VistaQuest N7227V5 installation instructions External Sounders

Page 49

Section 8. EXTERNAL SOUNDERS

This section provides a list of compatible sounders, connection information for an external sounder and programming procedures for those options that affect the operation of external sounders .

Compatible Sounders

Ademco AB-12M 10”

Motor bell & box. UL Grade A. 100mA current

Motorized Bell & Box

draw.

 

Ademco 1011BE12M

Motor bell & box. UL Listed. 100mA current draw.

10” Motorized Bell &

 

 

Box

 

 

Ademco 702

Self-contained 6–12 volt siren (driver built-in) and

Outdoor Siren

weatherproof for outdoor use. Can be wired for

 

either a steady or warble sound. 117dB @ 10

 

feet. 1500mA current draw.

Ademco 719

Self-contained 6–12-volt siren (driver built in).

2-Channel Siren

Steady or warble sound. 109dB @ 10 feet.

 

550mA current draw.

 

Ademco 747

Self-contained 6–15 volt siren (driver built-in) for

Indoor Siren

indoor wall mount.

747F available for flush

 

mounting. 105dB @ 10 feet. 400mA current draw.

 

 

Ademco 747UL

Self-contained 6–15 volt siren (driver built-in) for

Indoor Siren

indoor wall mount.

UL Listed. 85dB @ 10 feet.

 

320mA current draw.

 

Ademco 744

6 jumper-selected sound outputs. Rated at 119dB

Siren Driver

with use of an 8-ohm 30 watt speaker. 1.3 amps

 

current draw.

 

Ademco 745X3*

12 volt voice siren driver with English, Spanish

Voice Siren Driver

and French voice messages. Separate messages

 

for Fire and Burglary. Use with 8-ohm speaker.

 

UL Listed. 1100mA current draw.

Ademco 705–820,

20-watt, 8-ohm indoor or outdoor speaker.

5-inch Round Speaker

Requires a driver.

 

Ademco 713 Speaker

40-watt, 8-ohm, indoor/outdoor speaker. Requires

 

a driver.

 

System Sensor PA400B

Indoor piezo sounder (red or beige), rated at 90

(beige)/PA400R (red)

dB @ 10 feet.

 

Indoor Piezo Sounder

 

 

*Requires special power wiring, using additional components.

UL

Use only UL Listed sounding devices for UL installations.

The total current drawn from the alarm output and the auxiliary power output, combined, cannot exceed 600mA. In addition, the sounding device must be a UL Listed audible signal appliance rated to operate in a 10.2-13.8 VDC voltage range, and must be mounted indoors. Example: Wheelock Signals Inc. siren model 34T-12 (provides 85dB[A] for NFPA 74 & Standard 985).

Non-UL Installations

The total current drawn from the alarm output terminals cannot exceed 2 amps. The back-up battery must be installed since this current is supplied by that battery.

Going beyond the limits indicated (2 amps) will overload the power supply, or may cause the electronic circuit protecting the sounder output to trip.

