Hydrastep 2468CB and 2468CD Manual | 2468CB & 2468CD Dual Power Supply Version |
2.3.3.2Links LK2, LK3, LK4 and LK5
These links are used to select either the 8 - 16 display mode (two LEDs per electrode) or the 18 - 32 display mode (one LED per electrode).
Two link headers are provided with the unit and must be fitted in either LK2 and LK4, to enable the 8 - 16 electrode mode, or LK3 and LK5, to enable the 18 - 32 electrode mode.
| No. of Electrodes used | Link Headers fitted |
|
|
|
| 8 - 16 electrodes | LK 2 & LK 4 |
|
|
|
| 18 - 32 electrodes | LK 3 & LK 5 |
|
|
|
See also Figure 2.5 on page |
|
2.3.4PCB INTERCONNECTIONS
Signal interconnection between the input boards and the display board is via ribbon cables. The power supplies to the display board come from each input board via a
Slots are provided in the base plate to guide the cables towards the
24685034 |