Remote Display Options 24683B, C & D | Hydrastep 2468CB & 2468CD Manual |
Indication | Fault | Analysis and Corrective Action |
|
|
|
Bottom half of fault | Power present, but | Check that the wiring to connector PL1 in the remote |
LED illuminated and | loss of serial data. | display unit is correct. |
odd LEDs flashing at |
| If wiring is correct, proceed as follows: |
1Hz, or odd LEDs off. |
| |
|
| |
|
| 1. If a termination resistor is fitted, disconnect this from |
|
| the end of the daisy chain. |
|
| 2. With an ac voltmeter, check the ac voltage between |
|
| pins 1and 5, and pins 2 and 5, on PL1. |
|
| 3. An ac voltage is less than 1V indicates a fault on the |
|
| signal transmission lines. Check back to the previous |
|
| remote display in the daisy chain or to the 2468 |
|
| electronics unit, as appropriate. If the correct ac |
|
| voltages are present at this location then a line break |
|
| is indicated. |
|
| 4. If the ac voltages are still low then either the lines are |
|
| |
|
| remote displays upstream and |
|
| voltages. If there is a voltage of less than 1Vac at the |
|
| 2468 electronics unit (with PL3 removed) then the |
|
| display board is faulty. Remove this board and fit a |
|
| serviceable item. |
|
|
|
Bottom half of fault | Power present, but | Check that the wiring to connector PL2 in the remote |
LED illuminated and | loss of serial data. | display unit is correct. |
even LEDs flashing at |
| If wiring is correct, proceed as follows: |
1Hz, or even LEDs off. |
| |
|
| |
|
| 1. If a termination resistor is fitted, disconnect this from |
|
| the end of the daisy chain. |
|
| 2. With an ac voltmeter, check the ac voltage between |
|
| pins 1and 5, and pins 2 and 5, on PL2. |
|
| 3. An ac voltage is less than 1V indicates a fault on the |
|
| signal transmission lines. Check back to the previous |
|
| remote display in the daisy chain or to the 2468 |
|
| electronics unit, as appropriate. If the correct ac |
|
| voltages are present at this location then a line break |
|
| is indicated. |
|
| 4. If the ac voltages are still low then either the lines are |
|
| |
|
| remote displays upstream and |
|
| voltages. If there is a voltage of less than 1Vac at the |
|
| 2468 electronics unit (with PL7 removed) then the |
|
| display board is faulty. Remove this board and fit a |
|
| serviceable item. |
|
|
|
Table 4.1 (cont.) - Fault Analysis and Correction Chart
| 24685034 |