2.4.2.2Connecting Cables to Water Column Electrodes (16 Electrode System - See Page 2-WD.7)

The following assumes that the electrodes have been fitted to the water column.

1.Gain access to the electrodes mounted on the water column.

2.Undo both knurled nuts on the stud of the bottom electrode (referenced EL.1 on the drawings) and remove both the nuts and washers.

3.Take one of the brown (BN) conductors in Cable 1 and fit the ring clamp of the conductor over the stud, followed by a washer and a knurled nut. Tighten the nut to form a good secure contact, ensuring the conductor run to the cableform clamping bar is free from snags and sharp bends.

4.Repeat the operation for the remaining brown (BN) conductor of Cable 1.

5.Take the next electrode up, referenced EL.2 on the drawings, and repeat the operations detailed in paragraph 2 above.

6.Take the brown (BN) conductors of Cable 2 and repeat the fitting instructions detailed in paragraph 3 above.

7.Repeat the operations of paragraphs 2 and 3 for the remaining tabulated conductor/electrode pairings on the next page and connect as detailed on page 2-WD.7.

8.Check that all conductor runs affecting Cables 1 and 2 on the water column are satisfactory then clamp the cable securely to its clamping bar.

9.Refit any Electrode Protection Covers to the water column.

Water column connections for 16 electrodes

Electrode

Conductor

Cable

Enclosure

Number

Number

Number

Connection

1

 

Brown

1

PL2 pin 1

 

 

Brown

 

PL2 pin 2

2

 

Brown

2

PL2 pin 1

 

 

Brown

 

PL2 pin 2

3

 

Red

1

PL2 pin 4

 

 

Red

 

PL2 pin 5

4

 

Red

2

PL2 pin 4

 

 

Red

 

PL2 pin 5

5

 

Orange

1

PL2 pin 6

 

 

Orange

 

PL2 pin 7

6

 

Orange

2

PL2 pin 6

 

 

Orange

 

PL2 pin 7

7

 

Yellow

1

PL2 pin 9

 

 

Yellow

 

PL2 pin 10

8

 

Yellow

2

PL2 pin 9

 

 

Yellow

 

PL2 pin 10

9

 

Green

1

PL2 pin 9

 

 

Green

 

PL2 pin 10

Electrode

Conductor

Cable

Enclosure

Number

Number

Number

Connection

10

 

Green

2

PL3 pin 1

 

 

Green

 

PL3 pin 2

11

 

Blue

1

PL3 pin 4

 

 

Blue

 

PL3 pin 5

12

 

Blue

2

PL3 pin 4

 

 

Blue

 

PL3 pin 5

13

 

Purple

1

PL3 pin 6

 

 

Purple

 

PL3 pin 7

14

 

Purple

2

PL3 pin 6

 

 

Purple

 

PL3 pin 7

15

 

Grey

1

PL3 pin 9

 

 

Grey

 

PL3 pin 10

16

 

Grey

2

PL3 pin 9

 

 

Grey

 

PL3 pin 10

Earth

 

Black

1

PL2 pin 3

 

 

Black

 

PL2 pin 3

Earth

Black

2

PL2 pin 3

 

 

Black

 

PL2 pin 3

Note: There are two conductors of each colour per cable.

24685034

2-11

Page 31