PARAMETER NAME/

DESCRIPTION

SETTINGS (Default

[MENU LOCATION]

 

settings in BOLD)

 

 

Hardware System Voltage

Defines the output relay that is energized

Ignore, Minor, Major

Alarm

if there is a hardware failure in the

Output Relay 1-6

[Power Modules/Rectifiers]

system voltage monitoring function.

 

Hardware Temperature Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[System/DC Parameters]

if there is a hardware failure in the

Output Relay 1-6

 

system temperature monitoring function.

 

High Temperature Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[System/DC Parameters]

if the System Temperature exceeds the

Output Relay 1-6

 

system high temperature threshold. Not

 

 

the same as battery temperature alarm.

 

High Temperature Threshold

Ambient temperature measured inside

0 °C – 100 °C, 70.0 °C

[System/DC Parameters]

the controller. An alarm will be reported

 

 

if temperature is higher than the

 

 

temperature entered. Not the same as

 

 

battery temperature threshold.

 

High Voltage alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Power Modules/Rectifiers]

if the System Voltage is above the

Output Relay 1-6

 

System High Voltage threshold. Not the

 

 

same as battery voltage alarm.

 

High Voltage Threshold

DC voltage measured by the controller.

-60 V – -40 V, -58.00 V

[Power Modules/Rectifiers]

An alarm will be reported if voltage is

 

 

higher than the voltage entered. Not the

 

 

same as battery voltage threshold.

 

Imbalance Alarm

An alarm will be generated if the rectifiers

Ignore, Minor, Major

[Power Modules/Rectifiers]

do not current share. This feature is

Output Relay 1-6

 

supported by the standard SNMP card

 

 

monitor, but is not supported by this dc

 

 

system.

 

Input Relay 1

Defines the output relay that is energized

Ignore, Minor, Major

[I/O/Input]

when an external contact closure or

Output Relay 1-6

 

opening at the Input Relay 1 connection

 

 

changes state.

Ignore, Minor, Major

Input Relay 4

Defines the output relay that is energized

Output Relay 1-6

[I/O/Input]

when an external contact closure or

 

 

opening at the Input Relay 4 connection

 

 

changes state.

 

Input Relay 1-4 Alias

This feature is supported by the standard

Input 1-4

[I/O/Input]

SNMP card monitor, but is not supported

 

 

by this dc system.

 

Input Relay 1-4 Delay

This feature is supported by the standard

0.00 Seconds

[I/O/Input]

SNMP card monitor, but is not supported

 

 

by this dc system.

 

Low Temperature Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[System/DC Parameters]

if the System Temperature is below the

Output Relay 1-6

 

System Low Temperature threshold. Not

 

 

the same as battery temperature alarm.

 

Magnum VS –48 Vdc User’s Manual

Page 41

Image 46
Contents Magnum VS Vdc Power Systems User’s Manual Table of Contents Final Inspection TWF0500H54B Rectifier Magnum VS Controller Revision History Document # & Rev Date DescriptionSafety First General PrecautionsIntroduction How to Use This ManualGeneral Information Amp System Only Unpacking Equipment InstallationMechanical Installation Room / LocationVentilation AC Power ConnectionsAC Connections AC Power Cord Sets AWGPlanning the Battery installation Battery ConnectionsConnecting the Cables Battery Temperature Probe Installation 1 Battery Cable Connection LocationsCounter Electro-Motive Force Cemf Cell Connections DC System GroundingCircuit Breaker Installation Load Protection InstallationGMT Fuse Installation Circuit Breaker Protected Load Connections 30 or 60 a Load ConnectionsCable Size Considerations GMT Fuse protected Load ConnectionsFront Panel DB9 Connection RJ45 Ethernet ConnectorMonitoring and Relay Output Connections Major, Minor and Relay 1 Output ConnectionsOutput Relay 2-6 Connections Relay Terminal Relay Alias Output Relay Notes DesignationsRectifier Module Installation External Alarm Input ConnectionsController Module Installation Commissioning Electrical InstallationBattery Visual and Safety Inspection Pre-Commissioning InspectionCommissioning AC Power UpDC Power Up Initial Set-upLVD Test Battery Power UpRectifier Test Circuit Breaker/ Fuse TestFinal Inspection Battery Temperature CompensationOutput Relay Rectifier Management Technical DescriptionSystem Management System Current Monitor System Status and Alarm ReportingLoad Management Circuit BreakersBattery Charging Battery ManagementGMT Fuses Battery Protection Battery EqualizationBattery Temperature Monitoring Battery Functional Test Battery Low Voltage DisconnectCounter Electro-Motive Force Module Connections Controller with Display Controls and IndicatorsAlarm Outputs Output Relays Controller without DisplayExternal Alarm Inputs User Input Network Management Card Local & Remote MonitoringDescription OperationController Card Jumpers Controller with Display J12 J13Operation using Local Display and Keypad Interface 1 Controller with Display设置 / 电池 / 容量 设置 / 系统 / 时/日 均充 / 均充时间 状态 / 系统 /参数 Alarms 均充时间 Operation Using the RS-232 Comm Port Controller without DisplayOperation Using the 10/100 BaseT Ethernet Port 1 Parameter Locations, Descriptions, and Settings ON, OFF Power Modules/Rectifiers Seconds Disable Output Relay LVD Operation System/PreferencesProgramming Output Relays Page Equipment Preventive MaintenanceSystem Visual and Safety Inspection InspectionSystem Voltage Test Rectifier Alarm TestTest Rectifier Current Share TestBattery Current Test System Temperature TestBattery Temperature Test Battery Preventive Maintenance Procedure Alarm Summary System LT Alm System Temperature is below Minor AC Input SpecificationsMagnum VS 50 Power System TWF0500H54B RectifierMagnum VS 100 Power System DC OutputMagnum VS 50 Power System Mechanical Magnum VS ControllerEnvironmental Compliance EMCAPC Worldwide Customer Support Limited Product Warranty