VistaQuest N7227V5 installation instructions Programming Guide

Page 29

Data field 22 RF SYSTEM TYPE, must have been programmed for a 5700 RF system (“1”). Also, the House ID should have been entered in field24, and all 5700 transmitters set to the same House ID.

4.Press 56. (Zone Programming Mode)

Use this mode to program zone numbers, zone types, and alarm report codes for all 5700 wireless zones that are going to be used in the system.

5700 transmitters are programmed into the system one at a time, starting with the lowest Zone/ID number that has been assigned to it previously via its DIP switches.

Example: If the first transmitter to be programmed has been set via its DIP switches to Zone/ID 20, you will program zone types, and alarm report codes for that transmitter in zone 20.

Ente r Zn Num .

(0 0 = Q uit)

2 0

Zone 20 entered

 

 

 

 

 

 

 

 

 

Zn

ZT

RC

In:

L

 

 

2 0

0 0

– :

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zone Number

5.Enter the zone number that you wish to program. As an example, zone 20 is shown entered here.

Zone numbers between 10 and 63 can be assigned to transmitters. However, the total number of wireless zones that can be used is 8 for 5700 RF systems (see Table 1 on a previous page).

6.A summary display will appear, showing the status of that zone's program.

If it is programmed satisfactorily, press [#] to back up one step and enter another zone number, if desired.

If the zone is not programmed, or you want to change it, press []. A prompt for Zone Type will appear.

2 0 Zone Type

Pe r ime te r

0 3

Entry for Zone Type

03 shown

A detailed explanation of each zone type is provided in the ZONE RESPONSE TYPE DEFINITIONS section in the separate

Programming Guide.

7.Each zone must be assigned a zone type, which defines the way in which the system responds to faults in that zone.

Enter the zone type (or change it, if necessary). Zone types that you can assign are listed below. Enter the desired zone type code as listed.

00

= Zone Not Used

07

= 24 Hr Audible

01

= Entry/Exit Burglary

08

= 24 Hr Aux

03

= Perimeter

09 = Fire

04

= Interior Follower

10

= Interior w/Delay

05

= Trouble Day/Alarm Night

23

= No Alarm

06

= 24 Hr Silent

 

Response

2 0 Re por t Code

1 st 0 3 2 nd 1 2 3 C

2 0 Input De vic e RF Tr a ns. RF:

When the display shows the zone type you want, press [ ] to continue.

8.Enter the report code.

The report code consists of 2 hexadecimal digits, each in turn consisting of 2 numerical digits. For example, for a report code of "3C", enter [0][3] for "3" and [1][2] for "C".

See the SYSTEM COMMUNICATIONS section for complete information on report codes, if necessary.

Press [] to continue.

9.For the hardwired zones (HW), and the zones for a 5700 system's transmitters (RF), the Input Device types are automatically assigned (Panic, Duress, and Tamper inputs are not applicable).

