APC VS 50, VS 100 user manual Disable

Page 47

PARAMETER NAME/

DESCRIPTION

SETTINGS (Default

[MENU LOCATION]

 

settings in BOLD)

 

 

Low Temperature Threshold

System Temperature is ambient

-100 °C – 100 °C, 0.0 °C

[System/DC Parameters]

temperature measured inside the

 

 

controller. An alarm will be reported if

 

 

temperature is lower than the

 

 

temperature entered. Not the same as

 

 

battery temperature threshold.

 

Low Voltage Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Power Modules/Rectifiers]

if the System Voltage is below the

Output Relay 1-6

 

System Low Voltage threshold. Not the

 

 

same as battery voltage alarm.

 

Low Voltage Threshold

System Voltage is bus voltage measured

-60 V – -40 V, -50.00 V

[Power Modules/Rectifiers]

by the controller. An alarm will be

 

 

reported if voltage is lower than the

 

 

voltage entered. Not the same as battery

 

 

voltage threshold.

 

LVD 1 Option

If the unit has an LVD, but it is disabled,

Enable, Disable

[Batteries/LVD]

the controller will not disconnect the LVD.

 

LVD 1 Reset

LVD Reset (reconnect) threshold voltage.

-56 V – -40 V, -50.00 V

[Batteries/LVD]

 

 

LVD 1 Trip

LVD Trip (disconnect) threshold voltage.

-56 V – -40 V, -42.00 V

[Batteries/LVD]

 

 

LVD 2 Option

Not available on this system.

Disable

[Batteries/LVD]

 

 

LVD 2 Reset

Not available on this system.

0.00 V

[Batteries/LVD]

 

 

LVD 2 Trip

Not available on this system.

0.00 V

[Batteries/LVD]

 

 

LVD Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Batteries/LVD]

when the controller opens the LVD. If

Output Relay 1-6

 

unit has a battery LVD, no power will be

 

 

available to turn on any Output Relays.

 

Output Relay 1 Alarm

Output Relay 1 Alarm can be “mapped”

Ignore, Minor, Major

[I/O/Output]

to activate other output relays (“Ignore”

Output Relay 1-6

 

activates no additional relays).

 

 

 

 

Output Relay 2 Alarm

Output Relay 2-6 Alarm can be “mapped”

Ignore, Minor, Major

[I/O/Output]

to activate other output relays (“Ignore”

Output Relay 1-6

activates no additional relays). Alarms

 

that are mapped to output relay 2-6 are

 

not supported by hardware. The network

management card supports programming

Output Relay 6 Alarm

these relays. These relays can be

[I/O/Output]

mapped to the hardware relays minor

Ignore, Minor, Major

 

and major.

Output Relay 1-6

 

 

 

Magnum VS –48 Vdc User’s Manual

Page 42

Image 47
Contents Magnum VS Vdc Power Systems User’s Manual Table of Contents Final Inspection TWF0500H54B Rectifier Magnum VS Controller Document # & Rev Date Description Revision HistoryGeneral Precautions Safety FirstGeneral Information How to Use This ManualIntroduction Amp System Only Room / Location InstallationMechanical Installation Unpacking EquipmentAC Connections AC Power ConnectionsVentilation AWG AC Power Cord SetsConnecting the Cables Battery ConnectionsPlanning the Battery installation 1 Battery Cable Connection Locations Battery Temperature Probe InstallationDC System Grounding Counter Electro-Motive Force Cemf Cell ConnectionsGMT Fuse Installation Load Protection InstallationCircuit Breaker Installation GMT Fuse protected Load Connections Load ConnectionsCable Size Considerations Circuit Breaker Protected Load Connections 30 or 60 aMajor, Minor and Relay 1 Output Connections RJ45 Ethernet ConnectorMonitoring and Relay Output Connections Front Panel DB9 ConnectionRelay Terminal Relay Alias Output Relay Notes Designations Output Relay 2-6 ConnectionsExternal Alarm Input Connections Rectifier Module InstallationController Module Installation Pre-Commissioning Inspection Electrical InstallationBattery Visual and Safety Inspection CommissioningInitial Set-up AC Power UpDC Power Up CommissioningCircuit Breaker/ Fuse Test Battery Power UpRectifier Test LVD TestOutput Relay Battery Temperature CompensationFinal Inspection System Management Technical DescriptionRectifier Management Circuit Breakers System Status and Alarm ReportingLoad Management System Current MonitorGMT Fuses Battery ManagementBattery Charging Battery Temperature Monitoring Battery EqualizationBattery Protection Counter Electro-Motive Force Module Connections Battery Low Voltage DisconnectBattery Functional Test Controller without Display Controls and IndicatorsAlarm Outputs Output Relays Controller with DisplayNetwork Management Card Local & Remote Monitoring External Alarm Inputs User InputController Card Jumpers OperationDescription J12 J13 Controller with Display1 Controller with Display Operation using Local Display and Keypad Interface设置 / 电池 / 容量 设置 / 系统 / 时/日 均充 / 均充时间 状态 / 系统 /参数 Alarms 均充时间 Controller without Display Operation Using the RS-232 Comm PortOperation Using the 10/100 BaseT Ethernet Port 1 Parameter Locations, Descriptions, and Settings ON, OFF Power Modules/Rectifiers Seconds Disable Output Relay System/Preferences LVD OperationProgramming Output Relays Page Inspection Preventive MaintenanceSystem Visual and Safety Inspection EquipmentRectifier Current Share Test Rectifier Alarm TestTest System Voltage TestBattery Temperature Test System Temperature TestBattery Current Test Battery Preventive Maintenance Procedure Alarm Summary System LT Alm System Temperature is below Minor TWF0500H54B Rectifier SpecificationsMagnum VS 50 Power System AC InputDC Output Magnum VS 100 Power SystemMagnum VS 50 Power System Magnum VS Controller MechanicalEnvironmental EMC ComplianceAPC Worldwide Customer Support Limited Product Warranty