APC VS 50, VS 100 user manual Rectifier Module Installation, External Alarm Input Connections

Page 19

OUT RELAY #6

N/A

 

 

 

NO

N/A

 

MINOR

C

N/A

 

 

NC

N/A

 

 

NO

N/A

 

MAJOR

C

N/A

 

 

NC

N/A

 

Figure 3.9-3 Output Relay Connections

External Alarm Input Connections

Four external alarm inputs with assignable relay outputs are available. User 1 and 2 inputs respond only to external dry contact closures between normally open (NO) and common (C) and User 3 and 4 respond only to external dry contact openings between normally closed (NC) and

C.A Wago connector is located on the backplane card mounted in the left rear of the unit. The Wago connectors accept wires 26 AWG to 20 AWG (0.129mm2 to 0.518 mm2). To connect the user input, remove ¼ in (6mm) of insulation from the end of the wire. Push down the white tab on the Wago connector, insert the stripped wire and release the tab to make the connection. Refer to Figure 3.9-1for backplane board connections.

EXTERNAL ALARM

J412 TERMINAL

USER ALARM NOTES

INPUT

DESIGNATIONS

 

#1 NO

USER1NO

 

#2 NO

USER2NO

 

#3 NC

USER3NC

 

#4 NC

USER4NC

 

#1 C

USER1C

 

#2 C

USER2C

 

#3 C

USER3C

 

#4 C

USER4C

 

Figure 3.9-5 External User Input Connections

3.10.Rectifier Module Installation

WARNING: Rectifier dc output circuits will be damaged if battery is installed incorrectly. Before rectifier installation, ensure proper battery polarity and that the battery is isolated from the rest of the system

The rectifier modules are shipped in separate containers. Follow the procedure below to install a rectifier module. Rectifiers may be installed even when the system is energized.

1) Remove the rectifier from its shipping container.

Magnum VS –48 Vdc User’s Manual

Page 14

Image 19
Contents Magnum VS Vdc Power Systems User’s Manual Table of Contents Final Inspection TWF0500H54B Rectifier Magnum VS Controller Document # & Rev Date Description Revision HistoryGeneral Precautions Safety FirstIntroduction How to Use This ManualGeneral Information Amp System Only Room / Location InstallationMechanical Installation Unpacking EquipmentVentilation AC Power ConnectionsAC Connections AWG AC Power Cord SetsPlanning the Battery installation Battery ConnectionsConnecting the Cables 1 Battery Cable Connection Locations Battery Temperature Probe InstallationDC System Grounding Counter Electro-Motive Force Cemf Cell ConnectionsCircuit Breaker Installation Load Protection InstallationGMT Fuse Installation GMT Fuse protected Load Connections Load ConnectionsCable Size Considerations Circuit Breaker Protected Load Connections 30 or 60 aMajor, Minor and Relay 1 Output Connections RJ45 Ethernet ConnectorMonitoring and Relay Output Connections Front Panel DB9 ConnectionRelay Terminal Relay Alias Output Relay Notes Designations Output Relay 2-6 ConnectionsExternal Alarm Input Connections Rectifier Module InstallationController Module Installation Pre-Commissioning Inspection Electrical InstallationBattery Visual and Safety Inspection CommissioningInitial Set-up AC Power UpDC Power Up CommissioningCircuit Breaker/ Fuse Test Battery Power UpRectifier Test LVD TestFinal Inspection Battery Temperature CompensationOutput Relay Rectifier Management Technical DescriptionSystem Management Circuit Breakers System Status and Alarm ReportingLoad Management System Current MonitorBattery Charging Battery ManagementGMT Fuses Battery Protection Battery EqualizationBattery Temperature Monitoring Battery Functional Test Battery Low Voltage DisconnectCounter Electro-Motive Force Module Connections Controller without Display Controls and IndicatorsAlarm Outputs Output Relays Controller with DisplayNetwork Management Card Local & Remote Monitoring External Alarm Inputs User InputDescription OperationController Card Jumpers J12 J13 Controller with Display1 Controller with Display Operation using Local Display and Keypad Interface设置 / 电池 / 容量 设置 / 系统 / 时/日 均充 / 均充时间 状态 / 系统 /参数 Alarms 均充时间 Controller without Display Operation Using the RS-232 Comm PortOperation Using the 10/100 BaseT Ethernet Port 1 Parameter Locations, Descriptions, and Settings ON, OFF Power Modules/Rectifiers Seconds Disable Output Relay System/Preferences LVD OperationProgramming Output Relays Page Inspection Preventive MaintenanceSystem Visual and Safety Inspection EquipmentRectifier Current Share Test Rectifier Alarm TestTest System Voltage TestBattery Current Test System Temperature TestBattery Temperature Test Battery Preventive Maintenance Procedure Alarm Summary System LT Alm System Temperature is below Minor TWF0500H54B Rectifier SpecificationsMagnum VS 50 Power System AC InputDC Output Magnum VS 100 Power SystemMagnum VS 50 Power System Magnum VS Controller MechanicalEnvironmental EMC ComplianceAPC Worldwide Customer Support Limited Product Warranty