VistaQuest N7227V5 Check-Out Procedure for Wireless Zones, Transmitter ID, Sniffer Mode

Page 37

To Either Temporarily Or Permanently Remove A Zone From The System (5800 System).

1. Enter the programming mode:

Key Installer Code + 8 + 0 and press [][5][6].

2. Enter the zone number and press [ ]. A summary display will appear.

3. Press [] again.

2 0 Zone Type

 

Not Use d

0 0

4.The “Zone Type ” prompt will appear. Enter [0][0]. This sets the zone type to “Not Used”.

Press [] to continue.

 

2 0 De le te Zone ?

 

5. The next prompt will ask whether you want to

 

 

delete the zone.

 

1 = Ye s 0 = No

 

 

 

"Yes" will permanently remove the zone from

 

 

 

the system, while a "No" will disable it but retain

 

 

 

 

 

 

all data except the original zone type. You can then go back to this zone later and put back an active zone type to re-enable it.

A serial number that has been entered for a 5800 system will not be deleted if the zone is temporarily disabled by answering “No” to the prompt above.

If only the physical transmitter is to be removed or changed (i.e., its serial number deleted, as when replacing a unit that has a non-removable battery), it can be done in 56 Mode, as indicated next.

Deleting a Transmitter Serial Number From a Zone in 56 Mode (5800 System)

The abbreviated procedure below can be used to delete a serial number from a zone, using the 56 Mode.

1.In the programming mode, press [][5][6] to enter Zone Programming mode.

2.Then enter the zone number, and press [ ] repeatedly until the cursor is under the RF Input Loop (L) position. This is the specific input (loop) or button on the transmitter that has been entered for that zone.

3.Enter a [0] at this point, then press [].

4.A prompt " Delete S/N?" will appear.

Enter "Yes" to delete the existing serial number from the system.

Note that the other programmed values for that zone will not be deleted. This will allow you to re-instate a new transmitter in its place.

5.A display for the next zone number will appear. To exit, enter “00".

6.Press 99 to exit the programming mode.

Check-Out Procedure for Wireless Zones

Transmitter ID

When all transmitters have been installed, use the Transmitter Sniffer Mode to

Sniffer Mode

test that they have all been properly programmed.

(5700/5800

1. Enter Installer Code + # + 3. The keypad will display all zone numbers of

RF Systems)

wireless units programmed into the system.

 

2.Fault each wireless zone, causing each device to transmit. As the system receives a signal from each of the transmitters, the zone number of that transmitter will disappear from the display.

If a 5700 transmitter is not dipswitched correctly, or if a 5800 transmitter is not enrolled, its zone number will not turn off.

3.To exit the Transmitter Sniffer mode, enter the Installer Code + (OFF).

(Continued)

