APC VS 50, VS 100 user manual Parameter Locations, Descriptions, and Settings

Page 43

Figure 6.8-1 Parameter Locations, Descriptions, and Settings

PARAMETER NAME/

DESCRIPTION

SETTINGS (Default

[MENU LOCATION]

 

settings in BOLD)

 

 

Alarms Item 1

Display of up to 16 active alarms (a

No Alarms

{Status Only}

typical alarm screen is shown).

[System/Active Alarms]

No Alarms

Display of up to 16 active alarms (a

 

Alarms Item 16

typical alarm screen is shown).

 

[System/Active Alarms]

 

 

Battery Current

Battery current measured by the system

Status Only

{Status Only}

controller at the battery current shunt.

 

[System/DC Parameters]

 

 

Battery Discharge Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Batteries/Parameters]

if the battery discharge current exceeds

Output Relay 1-6

 

the programmed battery discharge

 

 

threshold.

 

Battery Discharge Threshold

An alarm is generated if the battery

0 A – 20A, 5 A

[Batteries/Parameters]

discharge current exceeds this value.

 

Battery Float Voltage

One of three parameters that control the

-56.5-47.0, -54.00 V

[Batteries/Parameters]

dc output voltage. Set the Float Voltage

 

 

at 25°C battery temperature per the

 

 

battery manufacturers recommendations.

 

Battery High Temperature

Defines the output relay that is energized

Ignore, Minor, Major

Alarm

if the battery temperature exceeds the

Output Relay 1-6

[Batteries/Parameters]

Battery High Temperature threshold.

 

Battery High Temperature

Battery Temperature is temperature

-100 °C – 200 °C, 40.0 °C

Threshold

measured at the battery probe. An alarm

 

[Batteries/Parameters]

is generated if the battery temperature

 

 

exceeds this value.

 

Battery High Voltage Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Batteries/Parameters]

if the dc output voltage rises above the

Output Relay 1-6

 

battery high voltage threshold.

 

Battery High Voltage Threshold

An alarm will be reported if temperature

-40.00 V – -60.00 V, -

[Batteries/Parameters]

is lower than the temperature entered.

58.00 V

 

An alarm is generated if the dc output

 

 

voltage rises above this value.

 

Battery Low Temperature

Defines the output relay that is energized

Ignore, Minor, Major

Alarm

if the Battery Temperature drops below

Output Relay 1-6

[Batteries/Parameters]

the battery Low Temperature threshold.

 

Battery Low Temperature

Battery Temperature is temperature

-100 °C – 200 °C, -20.0

Threshold

measured at the battery probe. An alarm

°C

[Batteries/Parameters]

is generated if the battery temperature

 

 

drops below this value.

 

Battery Low Voltage Alarm

Defines the output relay that is energized

Ignore, Minor, Major

[Batteries/Parameters]

if the dc output voltage drops below the

Output Relay 1-6

 

battery low voltage threshold.

 

Battery Low Voltage Threshold

An alarm is generated if the dc output

-40.00 V – -60.00 V,

[Batteries/Parameters]

voltage drops below this value.

-44.00 V

Magnum VS –48 Vdc User’s Manual

Page 38

Image 43
Contents Magnum VS Vdc Power Systems User’s Manual Table of Contents Final Inspection TWF0500H54B Rectifier Magnum VS Controller Document # & Rev Date Description Revision HistoryGeneral Precautions Safety FirstIntroduction How to Use This ManualGeneral Information Amp System Only Room / Location InstallationMechanical Installation Unpacking EquipmentVentilation AC Power ConnectionsAC Connections AWG AC Power Cord SetsPlanning the Battery installation Battery ConnectionsConnecting the Cables 1 Battery Cable Connection Locations Battery Temperature Probe InstallationDC System Grounding Counter Electro-Motive Force Cemf Cell ConnectionsCircuit Breaker Installation Load Protection InstallationGMT Fuse Installation GMT Fuse protected Load Connections Load ConnectionsCable Size Considerations Circuit Breaker Protected Load Connections 30 or 60 aMajor, Minor and Relay 1 Output Connections RJ45 Ethernet ConnectorMonitoring and Relay Output Connections Front Panel DB9 ConnectionRelay Terminal Relay Alias Output Relay Notes Designations Output Relay 2-6 ConnectionsExternal Alarm Input Connections Rectifier Module InstallationController Module Installation Pre-Commissioning Inspection Electrical InstallationBattery Visual and Safety Inspection CommissioningInitial Set-up AC Power UpDC Power Up CommissioningCircuit Breaker/ Fuse Test Battery Power UpRectifier Test LVD TestFinal Inspection Battery Temperature CompensationOutput Relay Rectifier Management Technical DescriptionSystem Management Circuit Breakers System Status and Alarm ReportingLoad Management System Current MonitorBattery Charging Battery ManagementGMT Fuses Battery Protection Battery EqualizationBattery Temperature Monitoring Battery Functional Test Battery Low Voltage DisconnectCounter Electro-Motive Force Module Connections Controller without Display Controls and IndicatorsAlarm Outputs Output Relays Controller with DisplayNetwork Management Card Local & Remote Monitoring External Alarm Inputs User InputDescription OperationController Card Jumpers J12 J13 Controller with Display1 Controller with Display Operation using Local Display and Keypad Interface设置 / 电池 / 容量 设置 / 系统 / 时/日 均充 / 均充时间 状态 / 系统 /参数 Alarms 均充时间 Controller without Display Operation Using the RS-232 Comm PortOperation Using the 10/100 BaseT Ethernet Port 1 Parameter Locations, Descriptions, and Settings ON, OFF Power Modules/Rectifiers Seconds Disable Output Relay System/Preferences LVD OperationProgramming Output Relays Page Inspection Preventive MaintenanceSystem Visual and Safety Inspection EquipmentRectifier Current Share Test Rectifier Alarm TestTest System Voltage TestBattery Current Test System Temperature TestBattery Temperature Test Battery Preventive Maintenance Procedure Alarm Summary System LT Alm System Temperature is below Minor TWF0500H54B Rectifier SpecificationsMagnum VS 50 Power System AC InputDC Output Magnum VS 100 Power SystemMagnum VS 50 Power System Magnum VS Controller MechanicalEnvironmental EMC ComplianceAPC Worldwide Customer Support Limited Product Warranty