APC VS 50 Rectifier Test, Battery Power Up, LVD Test, Circuit Breaker/ Fuse Test, User Inputs

Page 23

Rectifier Test:

1.To verify that all rectifiers are reporting correctly to the controller, navigate through the menu and verify that the status for every rectifier in the system is correct.

2.Remove any rectifier and verify that you get a Minor Relay Output for rectifier 1 of n failure.

3.Remove a second rectifier and verify that you get a Major Relay Output for rectifier 2 of n failure.

Battery Power Up

1.Monitor battery current and verify that it is +/- 0.1 A.

2.Set battery maximum recharge value in the Max Batt Rech screen.

3.Monitor the battery current while closing the battery disconnects or installing open battery links. Arcing can occur during this connection.

4.The voltage may drop if the maximum battery recharge current is exceeded.

5.The current should gradually decrease when the battery is nearing full charge.

LVD Test

1.Enable LVD 1.

2.Set the LVD trip for LVD 1 to negative 56 Vdc.

3.The LVD should have dropped out (opened). Verify by monitoring the voltage at the battery connection. Also, the minor alarm should be on.

4.Set LVD Trip back to negative 42 Vdc.

5.The LVD should have closed. Verify visually or by monitoring the voltage at the battery connection. The minor alarm should be off.

6.Ensure that the LVD parameters are set to desired value.

Circuit Breaker/ Fuse Test:

1.Monitor alarm screen for fuse alarm while installing blown GMT fuses in each position.

2.Verify proper voltage at fuse and circuit breaker output connections.

3.Turn on fuses and circuit breakers as desired.

User Inputs

1.Change the user input to desired output relay via the controller for any input that will be used.

2.Exercise the output relay by causing the user input to change state.

3.Verify the desired relay output LED on the controller module.

Magnum VS –48 Vdc User’s Manual

Page 18

Image 23
Contents Magnum VS Vdc Power Systems User’s Manual Table of Contents Final Inspection TWF0500H54B Rectifier Magnum VS Controller Document # & Rev Date Description Revision HistoryGeneral Precautions Safety FirstGeneral Information How to Use This ManualIntroduction Amp System Only Room / Location InstallationMechanical Installation Unpacking EquipmentAC Connections AC Power ConnectionsVentilation AWG AC Power Cord SetsConnecting the Cables Battery ConnectionsPlanning the Battery installation 1 Battery Cable Connection Locations Battery Temperature Probe InstallationDC System Grounding Counter Electro-Motive Force Cemf Cell ConnectionsGMT Fuse Installation Load Protection InstallationCircuit Breaker Installation GMT Fuse protected Load Connections Load ConnectionsCable Size Considerations Circuit Breaker Protected Load Connections 30 or 60 aMajor, Minor and Relay 1 Output Connections RJ45 Ethernet ConnectorMonitoring and Relay Output Connections Front Panel DB9 ConnectionRelay Terminal Relay Alias Output Relay Notes Designations Output Relay 2-6 ConnectionsExternal Alarm Input Connections Rectifier Module InstallationController Module Installation Pre-Commissioning Inspection Electrical InstallationBattery Visual and Safety Inspection CommissioningInitial Set-up AC Power UpDC Power Up CommissioningCircuit Breaker/ Fuse Test Battery Power UpRectifier Test LVD TestOutput Relay Battery Temperature CompensationFinal Inspection System Management Technical DescriptionRectifier Management Circuit Breakers System Status and Alarm ReportingLoad Management System Current MonitorGMT Fuses Battery ManagementBattery Charging Battery Temperature Monitoring Battery EqualizationBattery Protection Counter Electro-Motive Force Module Connections Battery Low Voltage DisconnectBattery Functional Test Controller without Display Controls and IndicatorsAlarm Outputs Output Relays Controller with DisplayNetwork Management Card Local & Remote Monitoring External Alarm Inputs User InputController Card Jumpers OperationDescription J12 J13 Controller with Display1 Controller with Display Operation using Local Display and Keypad Interface设置 / 电池 / 容量 设置 / 系统 / 时/日 均充 / 均充时间 状态 / 系统 /参数 Alarms 均充时间 Controller without Display Operation Using the RS-232 Comm PortOperation Using the 10/100 BaseT Ethernet Port 1 Parameter Locations, Descriptions, and Settings ON, OFF Power Modules/Rectifiers Seconds Disable Output Relay System/Preferences LVD OperationProgramming Output Relays Page Inspection Preventive MaintenanceSystem Visual and Safety Inspection EquipmentRectifier Current Share Test Rectifier Alarm TestTest System Voltage TestBattery Temperature Test System Temperature TestBattery Current Test Battery Preventive Maintenance Procedure Alarm Summary System LT Alm System Temperature is below Minor TWF0500H54B Rectifier SpecificationsMagnum VS 50 Power System AC InputDC Output Magnum VS 100 Power SystemMagnum VS 50 Power System Magnum VS Controller MechanicalEnvironmental EMC ComplianceAPC Worldwide Customer Support Limited Product Warranty