Hydrastep 2468CB and 2468CD Manual | 2468CB & 2468CD Dual Power Supply Version |
Indication | Fault(s) | Analysis and Corrective Action | |
|
|
| |
State 1 (contd.) |
| 3. Insert these sockets in place of the electrode cable | |
|
| sockets in the input boards, the level display should | |
|
| now show an all steam state and no fault | |
|
| indication. If this does not occur an internal fault | |
|
| exists. | |
|
| The circuit fault may be on either input board or the | |
|
| display board. If spares are available, change the input | |
|
| board first and if the fault is not rectified change the | |
|
| display board. If spares are not available, call the | |
|
| service engineer. | |
|
|
| |
State 2 | Internal fault | This state is indicating a fault which is not related to an | |
Top and bottom |
| electrode error because no LED pairs are alternating | |
| between water and steam. It is therefore likely that an | ||
halves of fault |
| ||
| internal fault exists. | ||
LED illuminated |
| ||
| Follow same procedure as above. | ||
No LED pairs |
| ||
|
| ||
alternating |
|
| |
between water |
|
| |
and steam |
|
| |
State 3 | Electrode wiring or | Check that all even numbered electrodes indicating | |
Top half of fault | internal fault | water have the correct pair of conductors connected. | |
| Check the connections to the left hand input board. | ||
LED illuminated | Even numbered | ||
Rectify wiring if incorrect. | |||
One or more | electrode connection | ||
Check ac voltage on all even electrodes immersed in | |||
LED pairs | |||
water with a true r.m.s. voltmeter. A voltage of less than | |||
alternating | |||
| 0.1V ac indicates a fault condition. | ||
between water | Affected electrode | ||
If wiring to all even electrodes is correct and the | |||
and steam | alternates between | ||
| water and steam. | electrodes still give a voltage reading of greater than | |
| Incorrect wiring, | 0.1V ac and a fault is still indicated, carry out the | |
| following procedure: | ||
| broken connection or | ||
| damaged cable | 1. Remove both conductors from electrode 2. With the | |
| assembly | conductors isolated from each other, the level | |
|
| display should show electrode 2 as alternating | |
|
| between water and steam (green and red). | |
|
| 2. With the conductors touching each other, the level | |
|
| display should show electrode 2 as being in steam. | |
|
| 3. Repeat operations 1 and 2 for all affected even | |
|
| numbered electrodes until a faulty indication is | |
|
| found. | |
|
| The above procedure checks the electrode wiring. If | |
|
| the display does not show the correct results, then | |
|
| check for a break in either of the suspect electrode | |
|
| conductors. | |
|
| Carry out repair to any faulty connection or substitute a | |
|
| new conductor or cable assembly in place of the | |
|
| defective item. |
Table 2.3 - Fault analysis/corrective action chart (continued)
24685034 |
|