Emerson 2468CD, 2468CB manual 2-25, Indication

Models: 2468CD 2468CB

1 186
Download 186 pages 11.63 Kb
Page 45
Image 45

Hydrastep 2468CB and 2468CD Manual

2468CB & 2468CD Dual Power Supply Version

Indication

Fault(s)

Analysis and Corrective Action

 

 

 

State 1 (contd.)

 

3. Insert these sockets in place of the electrode cable

 

 

sockets in the input boards, the level display should

 

 

now show an all steam state and no fault

 

 

indication. If this does not occur an internal fault

 

 

exists.

 

 

The circuit fault may be on either input board or the

 

 

display board. If spares are available, change the input

 

 

board first and if the fault is not rectified change the

 

 

display board. If spares are not available, call the

 

 

service engineer.

 

 

 

State 2

Internal fault

This state is indicating a fault which is not related to an

Top and bottom

 

electrode error because no LED pairs are alternating

 

between water and steam. It is therefore likely that an

halves of fault

 

 

internal fault exists.

LED illuminated

 

 

Follow same procedure as above.

No LED pairs

 

 

 

alternating

 

 

between water

 

 

and steam

 

 

State 3

Electrode wiring or

Check that all even numbered electrodes indicating

Top half of fault

internal fault

water have the correct pair of conductors connected.

 

Check the connections to the left hand input board.

LED illuminated

Even numbered

Rectify wiring if incorrect.

One or more

electrode connection

Check ac voltage on all even electrodes immersed in

open-circuit or

LED pairs

short-circuit to earth

water with a true r.m.s. voltmeter. A voltage of less than

alternating

 

0.1V ac indicates a fault condition.

between water

Affected electrode

If wiring to all even electrodes is correct and the

and steam

alternates between

 

water and steam.

electrodes still give a voltage reading of greater than

 

Incorrect wiring,

0.1V ac and a fault is still indicated, carry out the

 

following procedure:

 

broken connection or

 

damaged cable

1. Remove both conductors from electrode 2. With the

 

assembly

conductors isolated from each other, the level

 

 

display should show electrode 2 as alternating

 

 

between water and steam (green and red).

 

 

2. With the conductors touching each other, the level

 

 

display should show electrode 2 as being in steam.

 

 

3. Repeat operations 1 and 2 for all affected even

 

 

numbered electrodes until a faulty indication is

 

 

found.

 

 

The above procedure checks the electrode wiring. If

 

 

the display does not show the correct results, then

 

 

check for a break in either of the suspect electrode

 

 

conductors.

 

 

Carry out repair to any faulty connection or substitute a

 

 

new conductor or cable assembly in place of the

 

 

defective item.

Table 2.3 - Fault analysis/corrective action chart (continued)

24685034

2-25

Page 45
Image 45
Emerson 2468CD, 2468CB manual 2-25, Indication