
Setting the DIP Switches | Set the DIP switches on each 5700 series transmitter to the appropriate  | |||
on 5700 Series | zone/ID number and House ID.  | Refer to the Compatible 5700 Series | ||
Transmitters | Transmitters table on a following page in this section for zone numbers and  | |||
  | 
  | programming information for each particular transmitter. Refer also to DIP  | ||
  | 
  | SWITCH TABLES FOR 5700 RF WIRELESS DEVICES later in this section.  | ||
  | 
  | 
  | ||
  | 
  | The House ID allows the 5700 RF system to identify 5700 transmitters with a  | ||
  | 
  | matching House ID. If using a 5700 RF wireless system, the DIP switches on  | ||
  | 
  | the transmitters must match the system House ID programmed into the  | ||
  | 
  | control (in data field ✱24). If using a 5827BD wireless keypad, the House ID  | ||
  | 
  | also applies. Other than the 5827 and 5827BD, 5800 series devices do not  | ||
  | 
  | communicate by House ID, but by transmitting a unique serial number to the  | ||
  | 
  | control. In this case, programming a House ID is not necessary.  | ||
Wireless Zone/ID Each wireless zone can be assigned any zone response type, such as  | ||||
Assignments for 5700 | Entry/Exit, Interior Follower, Perimeter, etc. (see the ZONE RESPONSE TYPE  | |||
Series Transmitters | DEFINITIONS section in the separate Programming Guide for a detailed  | |||
explanations of each zone type). For 5700 series transmitters, each response  | ||||
  | 
  | |||
  | 
  | type uses a certain range of zone numbers. Each range of zone/ID numbers is  | ||
  | 
  | shown below.  | 
  | |
  | 
  | Zone Type | Transmitter Zone/ID # | |
  | 
  | |||
  | 
  | Entry/Exit Burg  | 10 through 47 *  | |
  | 
  | Perimeter Burg  | 10 through 47 *  | |
  | 
  | Interior Burg  | 10 through 47 *  | |
  | 
  | 
  | 32 through 47 * (5775)  | |
  | 
  | Fire  | 48 through 63 *  | |
  | 
  | 
  | 48 through 55 ** (5706)  | |
  | 
  | 24 Hour Panic  | 48 through 63 *  | |
  | 
  | (silent or audible)  | 62 or 63 *** (5701)  | |
  | 
  | Day/Night Burglary  | 10 through 47 *  | |
  | 
  | 24 Hour Auxiliary  | 10 through 47 *  | |
* Zone/ID numbers 
** Transmitter IDs 48 through 55 have highest signal priority.
*** Transmitter IDs 62 and 63 are unsupervised to allow removal of the 5701 off premises — signal priority is lower than that of fire, but higher than burglary.
Notes: 1. Transmitters set for zone/IDs 
2.Transmitters set for an zone/IDs of 32 through 47 will have a 
3.Refer also to “Compatible 5700 Series Transmitters”on a following page.
– 25 –