VistaQuest N7227V5 installation instructions Testing the System, Test Procedure

Page 71

Section 15. TESTING THE SYSTEM

Test Procedure

After installation is completed, the System should be carefully tested, as follows:

1.With the System in the disarmed state, check that all zones are intact. If a NOT READY message is displayed, press the [] key to display the faulted zone(s). Restore faulted zone(s) if necessary, so that the READY message is displayed.

2.Enter the security code and press the TEST key.

The external sounder will sound for 1 second. If the backup battery is discharged or missing, the sounder may not turn on and a LOW BATTERY report will be transmitted with a TEST report.

Note that the keypad will beep once every 40 seconds as a reminder that the system is in the Test Mode.

3, Fault and restore every sensor individually to assure that it is being monitored by the system. Each time a protection zone is faulted, the keypad will sound 3 beeps, and the identification of each faulted protection zone should appear on the keypad display.

Note: For 5800 wireless systems, triggering a zone set to Arm–Away, Arm– Stay, or Disarm will take the system out of the TEST mode and cause that action.

4.Walk in front of any interior motion detectors (if used) and listen for the required sound as movement is detected. The identification of the detector should appear on the display when it is activated.

Note: Wireless motion detectors (Passive Infrared units) will send signals out only if they have been inactive for 3 minutes.

5.Follow the manufacturer's instructions to test all smoke detectors, to ensure that all are functioning properly. The identification of each detector should appear on the display when each is activated.

6 Turn off the test mode by entering the security code and pressing the OFF key.

Alarm messages will be sent to the Central Station during the following tests. Notify them in advance that tests will be in progress.

7.Arm the system (STAY) and fault one or more perimeter zones. After 15 seconds, silence alarm sounder(s) by entering the security code and pressing OFF .

Arm the system AWAY, and check the Entry/Exit zones for the programmed exit and entry delays.

8.Check the keypad-initiated alarms that are in the system by using the Panic keys (or key pairs on some keypads). If a key (or key pair) has been programmed for audible emergency, the keypad will emit a steady alarm sound, and ALARM and zone number will be displayed.

If a key (or key pair) has been programmed for silent emergency, there will be no audible alarms or displays, but a report will be sent to the Central Station.

If a key (or key pair) has been programmed for Fire, the keypad and external sounder will emit an interrupted alarm sound, and ALARM, FIRE, and zone number will be displayed.

Silence alarms by entering the security code and pressing OFF.

9.If Output Relay Units have been installed, test their programmed action.

10.Notify the Central Station when all tests are finished, and verify results with them.

(Continued)