– 29 –

Image 29
Contents VISTA-10SE Recommendations For Proper Intrusion Protection Recommendations For Smoke And Heat DetectorsTable of Contents Relay Output Devices For 5800 Series Wireless Transmitters Section Sequential ModeList of Figures HOW to USE this Manual Conventions Used in this Manual General Description Wireless ExpansionBack-Up Battery AC Power SupplyOptional Phone module Supports the Ademco 4285 Phone module Communication FormatsMounting the Cabinet Installing the ControlInstalling the Lock if used Relay Unit if installed in cabinet Standard Telephone Line Connections Standard Phone Line ConnectionsInstalling The Back-Up Battery Wiring The AC TransformerWiring Table Do not Connect the Wires to the Battery YETKeypads That May Be Used Installing Remote KeypadsWiring To The Keypads Keypad Connections To The Control Board Mounting the KeypadsUsing a Supplementary Power Supply For Keypads Preliminary Check-out ProcedureInstalling the Hard-Wired Zones Basic HARD-WIRED ZonesWiring Burglary and Panic Devices To Zones Wiring 4-Wire Smoke/Combustion Detectors on ZoneProgramming Hard-Wired Zones Zone Types Programming Check-Out Procedure For Hard-Wired ZonesSpecial Notes on Zone Wireless Systems Available Wireless RF Zone Expansion 5800 RF SystemsSeries Receiver Wireless Zones Wireless System Operation and Transmitter SupervisionWireless System Installation Advisories Transmitter Battery LifeInstallation and Setup of the 4281/5881 Wireless Receivers Receiver SupervisionBoard Series Transmitter SetupOn 5700 Series Setting the DIP SwitchesRefer to the Compatible 5700 Series TransmittersDIP Switch Tables for 5700 RF System Wireless Devices Model Product Zone/ID # Description Compatible 5700 Series TransmittersUsing the House ID Sniffer Mode 5700 Systems Programming the Control For a 5700 Wireless SystemEnter your Installer Code + # + Zone Programming For 5700 TransmittersProgramming Guide Systems Enter the Installer Code + # +Programming 5700 RF Series Transmitter Setup Temp Compatible 5800 Series TransmittersGBD Programming the RF Transmitters 5800 RF SystemsEnrolling Through Zone Programming RF House ID CodeEnrolling 5800 Transmitters Into The System ZN ZT RC In L 0 0 0 0 RF Transmitter before proceeding to the next zone Recommend that you confirm the programming of everyTransmitter ID Check-Out Procedure for Wireless ZonesSniffer Mode Go/No Go Test Relay Modules Relay Output DevicesRelay Device Basics Alarm Programming Output Relays Choices for Zone Types Example of Output Relay Programming Phone Module Wiring Installing the Phone modulePhone Module General InformationCaller ID Units Terminal Connects to4285 Wiring NotesPress 95. Ring Detection Count Programming The Control For Phone AccessVoice Answering Module Downloading Field 95 ProgrammingTo Check Phone module Operation From an Off-Premises Phone Checking the Operation of the 4285 Phone moduleTo Check Phone module Operation From an On-Premises Phone External Sounders Testing the Sounder Press 30. Alarm Bell TimeoutSounder Connections Press 51. Confirmation of Arming DingConnection Long Range RadioGeneral Information Programming Audio Alarm Verification AAVWiring Connections Connection Of AAV Unit When Not Using a 4285 Phone module To bypass this delay, press # + Final Power UPCalculating the Battery Size Needed ExampleConnections Making the BatteryDevice Current # Units Total Current Total =Section Entering Zone Descriptors program menu modeProgramming the Descriptors PressO R Alternate Method For Programming Zone Descriptors Press 6 to accept the selected wordPress 8 to save all words in memory Method For Adding Custom Words Alpha Vocabulary ListSequential Mode For 5800 Series Wireless Transmitters Serial # ↑ Page Following describes each format in greater detail System Communication+1/4+1 Report Standard Expanded Ademco Contact ID Reporting takes the following formatTable of Contact ID Event Codes Communication ProgrammingPress 46 Report FORMAT, PRIMARY/SECONDARY Press 45 Phone System Select Enter 1 digit default =Press 47 SPLIT/DUAL Reporting To Primary Phone No To Secondary Phone NoPress 60 Trouble Report Code To Program System Status and Restore Report Codes 60 68, 70Press 61 Bypass Report Code Press 62 AC Loss Report CodePress 67 RF XMTR. LOW Battery Report Code Press65 OPEN/EXIT Alarm Report CODE, 1st DigitsPress 68 Cancel Report Code Press 70 Alarm Restore Report CODE, 1st DigitPress 75 RF XMTR. LOW Battery Restore Code Press 74 LOW BAT Restore Report CodePress 92 Number of Reports in Armed Period Press 94 Download Phone NumberTest Procedure Testing the SystemTo the Installer To program a Duress code System OperationTo change the Duress code To delete the Duress codeKeypad Functions Features for Each Arming ModeDisarmed, Not Ready Forced Quick BypassIf used Keys Displayed as ZoneRelay Outputs Security Code + # +Trouble Conditions See Troubleshooting Guide also System including Wireless Troubleshooting GuideControl Read the Instructions PleaseBefore you call Technical Support, be sure you Specifications Specifications & AccessoriesVISTA-10SE Security Control Remote Keypad Remote KeypadsZones With the Ademco VISTA-10SE Transmitter ModuleRelay Module Phone Module No CN Accessories Compatible DevicesAdemco 702 Outdoor SirenFederal Communications Commission FCC Part 68 Statement Federal Communications Commission FCC Part 15 StatementUL Notices Canadian Department of Communications DOC Statement Limitations of this Alarm System ADT VISTA-10SE Summary of Connections Ademco Limited Warranty