– 49 –

Image 49
Contents VISTA-10SE Recommendations For Proper Intrusion Protection Recommendations For Smoke And Heat DetectorsTable of Contents Relay Output Devices For 5800 Series Wireless Transmitters Section Sequential ModeList of Figures HOW to USE this Manual Conventions Used in this Manual General Description Wireless ExpansionBack-Up Battery AC Power SupplyOptional Phone module Supports the Ademco 4285 Phone module Communication FormatsInstalling the Lock if used Installing the ControlMounting the Cabinet Relay Unit if installed in cabinet Standard Telephone Line Connections Standard Phone Line ConnectionsInstalling The Back-Up Battery Wiring The AC TransformerWiring Table Do not Connect the Wires to the Battery YETWiring To The Keypads Installing Remote KeypadsKeypads That May Be Used Keypad Connections To The Control Board Mounting the KeypadsUsing a Supplementary Power Supply For Keypads Preliminary Check-out ProcedureInstalling the Hard-Wired Zones Basic HARD-WIRED ZonesWiring Burglary and Panic Devices To Zones Wiring 4-Wire Smoke/Combustion Detectors on ZoneProgramming Hard-Wired Zones Zone Types Special Notes on Zone Check-Out Procedure For Hard-Wired ZonesProgramming Wireless Systems Available Wireless RF Zone Expansion 5800 RF SystemsSeries Receiver Wireless Zones Wireless System Operation and Transmitter SupervisionWireless System Installation Advisories Transmitter Battery LifeInstallation and Setup of the 4281/5881 Wireless Receivers Receiver SupervisionBoard Series Transmitter SetupOn 5700 Series Setting the DIP SwitchesRefer to the Compatible 5700 Series TransmittersDIP Switch Tables for 5700 RF System Wireless Devices Model Product Zone/ID # Description Compatible 5700 Series TransmittersUsing the House ID Sniffer Mode 5700 Systems Programming the Control For a 5700 Wireless SystemEnter your Installer Code + # + Zone Programming For 5700 TransmittersProgramming Guide Programming 5700 RF Enter the Installer Code + # +Systems Series Transmitter Setup Temp Compatible 5800 Series TransmittersGBD Programming the RF Transmitters 5800 RF SystemsEnrolling 5800 Transmitters Into The System RF House ID CodeEnrolling Through Zone Programming ZN ZT RC In L 0 0 0 0 RF Transmitter before proceeding to the next zone Recommend that you confirm the programming of everySniffer Mode Check-Out Procedure for Wireless ZonesTransmitter ID Go/No Go Test Relay Device Basics Relay Output DevicesRelay Modules Alarm Programming Output Relays Choices for Zone Types Example of Output Relay Programming Phone Module Wiring Installing the Phone modulePhone Module General InformationCaller ID Units Terminal Connects to4285 Wiring NotesPress 95. Ring Detection Count Programming The Control For Phone AccessVoice Answering Module Downloading Field 95 ProgrammingTo Check Phone module Operation From an On-Premises Phone Checking the Operation of the 4285 Phone moduleTo Check Phone module Operation From an Off-Premises Phone External Sounders Testing the Sounder Press 30. Alarm Bell TimeoutSounder Connections Press 51. Confirmation of Arming DingGeneral Information Long Range RadioConnection Wiring Connections Audio Alarm Verification AAVProgramming Connection Of AAV Unit When Not Using a 4285 Phone module To bypass this delay, press # + Final Power UPCalculating the Battery Size Needed ExampleConnections Making the BatteryDevice Current # Units Total Current Total =Section Entering Zone Descriptors program menu modeProgramming the Descriptors PressO R Press 8 to save all words in memory Press 6 to accept the selected wordAlternate Method For Programming Zone Descriptors Method For Adding Custom Words Alpha Vocabulary ListSequential Mode For 5800 Series Wireless Transmitters Serial # ↑ Page Following describes each format in greater detail System Communication+1/4+1 Report Standard Expanded Ademco Contact ID Reporting takes the following formatTable of Contact ID Event Codes Communication ProgrammingPress 46 Report FORMAT, PRIMARY/SECONDARY Press 45 Phone System Select Enter 1 digit default =Press 47 SPLIT/DUAL Reporting To Primary Phone No To Secondary Phone NoPress 60 Trouble Report Code To Program System Status and Restore Report Codes 60 68, 70Press 61 Bypass Report Code Press 62 AC Loss Report CodePress 67 RF XMTR. LOW Battery Report Code Press65 OPEN/EXIT Alarm Report CODE, 1st DigitsPress 68 Cancel Report Code Press 70 Alarm Restore Report CODE, 1st DigitPress 75 RF XMTR. LOW Battery Restore Code Press 74 LOW BAT Restore Report CodePress 92 Number of Reports in Armed Period Press 94 Download Phone NumberTest Procedure Testing the SystemTo the Installer To program a Duress code System OperationTo change the Duress code To delete the Duress codeKeypad Functions Features for Each Arming ModeDisarmed, Not Ready Forced Quick BypassIf used Keys Displayed as ZoneRelay Outputs Security Code + # +Trouble Conditions See Troubleshooting Guide also System including Wireless Troubleshooting GuideControl Before you call Technical Support, be sure you PleaseRead the Instructions Specifications Specifications & AccessoriesVISTA-10SE Security Control Remote Keypad Remote KeypadsRelay Module Phone Module Transmitter ModuleZones With the Ademco VISTA-10SE No CN Accessories Compatible DevicesAdemco 702 Outdoor SirenFederal Communications Commission FCC Part 68 Statement Federal Communications Commission FCC Part 15 StatementUL Notices Canadian Department of Communications DOC Statement Limitations of this Alarm System ADT VISTA-10SE Summary of Connections Ademco Limited Warranty