APC VS 100, VS 50 user manual Output Relay

Page 48

PARAMETER NAME/

DESCRIPTION

SETTINGS (Default

[MENU LOCATION]

 

settings in BOLD)

 

 

Output Relay 1 Alias

An alternate name (alias) can be

Output Relay 1

[System/Out-Rly/Alias]

assigned to Output Relay 1 if desired.

 

 

Output Relay 6 Alias

An alternate name (alias) can be

Output Relay 6

[System/Out-Rly/Alias]

assigned to Output Relay 6 if desired.

 

Output Relay 1 Delay

Delay between sensing of the alarm

0.00 seconds – 600.00

[I/O/Output]

condition and activation of the mapped

seconds, 0.00 seconds

relay. An alarm condition must exist for

 

longer than the delay to be activated.

 

 

 

Output Relay 6 Delay

 

 

[I/O/Output]

 

 

Rectifier 1-of-N Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Power Modules/Rectifiers]

if Rectifier Fail 1-of-N alarm occurs. This

Output Relay 1-6

 

is a special rectifier alarm group that

 

 

signifies that one rectifier has at least

 

 

one alarm condition.

 

Rectifier 2-of-N Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Power Modules/Rectifiers]

if Rectifier Fail 2-of-N alarm occurs This

Output Relay 1-6

 

is a special rectifier alarm group that

 

 

signifies that more than one rectifier has

 

 

at least one alarm condition.

 

Rectifier Configuration Alarm

Defines the output relay that is that is

Ignore, Minor, Major

[Power Modules/Rectifiers]

energized a rectifier is added to any

Output Relay 1-6, n of N

 

empty slot after the dc system is

 

 

powered up or configured. This feature

 

 

is supported by the standard SNMP card

 

 

monitor, but is not supported by this dc

 

 

system.

 

Rectifier Current Limit Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Power Modules/Rectifiers]

or special rectifier alarm group n of N that

Output Relay 1-6, n of N

 

occurs when a rectifier has been forced

 

 

into the current limited mode.

 

Rectifier Current Output Status

A display of the dc output current for the

Status Only

{Status Only}

individual rectifier.

 

[Power Modules/Rectifiers]

 

 

Rectifier Description

Displays the model number of the

Status Only

{Status Only}

installed rectifier.

 

[Power Modules/Rectifiers]

 

 

Rectifier Diagnostic Alarm

This feature is not needed in this

Ignore, Minor, Major

[Power Modules/Rectifiers]

particular configuration.

Output Relay 1-6, n of N

Rectifier Fan Fail Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Power Modules/Rectifiers]

or special rectifier alarm group n of N that

Output Relay 1-6,n of N

 

occurs when a rectifier fan has failed.

 

Rectifier Fan Fail Alarm Status

The status will be “ON” if the rectifier fan

Status Only

{Status Only}

has failed.

 

[Power Modules/Rectifiers]

 

 

Magnum VS –48 Vdc User’s Manual

Page 43

Image 48
Contents Magnum VS Vdc Power Systems User’s Manual Table of Contents Final Inspection TWF0500H54B Rectifier Magnum VS Controller Revision History Document # & Rev Date DescriptionSafety First General PrecautionsHow to Use This Manual IntroductionGeneral Information Amp System Only Installation Mechanical InstallationUnpacking Equipment Room / LocationAC Power Connections VentilationAC Connections AC Power Cord Sets AWGBattery Connections Planning the Battery installationConnecting the Cables Battery Temperature Probe Installation 1 Battery Cable Connection LocationsCounter Electro-Motive Force Cemf Cell Connections DC System GroundingLoad Protection Installation Circuit Breaker InstallationGMT Fuse Installation Load Connections Cable Size ConsiderationsCircuit Breaker Protected Load Connections 30 or 60 a GMT Fuse protected Load ConnectionsRJ45 Ethernet Connector Monitoring and Relay Output ConnectionsFront Panel DB9 Connection Major, Minor and Relay 1 Output ConnectionsOutput Relay 2-6 Connections Relay Terminal Relay Alias Output Relay Notes DesignationsRectifier Module Installation External Alarm Input ConnectionsController Module Installation Electrical Installation Battery Visual and Safety InspectionCommissioning Pre-Commissioning InspectionAC Power Up DC Power UpCommissioning Initial Set-upBattery Power Up Rectifier TestLVD Test Circuit Breaker/ Fuse TestBattery Temperature Compensation Final InspectionOutput Relay Technical Description Rectifier ManagementSystem Management System Status and Alarm Reporting Load ManagementSystem Current Monitor Circuit BreakersBattery Management Battery ChargingGMT Fuses Battery Equalization Battery ProtectionBattery Temperature Monitoring Battery Low Voltage Disconnect Battery Functional TestCounter Electro-Motive Force Module Connections Controls and Indicators Alarm Outputs Output RelaysController with Display Controller without DisplayExternal Alarm Inputs User Input Network Management Card Local & Remote MonitoringOperation DescriptionController Card Jumpers Controller with Display J12 J13Operation using Local Display and Keypad Interface 1 Controller with Display设置 / 电池 / 容量 设置 / 系统 / 时/日 均充 / 均充时间 状态 / 系统 /参数 Alarms 均充时间 Operation Using the RS-232 Comm Port Controller without DisplayOperation Using the 10/100 BaseT Ethernet Port 1 Parameter Locations, Descriptions, and Settings ON, OFF Power Modules/Rectifiers Seconds Disable Output Relay LVD Operation System/PreferencesProgramming Output Relays Page Preventive Maintenance System Visual and Safety InspectionEquipment InspectionRectifier Alarm Test TestSystem Voltage Test Rectifier Current Share TestSystem Temperature Test Battery Current TestBattery Temperature Test Battery Preventive Maintenance Procedure Alarm Summary System LT Alm System Temperature is below Minor Specifications Magnum VS 50 Power SystemAC Input TWF0500H54B RectifierMagnum VS 100 Power System DC OutputMagnum VS 50 Power System Mechanical Magnum VS ControllerEnvironmental Compliance EMCAPC Worldwide Customer Support Limited Product Warranty