– 37 –

Image 37
Contents VISTA-10SE Recommendations For Proper Intrusion Protection Recommendations For Smoke And Heat DetectorsTable of Contents Relay Output Devices For 5800 Series Wireless Transmitters Section Sequential ModeList of Figures HOW to USE this Manual Conventions Used in this Manual General Description Wireless ExpansionBack-Up Battery AC Power SupplyOptional Phone module Supports the Ademco 4285 Phone module Communication FormatsInstalling the Lock if used Installing the ControlMounting the Cabinet Relay Unit if installed in cabinet Standard Telephone Line Connections Standard Phone Line ConnectionsInstalling The Back-Up Battery Wiring The AC TransformerWiring Table Do not Connect the Wires to the Battery YETWiring To The Keypads Installing Remote KeypadsKeypads That May Be Used Keypad Connections To The Control Board Mounting the KeypadsUsing a Supplementary Power Supply For Keypads Preliminary Check-out ProcedureInstalling the Hard-Wired Zones Basic HARD-WIRED ZonesWiring Burglary and Panic Devices To Zones Wiring 4-Wire Smoke/Combustion Detectors on ZoneProgramming Hard-Wired Zones Zone Types Special Notes on Zone Check-Out Procedure For Hard-Wired ZonesProgramming Wireless Systems Available Wireless RF Zone Expansion 5800 RF SystemsSeries Receiver Wireless Zones Wireless System Operation and Transmitter SupervisionWireless System Installation Advisories Transmitter Battery LifeInstallation and Setup of the 4281/5881 Wireless Receivers Receiver SupervisionBoard Series Transmitter SetupOn 5700 Series Setting the DIP SwitchesRefer to the Compatible 5700 Series TransmittersDIP Switch Tables for 5700 RF System Wireless Devices Model Product Zone/ID # Description Compatible 5700 Series TransmittersUsing the House ID Sniffer Mode 5700 Systems Programming the Control For a 5700 Wireless SystemEnter your Installer Code + # + Zone Programming For 5700 TransmittersProgramming Guide Programming 5700 RF Enter the Installer Code + # +Systems Series Transmitter Setup Temp Compatible 5800 Series TransmittersGBD Programming the RF Transmitters 5800 RF SystemsEnrolling 5800 Transmitters Into The System RF House ID CodeEnrolling Through Zone Programming ZN ZT RC In L 0 0 0 0 RF Transmitter before proceeding to the next zone Recommend that you confirm the programming of everySniffer Mode Check-Out Procedure for Wireless ZonesTransmitter ID Go/No Go Test Relay Device Basics Relay Output DevicesRelay Modules Alarm Programming Output Relays Choices for Zone Types Example of Output Relay Programming Phone Module Wiring Installing the Phone modulePhone Module General InformationCaller ID Units Terminal Connects to4285 Wiring NotesPress 95. Ring Detection Count Programming The Control For Phone AccessVoice Answering Module Downloading Field 95 ProgrammingTo Check Phone module Operation From an On-Premises Phone Checking the Operation of the 4285 Phone moduleTo Check Phone module Operation From an Off-Premises Phone External Sounders Testing the Sounder Press 30. Alarm Bell TimeoutSounder Connections Press 51. Confirmation of Arming DingGeneral Information Long Range RadioConnection Wiring Connections Audio Alarm Verification AAVProgramming Connection Of AAV Unit When Not Using a 4285 Phone module To bypass this delay, press # + Final Power UPCalculating the Battery Size Needed ExampleConnections Making the BatteryDevice Current # Units Total Current Total =Section Entering Zone Descriptors program menu modeProgramming the Descriptors PressO R Press 8 to save all words in memory Press 6 to accept the selected wordAlternate Method For Programming Zone Descriptors Method For Adding Custom Words Alpha Vocabulary ListSequential Mode For 5800 Series Wireless Transmitters Serial # ↑ Page Following describes each format in greater detail System Communication+1/4+1 Report Standard Expanded Ademco Contact ID Reporting takes the following formatTable of Contact ID Event Codes Communication ProgrammingPress 46 Report FORMAT, PRIMARY/SECONDARY Press 45 Phone System Select Enter 1 digit default =Press 47 SPLIT/DUAL Reporting To Primary Phone No To Secondary Phone NoPress 60 Trouble Report Code To Program System Status and Restore Report Codes 60 68, 70Press 61 Bypass Report Code Press 62 AC Loss Report CodePress 67 RF XMTR. LOW Battery Report Code Press65 OPEN/EXIT Alarm Report CODE, 1st DigitsPress 68 Cancel Report Code Press 70 Alarm Restore Report CODE, 1st DigitPress 75 RF XMTR. LOW Battery Restore Code Press 74 LOW BAT Restore Report CodePress 92 Number of Reports in Armed Period Press 94 Download Phone NumberTest Procedure Testing the SystemTo the Installer To program a Duress code System OperationTo change the Duress code To delete the Duress codeKeypad Functions Features for Each Arming ModeDisarmed, Not Ready Forced Quick BypassIf used Keys Displayed as ZoneRelay Outputs Security Code + # +Trouble Conditions See Troubleshooting Guide also System including Wireless Troubleshooting GuideControl Before you call Technical Support, be sure you PleaseRead the Instructions Specifications Specifications & AccessoriesVISTA-10SE Security Control Remote Keypad Remote KeypadsRelay Module Phone Module Transmitter ModuleZones With the Ademco VISTA-10SE No CN Accessories Compatible DevicesAdemco 702 Outdoor SirenFederal Communications Commission FCC Part 68 Statement Federal Communications Commission FCC Part 15 StatementUL Notices Canadian Department of Communications DOC Statement Limitations of this Alarm System ADT VISTA-10SE Summary of Connections Ademco Limited Warranty