PARAMETER NAME/ | DESCRIPTION | SETTINGS (Default |
[MENU LOCATION] |
| settings in BOLD) |
|
| |
Current Limit Alarm Status | The status will be “ON” if the rectifier has | Status Only |
{Status Only} | been forced into its current limited mode. |
|
[Power Modules/Rectifiers] |
|
|
Date | Internal network management card | Current Date |
[System/Date & Time] | calendar date. Used as a date stamp in |
|
| the web card event log. |
|
Description 1 | Power plant identification - first line. |
|
[System/DC Parameters] |
|
|
Description 2 | Power plant identification - second line. | Magnum VS |
[System/DC Parameters] |
| This is not user |
Description 3 | Power plant identification - third line. | Power System |
[System/DC Parameters] |
| This is not user |
Fail Safe | If the rectifiers fail to communicate with | This feature is supported |
[Power Modules/Rectifiers] | the system, the rectifiers will output this | by the standard SNMP |
| card monitor, but is not | |
|
| supported by this dc |
|
| system. |
FUSE 1 Alias | An alternate name (alias) can be | FUSE 1 |
[Distribution/Fuses] | assigned to Fuse 1 if desired. This |
|
• | feature is supported by the standard | • |
• | SNMP card monitor, but is not supported | • |
• | by this dc system. | • |
FUSE 1 Alias |
| FUSE 16 |
[Distribution/Fuses] |
|
|
FUSE 1 Blown | Defines the output relay that is energized | Ignore, Minor, Major |
[Distribution/Fuses] | when | Output Relay |
• | • | • |
• | • | • |
• | • | • |
FUSE 4 Blown | Defines the output relay that is energized | Ignore, Minor, Major |
[Distribution/Fuses] | when | Output Relay |
|
| Fuse |
|
| this system |
Hardware Battery Current | Defines the output relay that is energized | Ignore, Minor, Major |
Alarm | if there is a hardware failure in the | Output Relay |
[Batteries Parameters] | battery current monitoring function. This |
|
| feature is supported by the standard |
|
| SNMP card monitor, but is not supported |
|
| by this dc system. |
|
Hardware Battery Temperature | Defines the output relay that is energized | Ignore, Minor, Major |
Alarm | if there is a hardware failure in the | Output Relay |
[Batteries Parameters] | battery temperature monitoring function. |
|
| Program to Ignore if no battery |
|
| temperature probe is connected to J410. |
|
Hardware LVD Alarm | Defines the output relay that is energized | Ignore, Minor, Major |
[Batteries/LVD] | if there is a conflict between the | Output Relay |
| commanded and sensed positions of the |
|
| LVD contactor. This feature is supported |
|
| by the standard SNMP card monitor, but |
|
| is not supported by this dc system. |
|
Magnum VS | Page 40 |