VistaQuest N7227V5 installation instructions Preliminary Check-out Procedure

Page 17

SUPPLEMENTARY POWER SUPPLY

+

CONTROL

TERMINAL STRIP

AUX

AUX. DATA DATA

 

+

 

IN

OUT

4

5

6

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED WIRE

BLK WIRE

GRN WIRE

YEL WIRE

TO KEYPAD

TO KEYPAD

TO KEYPAD

TO KEYPAD

IMPORTANT:

MAKE THESE

CONNECTIONS

DIRECTLY TO SCREW TERMINALS AS SHOWN.

TO KEYPAD BLK WIRE

TO KEYPAD RED WIRE

GRN WIRE

YEL WIRE

TO KEYPAD

TO KEYPAD

Figure 6. Using A Supplementary Power Supply For Keypads

Preliminary Check-out Procedure

If you want to check that the system is working before connecting field wiring from zones and devices, do the following:

1.Temporarily connect a 1000 ohm end-of-line resistor across each of the basic hard-wire zones 1–6, as shown in the Summary of Connections diagram.

Without actual zone wiring or EOL resistors connected, the keypads in the system will not display the “Ready” message.

2.Power up the system temporarily by plugging the AC transformer (previously wired to the control) into a 120VAC outlet.

3.Bu s y – S ta n d b y (Alpha keypads) or dI (Fixed-word keypads) will be displayed.

After approximately 1 minute *, the green “READY” LED (or “POWER” LED on some types of keypads) should light, and the word READY (Fixed- word keypads), or DISARMED...READY TO ARM (Alpha keypads) should be displayed.

*To bypass the 1-minute delay, press # plus 0.

If the “Ready” message is not displayed on any of the keypads in the system, or a “Not Ready” message is displayed, check the keypad wiring connections, and make sure each of the 6 basic hard-wired zones has a 1000 ohm resistor connected across its terminals.

4.When you get the proper “Ready” displays on the keypad(s), the system is functioning properly at this point.

Do not remove the EOL resistors until you are ready to make connections to the hard-wired zones, to allow for testing later in the manual.

If an OC or OPEN CIRCUIT display is present on the keypad, data from the control is not reaching the keypad. Check the wiring.

