ALARM/ | DESCRIPTION | DEFAULT SETTINGS |
[MENU LOCATION] |
|
|
System LT Alm | The System Temperature is below the | Minor |
[System/DC Parameters] | System Low Temperature threshold. Not |
|
| the same as battery temperature alarm. |
|
Low Voltage Alarm | The System Voltage is below the System | Minor |
[Power Modules/Rectifiers] | Low Voltage threshold. Not the same as |
|
| battery voltage alarm. |
|
LVD Alarm | The controller opened the LVD. If unit | Major |
[Batteries/LVD] | has a battery LVD, no power will be |
|
| available to turn on any Output Relays. |
|
User Output Relay 1 Alarm | Output Relay 1 Alarm can be “mapped” | Ignore |
[I/O/Output] | to activate other output relays (“Ignore” |
|
| activates no additional relays). |
|
Rectifier | Rectifier Fail | Minor |
[Power Modules/Rectifiers] | a special rectifier alarm group that |
|
| signifies that one rectifier has at least |
|
| one alarm condition. |
|
Rectifier | Rectifier Fail | Major |
[Power Modules/Rectifiers] | a special rectifier alarm group that |
|
| signifies that more than one rectifier has |
|
| at least one alarm condition. |
|
Rectifier Current Limit Alarm | A rectifier is in the current limited mode. | n of N |
[Power Modules/Rectifiers] |
|
|
Rectifier Fan Fail Alm | A rectifier fan has failed. | n of N |
[Power Modules/Rectifiers] |
|
|
Rectifier RFA Alarm | A rectifier output has failed. | n of N |
[Power Modules/Rectifiers] |
|
|
Magnum VS | Page 52 |