Hydrastep 2468CB and 2468CD Manual

2468CB & 2468CD Dual Power Supply Version

Indication

Fault(s)

Analysis and Corrective Action

 

 

 

State 5

Electrode wiring or

Check that all odd numbered electrodes indicating

Bottom half of

internal fault

water have the correct pair of conductors connected.

 

Check the connections to the right hand input board.

fault LED

Odd numbered

Rectify wiring if incorrect.

illuminated

electrode

Check ac voltage on all odd electrodes immersed in

One or more

connection open-

circuit or

water with a true r.m.s. voltmeter. A voltage of less than

LED pairs

short-circuit to

0.1V ac indicates a fault condition.

alternating

earth

If wiring to all odd electrodes is correct and the

between water

 

and steam

Affected electrode

electrodes still give a voltage reading of greater than

 

alternates

0.1V ac and a fault is still indicated, carry out the

 

between water and

following procedure:

 

steam.

1. Remove both conductors from electrode 1. With the

 

 

 

Incorrect wiring,

conductors isolated from each other, the level

 

broken connection

display should show electrode 1 as being

 

or damaged cable

alternating between water and steam (green and

 

assembly

red).

 

 

2. With the conductors touching each other, the level

 

 

display should show electrode 1 as being in steam.

 

 

3. Repeat operations 1 and 2 for all affected odd

 

 

numbered electrodes until a faulty indication is

 

 

found.

 

 

The above procedure checks the electrode wiring. If the

 

 

display does not show the correct results, then check for

 

 

a break in either of the suspect electrode conductors.

 

 

Carry out repair to any faulty connection or substitute a

 

 

new conductor or cable assembly in place of the

 

 

defective item.

 

Dirt on electrode

If the wiring checks carried out as described above have

 

Affected electrode

not located a fault, then dirt on an electrode insulator

 

may be the cause of the problem giving an effective

 

alternates

 

short-circuit to ground.

 

between water and

 

steam.

Check all odd numbered electrodes alternating between

 

 

water and steam for dirt over the external insulator and

 

 

clean with a cloth as required.

 

 

Checking for dirt on the internal insulator of the

 

 

electrode requires the draining of the water column

 

 

(refer to the appropriate manual for the correct

 

 

procedure).

 

 

Once the water column is drained, check the ac voltage

 

 

on each odd numbered electrode using a true r.m.s.

 

 

voltmeter. Any electrode showing a voltage of less than

 

 

3V ac needs cleaning or replacement. Electrodes must

 

 

be removed from the column for inspection and

 

 

cleaning.

 

 

Note: The electrode insulator can be cleaned using a

 

 

clean cloth

Table 2.3 - Fault analysis/corrective action chart (continued)

24685034

2-27

Page 47
Image 47
Emerson 2468CD, 2468CB manual 2-27, Indication, Faults, Analysis and Corrective Action, State, Bottom half of, alternates