APC VS 100, VS 50 user manual On, Off

Page 44

PARAMETER NAME/

DESCRIPTION

SETTINGS (Default

[MENU LOCATION]

 

settings in BOLD)

 

 

Battery Max Recharge

This is just a convenient place to view

Status Only

{Status Only}

the Battery Max Recharge Current

 

[System/DC Parameters]

parameter. Go to Batteries/Parameters

 

 

to change setting.

 

Battery Maximum Recharge

One of three parameters that control the

0 – 10,000 A, 10 A

Current

dc output voltage. If Battery Current

 

[Batteries/Parameters]

surpasses the Maximum Battery

 

 

Recharge Current, the dc output voltage

 

 

will be reduced (the system limits the

 

 

charging current to this programmable

 

 

value).

 

Battery Temperature

Battery temperature measured by the

Status Only

[System/DC Parameters]

system controller at the optional battery

 

 

temperature sensor probe.

 

Battery Temperature

The temperature compensation high

0 °C – 100 °C, 40.0 °C

Compensation High Knee

knee is the point where there is no

 

[Batteries/Parameters]

additional battery voltage compensation

 

 

for further increases in temperature.

 

Battery Temperature

The temperature compensation low knee

-100 °C – 100 °C, 0.0 °C

Compensation Low Knee

is the point where there is no additional

 

[Batteries/Parameters]

battery voltage compensation for further

 

 

decreases in temperature.

 

Battery Temperature

One of three parameters that control the

ON, OFF

Compensation Method

dc output voltage. Activate “ON” or de-

 

[Batteries/Parameters]

activate “OFF” battery temperature

 

 

compensation.

 

Battery Temperature

Temperature compensation coefficient

-4.99 mV – 0 mV,

Compensation Temperature

between low knee and high knee in

-3.00mV

Coefficient

mV/cell/°C. (Compensation equals zero

 

[Batteries/Parameters]

at 25°C.)

 

Circuit Breaker 1 Alias

An alternate name (alias) can be

Circuit Breaker 1

[Distribution/Breakers]

assigned to Circuit Breaker 1 if desired.

 

This feature is supported by the standard

SNMP card monitor, but is not supported

by this dc system.

Circuit Breaker 4 Alias

 

Circuit Breaker 4

[Distribution/Breakers]

 

 

 

 

 

Circuit Breaker 1 Tripped

Defines the output relay that is energized

Ignore, Minor, Major

[Distribution/Breakers]

when Circuit Breaker 1 is tripped.

Output Relay 1-6

Circuit Breaker 4 Tripped

Defines the output relay that is energized

Ignore, Minor, Major

[Distribution/Breakers]

when Circuit Breaker 4 is tripped.

Output Relay 1-6

 

 

Circuit Breaker 5-72 is not

 

 

used in this system.

Communications Fail

Defines the output relay that is energized

Ignore, Minor, Major

 

if the System stops communicating with

Output Relay 1-6•

 

the rectifiers. This feature is supported

 

 

by the standard SNMP card monitor, but

 

 

is not supported by this dc system.

 

Magnum VS –48 Vdc User’s Manual

Page 39

Image 44
Contents Magnum VS Vdc Power Systems User’s Manual Table of Contents Final Inspection TWF0500H54B Rectifier Magnum VS Controller Revision History Document # & Rev Date DescriptionSafety First General PrecautionsGeneral Information How to Use This ManualIntroduction Amp System Only Installation Mechanical InstallationUnpacking Equipment Room / LocationAC Connections AC Power ConnectionsVentilation AC Power Cord Sets AWGConnecting the Cables Battery ConnectionsPlanning the Battery installation Battery Temperature Probe Installation 1 Battery Cable Connection LocationsCounter Electro-Motive Force Cemf Cell Connections DC System GroundingGMT Fuse Installation Load Protection InstallationCircuit Breaker Installation Load Connections Cable Size ConsiderationsCircuit Breaker Protected Load Connections 30 or 60 a GMT Fuse protected Load ConnectionsRJ45 Ethernet Connector Monitoring and Relay Output ConnectionsFront Panel DB9 Connection Major, Minor and Relay 1 Output ConnectionsOutput Relay 2-6 Connections Relay Terminal Relay Alias Output Relay Notes DesignationsRectifier Module Installation External Alarm Input ConnectionsController Module Installation Electrical Installation Battery Visual and Safety InspectionCommissioning Pre-Commissioning InspectionAC Power Up DC Power UpCommissioning Initial Set-upBattery Power Up Rectifier TestLVD Test Circuit Breaker/ Fuse TestOutput Relay Battery Temperature CompensationFinal Inspection System Management Technical DescriptionRectifier Management System Status and Alarm Reporting Load ManagementSystem Current Monitor Circuit BreakersGMT Fuses Battery ManagementBattery Charging Battery Temperature Monitoring Battery EqualizationBattery Protection Counter Electro-Motive Force Module Connections Battery Low Voltage DisconnectBattery Functional Test Controls and Indicators Alarm Outputs Output RelaysController with Display Controller without DisplayExternal Alarm Inputs User Input Network Management Card Local & Remote MonitoringController Card Jumpers OperationDescription Controller with Display J12 J13Operation using Local Display and Keypad Interface 1 Controller with Display设置 / 电池 / 容量 设置 / 系统 / 时/日 均充 / 均充时间 状态 / 系统 /参数 Alarms 均充时间 Operation Using the RS-232 Comm Port Controller without DisplayOperation Using the 10/100 BaseT Ethernet Port 1 Parameter Locations, Descriptions, and Settings ON, OFF Power Modules/Rectifiers Seconds Disable Output Relay LVD Operation System/PreferencesProgramming Output Relays Page Preventive Maintenance System Visual and Safety InspectionEquipment InspectionRectifier Alarm Test TestSystem Voltage Test Rectifier Current Share TestBattery Temperature Test System Temperature TestBattery Current Test Battery Preventive Maintenance Procedure Alarm Summary System LT Alm System Temperature is below Minor Specifications Magnum VS 50 Power SystemAC Input TWF0500H54B RectifierMagnum VS 100 Power System DC OutputMagnum VS 50 Power System Mechanical Magnum VS ControllerEnvironmental Compliance EMCAPC Worldwide Customer Support Limited Product Warranty