APC VS 100, VS 50 user manual Alarm Summary

Page 56

 

 

8

Alarm Summary

 

 

 

 

 

ALARM/

DESCRIPTION

DEFAULT SETTINGS

 

 

[MENU LOCATION]

 

 

 

Battery Discharge Alarm

The battery discharge current exceeds

Minor

 

[Batteries/Parameters]

the programmed battery discharge

 

 

 

 

threshold.

 

 

Battery High Temp Alm

The battery temperature exceeds the

Minor

 

[Batteries/Parameters]

Battery High Temperature threshold.

 

 

Battery Low Temp Alm

The Battery Temperature is below the

Minor

 

[Batteries/Parameters]

battery Low Temperature threshold.

 

 

Battery LV Alm

The dc output voltage is below the

Major

 

[Batteries/Parameters]

battery low voltage threshold.

 

 

Circuit Breaker Alm 1

The top Circuit Breaker in the top shelf is

Major

 

[Distribution/Breakers]

tripped.

 

 

Circuit Breaker Alm 2

The bottom Circuit Breaker in the top

Major

 

[Distribution/Breakers]

shelf is tripped

 

 

Circuit Breaker Alm 3

The top Circuit Breaker in the bottom

Major

 

[Distribution/Breakers]

shelf is tripped.

 

 

Circuit Breaker Alm 4

The bottom Circuit Breaker in the bottom

Major

 

[Distribution/Breakers]

shelf is tripped

 

 

FUSE Alm 1

Any of Fuse 1 through 4 is blown.

Major

 

[Distribution/Fuses]

 

 

 

FUSE Alm 2

Any of Fuse 5 through 8 is blown.

Major

 

[Distribution/Fuses]

 

 

 

FUSE Alm 3

Any of Fuse 9 through 12 is blown.

Major

 

[Distribution/Fuses]

 

 

 

FUSE Alm 4

Any of Fuse 13 through 16 is blown.

Major

 

[Distribution/Fuses]

 

 

 

Hardware Batt Temp Alm

There is a hardware failure in the battery

Minor

 

[Batteries Parameters]

temperature monitoring function.

 

 

Hardware Sys Volt Alm

There is a hardware failure in the system

Minor

 

[Power Modules/Rectifiers]

voltage monitoring function.

 

 

Hardware Sys Temp Alm

There is a hardware failure in the system

Minor.

 

[System/DC Parameters]

temperature monitoring function.

 

 

System HT Alm

The System Temperature exceeds the

Minor

 

[System/DC Parameters]

system high temperature threshold. Not

 

 

 

 

the same as battery temperature alarm.

 

 

System HV Alm

The System Voltage is above the System

Minor

 

[Power Modules/Rectifiers]

High Voltage threshold. Not the same as

 

 

 

 

battery high voltage alarm.

 

 

Input Relay 1

An external contact closure at the Input

Ignore

 

[I/O/Input]

Relay 1 connection.

 

 

 

 

 

 

 

 

 

 

An external contact opening at the Input

 

Relay 4 connection.

Ignore

 

Input Relay 4

 

 

 

[I/O/Input]

 

 

 

Magnum VS –48 Vdc User’s Manual

Page 51

Image 56
Contents Magnum VS Vdc Power Systems User’s Manual Table of Contents Final Inspection TWF0500H54B Rectifier Magnum VS Controller Revision History Document # & Rev Date DescriptionSafety First General PrecautionsGeneral Information How to Use This ManualIntroduction Amp System Only Installation Mechanical InstallationUnpacking Equipment Room / LocationAC Connections AC Power ConnectionsVentilation AC Power Cord Sets AWGConnecting the Cables Battery ConnectionsPlanning the Battery installation Battery Temperature Probe Installation 1 Battery Cable Connection LocationsCounter Electro-Motive Force Cemf Cell Connections DC System GroundingGMT Fuse Installation Load Protection InstallationCircuit Breaker Installation Load Connections Cable Size ConsiderationsCircuit Breaker Protected Load Connections 30 or 60 a GMT Fuse protected Load ConnectionsRJ45 Ethernet Connector Monitoring and Relay Output ConnectionsFront Panel DB9 Connection Major, Minor and Relay 1 Output ConnectionsOutput Relay 2-6 Connections Relay Terminal Relay Alias Output Relay Notes DesignationsRectifier Module Installation External Alarm Input ConnectionsController Module Installation Electrical Installation Battery Visual and Safety InspectionCommissioning Pre-Commissioning InspectionAC Power Up DC Power UpCommissioning Initial Set-upBattery Power Up Rectifier TestLVD Test Circuit Breaker/ Fuse TestOutput Relay Battery Temperature CompensationFinal Inspection System Management Technical DescriptionRectifier Management System Status and Alarm Reporting Load ManagementSystem Current Monitor Circuit BreakersGMT Fuses Battery ManagementBattery Charging Battery Temperature Monitoring Battery EqualizationBattery Protection Counter Electro-Motive Force Module Connections Battery Low Voltage DisconnectBattery Functional Test Controls and Indicators Alarm Outputs Output RelaysController with Display Controller without DisplayExternal Alarm Inputs User Input Network Management Card Local & Remote MonitoringController Card Jumpers OperationDescription Controller with Display J12 J13Operation using Local Display and Keypad Interface 1 Controller with Display设置 / 电池 / 容量 设置 / 系统 / 时/日 均充 / 均充时间 状态 / 系统 /参数 Alarms 均充时间 Operation Using the RS-232 Comm Port Controller without DisplayOperation Using the 10/100 BaseT Ethernet Port 1 Parameter Locations, Descriptions, and Settings ON, OFF Power Modules/Rectifiers Seconds Disable Output Relay LVD Operation System/PreferencesProgramming Output Relays Page Preventive Maintenance System Visual and Safety InspectionEquipment InspectionRectifier Alarm Test TestSystem Voltage Test Rectifier Current Share TestBattery Temperature Test System Temperature TestBattery Current Test Battery Preventive Maintenance Procedure Alarm Summary System LT Alm System Temperature is below Minor Specifications Magnum VS 50 Power SystemAC Input TWF0500H54B RectifierMagnum VS 100 Power System DC OutputMagnum VS 50 Power System Mechanical Magnum VS ControllerEnvironmental Compliance EMCAPC Worldwide Customer Support Limited Product Warranty