |
|
|
irregular | As above. | As above. |
red/green |
| |
|
| |
pattern. |
|
|
Table 4.1 (cont.) - Fault Analysis and Correction Chart
24685034 |
|