– 17 –

Image 17
Contents VISTA-10SE Recommendations For Proper Intrusion Protection Recommendations For Smoke And Heat DetectorsTable of Contents Relay Output Devices For 5800 Series Wireless Transmitters Section Sequential ModeList of Figures HOW to USE this Manual Conventions Used in this Manual General Description Wireless ExpansionBack-Up Battery AC Power SupplyOptional Phone module Supports the Ademco 4285 Phone module Communication FormatsMounting the Cabinet Installing the ControlInstalling the Lock if used Relay Unit if installed in cabinet Standard Telephone Line Connections Standard Phone Line ConnectionsInstalling The Back-Up Battery Wiring The AC TransformerWiring Table Do not Connect the Wires to the Battery YETKeypads That May Be Used Installing Remote KeypadsWiring To The Keypads Keypad Connections To The Control Board Mounting the KeypadsUsing a Supplementary Power Supply For Keypads Preliminary Check-out ProcedureInstalling the Hard-Wired Zones Basic HARD-WIRED ZonesWiring Burglary and Panic Devices To Zones Wiring 4-Wire Smoke/Combustion Detectors on ZoneProgramming Hard-Wired Zones Zone Types Programming Check-Out Procedure For Hard-Wired ZonesSpecial Notes on Zone Wireless Systems Available Wireless RF Zone Expansion 5800 RF SystemsSeries Receiver Wireless Zones Wireless System Operation and Transmitter SupervisionWireless System Installation Advisories Transmitter Battery LifeInstallation and Setup of the 4281/5881 Wireless Receivers Receiver SupervisionBoard Series Transmitter SetupOn 5700 Series Setting the DIP SwitchesRefer to the Compatible 5700 Series TransmittersDIP Switch Tables for 5700 RF System Wireless Devices Model Product Zone/ID # Description Compatible 5700 Series TransmittersUsing the House ID Sniffer Mode 5700 Systems Programming the Control For a 5700 Wireless SystemEnter your Installer Code + # + Zone Programming For 5700 TransmittersProgramming Guide Systems Enter the Installer Code + # +Programming 5700 RF Series Transmitter Setup Temp Compatible 5800 Series TransmittersGBD Programming the RF Transmitters 5800 RF SystemsEnrolling Through Zone Programming RF House ID CodeEnrolling 5800 Transmitters Into The System ZN ZT RC In L 0 0 0 0 RF Transmitter before proceeding to the next zone Recommend that you confirm the programming of everyTransmitter ID Check-Out Procedure for Wireless ZonesSniffer Mode Go/No Go Test Relay Modules Relay Output DevicesRelay Device Basics Alarm Programming Output Relays Choices for Zone Types Example of Output Relay Programming Phone Module Wiring Installing the Phone modulePhone Module General InformationCaller ID Units Terminal Connects to4285 Wiring NotesPress 95. Ring Detection Count Programming The Control For Phone AccessVoice Answering Module Downloading Field 95 ProgrammingTo Check Phone module Operation From an Off-Premises Phone Checking the Operation of the 4285 Phone moduleTo Check Phone module Operation From an On-Premises Phone External Sounders Testing the Sounder Press 30. Alarm Bell TimeoutSounder Connections Press 51. Confirmation of Arming DingConnection Long Range RadioGeneral Information Programming Audio Alarm Verification AAVWiring Connections Connection Of AAV Unit When Not Using a 4285 Phone module To bypass this delay, press # + Final Power UPCalculating the Battery Size Needed ExampleConnections Making the BatteryDevice Current # Units Total Current Total =Section Entering Zone Descriptors program menu modeProgramming the Descriptors PressO R Alternate Method For Programming Zone Descriptors Press 6 to accept the selected wordPress 8 to save all words in memory Method For Adding Custom Words Alpha Vocabulary ListSequential Mode For 5800 Series Wireless Transmitters Serial # ↑ Page Following describes each format in greater detail System Communication+1/4+1 Report Standard Expanded Ademco Contact ID Reporting takes the following formatTable of Contact ID Event Codes Communication ProgrammingPress 46 Report FORMAT, PRIMARY/SECONDARY Press 45 Phone System Select Enter 1 digit default =Press 47 SPLIT/DUAL Reporting To Primary Phone No To Secondary Phone NoPress 60 Trouble Report Code To Program System Status and Restore Report Codes 60 68, 70Press 61 Bypass Report Code Press 62 AC Loss Report CodePress 67 RF XMTR. LOW Battery Report Code Press65 OPEN/EXIT Alarm Report CODE, 1st DigitsPress 68 Cancel Report Code Press 70 Alarm Restore Report CODE, 1st DigitPress 75 RF XMTR. LOW Battery Restore Code Press 74 LOW BAT Restore Report CodePress 92 Number of Reports in Armed Period Press 94 Download Phone NumberTest Procedure Testing the SystemTo the Installer To program a Duress code System OperationTo change the Duress code To delete the Duress codeKeypad Functions Features for Each Arming ModeDisarmed, Not Ready Forced Quick BypassIf used Keys Displayed as ZoneRelay Outputs Security Code + # +Trouble Conditions See Troubleshooting Guide also System including Wireless Troubleshooting GuideControl Read the Instructions PleaseBefore you call Technical Support, be sure you Specifications Specifications & AccessoriesVISTA-10SE Security Control Remote Keypad Remote KeypadsZones With the Ademco VISTA-10SE Transmitter ModuleRelay Module Phone Module No CN Accessories Compatible DevicesAdemco 702 Outdoor SirenFederal Communications Commission FCC Part 68 Statement Federal Communications Commission FCC Part 15 StatementUL Notices Canadian Department of Communications DOC Statement Limitations of this Alarm System ADT VISTA-10SE Summary of Connections Ademco Limited Warranty