APC VS 100, VS 50 user manual 设置 / 系统 / 时/日

Page 36

PARAMETER NAME/

DESCRIPTION

SETTINGS (Default

[MENU LOCATION]

 

Settings in BOLD)

 

 

Battery Temperature

Battery temperature measured by the

Battery Temperature

[STATUS/BATTERY/

system controller at the optional battery

Status Only

PARAMETERS]

temperature sensor probe.

 

[状态 / 电池 /参数]

 

 

 

 

 

Date Setup

System date stored in the controller.

Current DATE

[SETUP/SYSTEM/TIME/DATE]

Used as a date stamp in the event log.

 

[设置 / 系统 / /]

 

 

 

 

 

Date Status

Displays the current controller date.

Date Status Only

[STATUS/SYSTEM/Time/Date]

 

 

[状态 / 系统 / /]

 

 

 

 

 

Equalize Automatically On/Off

Applies an overcharge to the battery to

ON, OFF

[SETUP/BATTERY/

equalize the specific gravity of a battery.

 

VOLTAGE/EQUALIZATION/

Auto equalization is initiated when the

 

METHOD/AUTO]

controller determines that the batteries

 

[设置 / 电池 /电压 /

have been discharged a set percentage

 

of their capacity or the batteries have

 

均充 / 模式 / 自动]

been on discharge for a set duration.

 

Use this screen to turn auto equalization

 

 

on.

 

Equalize Automatically on AC

Sets the time the ac input power has to

15 MINUTES – 360

Fail

be off before equalization occurs.

MINUTES, 15 MINUTES

[SETUP/BATTERY/

 

 

VOLTAGE/EQUALIZATION/

 

 

METHOD/AUTO/AC

 

 

FAIL/ON/OFF]

 

 

[设置 / 电池 /电压 /

 

 

均充 / 模式 / 自动

 

 

/自动]

 

 

 

 

 

Equalize Automatically on

Sets the percent of battery discharge

5% - 50%, 30 %

Battery Discharge

before equalization occurs. Percent

 

[SETUP/BATTERY/

Discharge = Discharged ampere-hours /

 

VOLTAGE/EQUALIZATION/

Battery Capacity ampere-hours

 

METHOD/AUTO/DISCHARGE]

 

 

[设置 / 电池 /电压 /

 

 

均充 / 模式 / 自动 /

 

 

交流故障]

 

 

 

 

 

Magnum VS –48 Vdc User’s Manual

Page 31

Image 36
Contents Magnum VS Vdc Power Systems User’s Manual Table of Contents Final Inspection TWF0500H54B Rectifier Magnum VS Controller Revision History Document # & Rev Date DescriptionSafety First General PrecautionsHow to Use This Manual IntroductionGeneral Information Amp System Only Installation Mechanical InstallationUnpacking Equipment Room / LocationAC Power Connections VentilationAC Connections AC Power Cord Sets AWGBattery Connections Planning the Battery installationConnecting the Cables Battery Temperature Probe Installation 1 Battery Cable Connection LocationsCounter Electro-Motive Force Cemf Cell Connections DC System GroundingLoad Protection Installation Circuit Breaker InstallationGMT Fuse Installation Load Connections Cable Size ConsiderationsCircuit Breaker Protected Load Connections 30 or 60 a GMT Fuse protected Load ConnectionsRJ45 Ethernet Connector Monitoring and Relay Output ConnectionsFront Panel DB9 Connection Major, Minor and Relay 1 Output ConnectionsOutput Relay 2-6 Connections Relay Terminal Relay Alias Output Relay Notes DesignationsRectifier Module Installation External Alarm Input ConnectionsController Module Installation Electrical Installation Battery Visual and Safety InspectionCommissioning Pre-Commissioning InspectionAC Power Up DC Power UpCommissioning Initial Set-upBattery Power Up Rectifier TestLVD Test Circuit Breaker/ Fuse TestBattery Temperature Compensation Final InspectionOutput Relay Technical Description Rectifier ManagementSystem Management System Status and Alarm Reporting Load ManagementSystem Current Monitor Circuit BreakersBattery Management Battery ChargingGMT Fuses Battery Equalization Battery ProtectionBattery Temperature Monitoring Battery Low Voltage Disconnect Battery Functional TestCounter Electro-Motive Force Module Connections Controls and Indicators Alarm Outputs Output RelaysController with Display Controller without DisplayExternal Alarm Inputs User Input Network Management Card Local & Remote MonitoringOperation DescriptionController Card Jumpers Controller with Display J12 J13Operation using Local Display and Keypad Interface 1 Controller with Display设置 / 电池 / 容量 设置 / 系统 / 时/日 均充 / 均充时间 状态 / 系统 /参数 Alarms 均充时间 Operation Using the RS-232 Comm Port Controller without DisplayOperation Using the 10/100 BaseT Ethernet Port 1 Parameter Locations, Descriptions, and Settings ON, OFF Power Modules/Rectifiers Seconds Disable Output Relay LVD Operation System/PreferencesProgramming Output Relays Page Preventive Maintenance System Visual and Safety InspectionEquipment InspectionRectifier Alarm Test TestSystem Voltage Test Rectifier Current Share TestSystem Temperature Test Battery Current TestBattery Temperature Test Battery Preventive Maintenance Procedure Alarm Summary System LT Alm System Temperature is below Minor Specifications Magnum VS 50 Power SystemAC Input TWF0500H54B RectifierMagnum VS 100 Power System DC OutputMagnum VS 50 Power System Mechanical Magnum VS ControllerEnvironmental Compliance EMCAPC Worldwide Customer Support Limited Product Warranty