Briggs & Stratton 71018, 71021 Maintenance, Specifications, UL 1008 Listed Transfer Switch Model

Page 11

Maintenance

The transfer switch is designed to be maintenance free under normal usage. However, inspection and maintenance checks should be made on a regular basis. Maintenance will consist mainly of keeping the transfer switch clean.

Visual inspections should be done at least once a month. Access to transfer switch must not be obstructed. Keep

3 feet (1 m) clearance around transfer switch. Check for an accumulation of dirt, moisture and/or corrosion on and

around the enclosure, loose parts/hardware, cracks and/or discoloration to insulation, and damaged or discolored components.

Exercise the transfer switch at least once every three months as described in section Testing the Automatic Transfer Switch unless a power outage occurs and home generator system has gone through an automatic sequence. Allow generator to run for at least 30 minutes.

Contact a licensed electrical professional to inspect and clean the inside of your transfer switch at least once a year.

Specifications

UL® 1008 Listed Transfer Switch

 

 

Model 071018

 

Model 071020

 

Maximum Load Current .

. . . . . . . . . . . . . . . . . . . .100 Amps

Maximum Load Current .

. . . . . . . . . . . . . . . . . . . .100 Amps

Rated AC Voltage

. . . . . . . . . . . . . . . . . . . . .250 Volts

Rated AC Voltage

. . . . . . . . . . . . . . . . . . . . .250 Volts

Poles

. . . . . . . . . . . . . . . . . . . . . . . . . . .2

Poles

. . . . . . . . . . . . . . . . . . . . . . . . . . .2

Frequency

. . . . . . . . . . . . . . . . . . . . .50/60 Hz

Frequency

. . . . . . . . . . . . . . . . . . . . .50/60 Hz

Fault Current Rating . . . .

22,000 RMS Symmetrical Amperes

Fault Current Rating . . . .

22,000 RMS Symmetrical Amperes

Supervisory Contacts Rating:

Supervisory Contacts Rating:

A-A Terminals

. . . . . . . . . . . . . . . . . . . .24 Volt AC

A-A Terminals

. . . . . . . . . . . . . . . . . . . .24 Volt AC

B-B Terminals

. . . .1 Amp, 125 Volt AC, Pilot Duty

B-B Terminals

. . . .1 Amp, 125 Volt AC, Pilot Duty

Weight

. . . . . . . . . . . . . . . . . . . . . . .21 lbs.

Weight

. . . . . . . . . . . . . . . . . . . . . . .32 lbs.

Model 071019

 

Model 071021

 

Maximum Load Current .

. . . . . . . . . . . . . . . . . . . .200 Amps

Maximum Load Current .

. . . . . . . . . . . . . . . . . . . .200 Amps

Rated AC Voltage

. . . . . . . . . . . . . . . . . . . . .250 Volts

Rated AC Voltage

. . . . . . . . . . . . . . . . . . . . .250 Volts

Poles

. . . . . . . . . . . . . . . . . . . . . . . . . . .2

Poles

. . . . . . . . . . . . . . . . . . . . . . . . . . .2

Frequency

. . . . . . . . . . . . . . . . . . . . .50/60 Hz

Frequency

. . . . . . . . . . . . . . . . . . . . .50/60 Hz

Fault Current Rating . . . .

25,000 RMS Symmetrical Amperes

Fault Current Rating . . . .

25,000 RMS Symmetrical Amperes

Supervisory Contacts Rating:

Supervisory Contacts Rating:

A-A Terminals

. . . . . . . . . . . . . . . . . . . .24 Volt AC

A-A Terminals

. . . . . . . . . . . . . . . . . . . .24 Volt AC

B-B Terminals

. . . .1 Amp, 125 Volt AC, Pilot Duty

B-B Terminals

. . . .1 Amp, 125 Volt AC, Pilot Duty

Weight

. . . . . . . . . . . . . . . . . . . . . . .34 lbs.

Weight

. . . . . . . . . . . . . . . . . . . . . . .44 lbs.

9

Image 11
Contents 100 AMP/200 AMP Call Transfer Switch Helpline BRIGGSandSTRATTON.COMDate Purchased Where to Find UsTransfer Switch Table of Contents Important Safety Instructions Owner Orientation Installer ResponsibilitiesIntroduction For the Home OwnerMounting Guidelines InstallationShipment Contents UnpackingAlternate Transfer Switch Mounting Utility Connnection Power Wiring InterconnectionsControls Supervisory Control WiringSystem Setup Automatic Sequence Testing the Automatic Transfer SwitchWhen Calling the Factory OperationSupervisory Contacts Rating MaintenanceSpecifications UL 1008 Listed Transfer Switch ModelProblem Cause Correction TroubleshootingSchematic and Wiring Diagram, Models 071018 Schematic and Wiring Diagram, Models 071020 Items Not Illustrated Illustrated Parts List, ModelDescription WASHER, Lock 1/4 190984GS DECAL, Fuse ENCLOSURE, 22 x 16 x 197355GS CLIP, Latching Wire192597GS DECAL, Utility 240VAC 196094GS 192166GSDECAL, UL Listed 193159GS DECAL, Reinstall Barrier 192151GS197355GS CLIP, Latching Wire ASSY, Enclosure 196520GS197294GS DECAL, Contacts Rating WASHER, Lock 1/4 192881GS 197355GS CLIP, Latching Wire 195728GSASSY, Enclosure 196521GS 192879GS INSULATION, Circuit Breaker 196094GSLimited Warranty Reserved Manual de Instalación Del Operario Fecha de compra Dónde puede encontrarnosConectador Automático Especificaciones MandosMantenimiento Instrucciones importantes de seguridad Conserve estas instruccionesResponsabilidades del Instalador IntroduccionPara el Propietario Doméstico Orientación para el PropietarioInspección al Momento de la Entrega InstalacionDesempaque Pautas de MontajeFigura 2 Montaje de un Conectador Alternativo Interconexiones de Cableado de Energía Cableado de Control de Supervisión Configuración del SistemaSecuencia Automática MandosSistema Funcionamiento Prueba del conectador automáticoCarga máxima/circuito MantenimientoEspecificaciones UL 1008 Listó Conectador ModeloReparacion de AveriasGarantía Garantía Limitada Reserved Guide dInstallation Et dUtilisation Date d’achat Où nous trouverCommutateur de Transfert Caractéristiques Commandes FonctionnementMise à lessai du commutateur de transfert automatique EntretienSécurité Instalación FonctionnementCommandesVeuillez conserver ces instructions Directives de sécurité importantesConseils au Propriétaire Responsabilités de lInstallateurIntroduction Au Propriétaire RésidentielDéballage Consignes dinstallationInstalación Commandes Vérification de la Livraison InstalationIté Rantie Interconnexions du câblage dalimentationIté EtienCâblage de contrôle Configuration du systèmeSéquence Automatique CommandesFonctionnement Mise à lessai du commutateur de transfert automatiqueModèle EntretienCaractéristiques UL 1008 Enuméré Commutateur de Transfert ModéleDepannage Garantie Limitée