3.8. Load Connections
Cable Size Considerations
The dc load cable(s) should be sized to limit the voltage drop from the dc power plant to the loads per system design requirements. The cable(s) must also carry the full load current during battery operation. During battery operation the voltage will be lower and for constant power loads, the current will typically be higher. If assistance is required to determine the necessary cables for the application, contact your sales representative or APC.
Circuit Breaker Protected Load Connections (30 or 60 A)
The circuit breaker lug landing connection provides a pair of
Load Returns
Figure 3.8-1 Connections to Circuit Breakers
GMT Fuse protected Load Connections
Connections for ¼ to