Maintenance
Table 13 Battery retorque values
Battery | Battery | Retorque | |
Manufacturer | Model No. | Value | |
| 32 | ||
Dynasty | 52 | ||
52 | |||
| |||
| 100 | ||
C&D Batteries | 100 | ||
100 | |||
| |||
| HX205 | 60 | |
| HX300 | 60 | |
Enersys | HX370 | 60 | |
| HX400 | 60 | |
| HX500 | 60 |
If you have a different model battery, contact Liebert Global Services for the required torque value.
To access battery cell terminals, disconnect the
When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and insulate the cables connected to the battery. Secure each battery shelf with retaining screws when maintenance is complete.
Rack-Mounted Batteries
If the UPS system uses a battery other than a
Table 14 Battery voltage record
Date
Float Voltage (Volts DC)
Nominal Voltage (Volts DC)
Ambient Temp. (°F)
(To be completed by Liebert Global Services customer engineer at time of