APC VS 50, VS 100 user manual 均充 / 均充时间

Page 37

PARAMETER NAME/

DESCRIPTION

SETTINGS (Default

[MENU LOCATION]

 

Settings in BOLD)

 

 

Equalization Duration

This setting defines the number of hours

00 HOURS- 24 HOURS,

[SETUP/BATTERY/

the batteries will be equalized in all

0 HOURS

VOLTAGE/EQUALIZATION/

methods of equalization. During the

 

DURATION]

initial stage of equalization the batteries

 

[设置 / 电池 / 电压 /

will have to be increased to the

 

equalization voltage. Once the battery

 

均充 / 均充时间]

voltage and current meet equalization

 

parameters, the equalization duration

 

 

timer will start.

 

Equalize Manually

Applies an overcharge to the battery to

ON, OFF

[SETUP/BATTERY/

equalize the specific gravity of a battery.

 

VOLTAGE/EQUALIZATION/

Manual equalization is a one-time

 

METHOD/MANUAL]

equalization process. The operator turns

 

[设置 / 电池 /电压 /

on manual equalization each time he

 

wishes an unscheduled equalization to

 

均充 / 模式 /手动]

occur. To abort an automatic or periodic

 

equalization in progress, turn manual

 

 

equalization ON and then OFF.

 

Equalize Periodically

Applies an overcharge to the battery to

ON, OFF;

[SETUP/BATTERY/

equalize the specific gravity of a battery.

0-180 Days, 180 Days

VOLTAGE/EQUALIZATION/

Periodic equalization is equalization after

 

METHOD/PERIODIC]

a set number of days.

 

[设置 / 电池 /电压 /

 

 

均充 / 模式 /周期]

 

 

 

 

 

Equalization Voltage

The overcharge voltage that will be

-56.5 V - -48.0 V, -56.0 V

[SETUP/BATTERY/

applied to the battery

 

VOLTAGE/EQUALIZATION/

 

 

VOLTAGE]

 

 

[设置 / 电池 / 电压 /

 

 

均充 / 电压]

 

 

 

 

 

Language Selection

The screen will revert to the language

 

 

selection screen after a reset. Choices

 

 

are English and Chinese.

 

Pin Entry

Enter PIN to access setup menus.

0000 – 9999, 2222

[SETUP]

Entering setup brings you to the PIN

 

[设置]

entry screen. In-activity for two minutes

 

will de-activate system access.

 

PIN Setup

Change PIN that the user will use to log

0000 – 9999, 2222

[SETUP/SYSTEM/SET PIN]

on to the system. If you change the PIN,

 

[设置 / 系统 / 码设置]

Do Not Forget It.

 

 

 

 

 

 

Rectifier Current Limit Status

A display of the current limit alarm for the

Rectifier Current Limit

{Status Only}

individual rectifier. Scroll up or down to

Status Only

[STATUS/RECT]

select individual rectifiers.

 

[ 状态 / 模块]

 

 

 

 

 

Magnum VS –48 Vdc User’s Manual

Page 32

Image 37
Contents Magnum VS Vdc Power Systems User’s Manual Table of Contents Final Inspection TWF0500H54B Rectifier Magnum VS Controller Document # & Rev Date Description Revision HistoryGeneral Precautions Safety FirstIntroduction How to Use This ManualGeneral Information Amp System Only Mechanical Installation InstallationUnpacking Equipment Room / LocationVentilation AC Power ConnectionsAC Connections AWG AC Power Cord SetsPlanning the Battery installation Battery ConnectionsConnecting the Cables 1 Battery Cable Connection Locations Battery Temperature Probe InstallationDC System Grounding Counter Electro-Motive Force Cemf Cell ConnectionsCircuit Breaker Installation Load Protection InstallationGMT Fuse Installation Cable Size Considerations Load ConnectionsCircuit Breaker Protected Load Connections 30 or 60 a GMT Fuse protected Load ConnectionsMonitoring and Relay Output Connections RJ45 Ethernet ConnectorFront Panel DB9 Connection Major, Minor and Relay 1 Output ConnectionsRelay Terminal Relay Alias Output Relay Notes Designations Output Relay 2-6 ConnectionsExternal Alarm Input Connections Rectifier Module InstallationController Module Installation Battery Visual and Safety Inspection Electrical InstallationCommissioning Pre-Commissioning InspectionDC Power Up AC Power UpCommissioning Initial Set-upRectifier Test Battery Power UpLVD Test Circuit Breaker/ Fuse TestFinal Inspection Battery Temperature CompensationOutput Relay Rectifier Management Technical DescriptionSystem Management Load Management System Status and Alarm ReportingSystem Current Monitor Circuit BreakersBattery Charging Battery ManagementGMT Fuses Battery Protection Battery EqualizationBattery Temperature Monitoring Battery Functional Test Battery Low Voltage DisconnectCounter Electro-Motive Force Module Connections Alarm Outputs Output Relays Controls and IndicatorsController with Display Controller without DisplayNetwork Management Card Local & Remote Monitoring External Alarm Inputs User InputDescription OperationController Card Jumpers J12 J13 Controller with Display1 Controller with Display Operation using Local Display and Keypad Interface设置 / 电池 / 容量 设置 / 系统 / 时/日 均充 / 均充时间 状态 / 系统 /参数 Alarms 均充时间 Controller without Display Operation Using the RS-232 Comm PortOperation Using the 10/100 BaseT Ethernet Port 1 Parameter Locations, Descriptions, and Settings ON, OFF Power Modules/Rectifiers Seconds Disable Output Relay System/Preferences LVD OperationProgramming Output Relays Page System Visual and Safety Inspection Preventive MaintenanceEquipment InspectionTest Rectifier Alarm TestSystem Voltage Test Rectifier Current Share TestBattery Current Test System Temperature TestBattery Temperature Test Battery Preventive Maintenance Procedure Alarm Summary System LT Alm System Temperature is below Minor Magnum VS 50 Power System SpecificationsAC Input TWF0500H54B RectifierDC Output Magnum VS 100 Power SystemMagnum VS 50 Power System Magnum VS Controller MechanicalEnvironmental EMC ComplianceAPC Worldwide Customer Support Limited Product Warranty