– 71 –

Image 71
Contents VISTA-10SE Recommendations For Proper Intrusion Protection Recommendations For Smoke And Heat DetectorsTable of Contents Relay Output Devices For 5800 Series Wireless Transmitters Section Sequential ModeList of Figures HOW to USE this Manual Conventions Used in this Manual General Description Wireless ExpansionCommunication Formats AC Power SupplyBack-Up Battery Optional Phone module Supports the Ademco 4285 Phone moduleMounting the Cabinet Installing the ControlInstalling the Lock if used Relay Unit if installed in cabinet Standard Telephone Line Connections Standard Phone Line ConnectionsDo not Connect the Wires to the Battery YET Wiring The AC TransformerInstalling The Back-Up Battery Wiring TableKeypads That May Be Used Installing Remote KeypadsWiring To The Keypads Keypad Connections To The Control Board Mounting the KeypadsUsing a Supplementary Power Supply For Keypads Preliminary Check-out ProcedureWiring 4-Wire Smoke/Combustion Detectors on Zone Basic HARD-WIRED ZonesInstalling the Hard-Wired Zones Wiring Burglary and Panic Devices To ZonesProgramming Hard-Wired Zones Zone Types Programming Check-Out Procedure For Hard-Wired ZonesSpecial Notes on Zone Wireless System Operation and Transmitter Supervision Wireless RF Zone Expansion 5800 RF SystemsWireless Systems Available Series Receiver Wireless ZonesReceiver Supervision Transmitter Battery LifeWireless System Installation Advisories Installation and Setup of the 4281/5881 Wireless ReceiversBoard Series Transmitter SetupTransmitters Setting the DIP SwitchesOn 5700 Series Refer to the Compatible 5700 SeriesDIP Switch Tables for 5700 RF System Wireless Devices Model Product Zone/ID # Description Compatible 5700 Series TransmittersZone Programming For 5700 Transmitters Programming the Control For a 5700 Wireless SystemUsing the House ID Sniffer Mode 5700 Systems Enter your Installer Code + # +Programming Guide Systems Enter the Installer Code + # +Programming 5700 RF Series Transmitter Setup Temp Compatible 5800 Series TransmittersGBD Programming the RF Transmitters 5800 RF SystemsEnrolling Through Zone Programming RF House ID CodeEnrolling 5800 Transmitters Into The System ZN ZT RC In L 0 0 0 0 RF Transmitter before proceeding to the next zone Recommend that you confirm the programming of everyTransmitter ID Check-Out Procedure for Wireless ZonesSniffer Mode Go/No Go Test Relay Modules Relay Output DevicesRelay Device Basics Alarm Programming Output Relays Choices for Zone Types Example of Output Relay Programming General Information Installing the Phone modulePhone Module Wiring Phone ModuleCaller ID Units Terminal Connects to4285 Wiring NotesDownloading Field 95 Programming Programming The Control For Phone AccessPress 95. Ring Detection Count Voice Answering ModuleTo Check Phone module Operation From an Off-Premises Phone Checking the Operation of the 4285 Phone moduleTo Check Phone module Operation From an On-Premises Phone External Sounders Press 51. Confirmation of Arming Ding Press 30. Alarm Bell TimeoutTesting the Sounder Sounder ConnectionsConnection Long Range RadioGeneral Information Programming Audio Alarm Verification AAVWiring Connections Connection Of AAV Unit When Not Using a 4285 Phone module Example Final Power UPTo bypass this delay, press # + Calculating the Battery Size NeededTotal = Making the BatteryConnections Device Current # Units Total CurrentPress Entering Zone Descriptors program menu modeSection Programming the DescriptorsO R Alternate Method For Programming Zone Descriptors Press 6 to accept the selected wordPress 8 to save all words in memory Method For Adding Custom Words Alpha Vocabulary ListSequential Mode For 5800 Series Wireless Transmitters Serial # ↑ Page Following describes each format in greater detail System Communication+1/4+1 Report Standard Expanded Ademco Contact ID Reporting takes the following formatTable of Contact ID Event Codes Communication ProgrammingTo Primary Phone No To Secondary Phone No Press 45 Phone System Select Enter 1 digit default =Press 46 Report FORMAT, PRIMARY/SECONDARY Press 47 SPLIT/DUAL ReportingPress 62 AC Loss Report Code To Program System Status and Restore Report Codes 60 68, 70Press 60 Trouble Report Code Press 61 Bypass Report CodePress 70 Alarm Restore Report CODE, 1st Digit Press65 OPEN/EXIT Alarm Report CODE, 1st DigitsPress 67 RF XMTR. LOW Battery Report Code Press 68 Cancel Report CodePress 94 Download Phone Number Press 74 LOW BAT Restore Report CodePress 75 RF XMTR. LOW Battery Restore Code Press 92 Number of Reports in Armed PeriodTest Procedure Testing the SystemTo the Installer To delete the Duress code System OperationTo program a Duress code To change the Duress codeForced Quick Bypass Features for Each Arming ModeKeypad Functions Disarmed, Not ReadySecurity Code + # + Keys Displayed as ZoneIf used Relay OutputsTrouble Conditions See Troubleshooting Guide also System including Wireless Troubleshooting GuideControl Read the Instructions PleaseBefore you call Technical Support, be sure you Remote Keypads Specifications & AccessoriesSpecifications VISTA-10SE Security Control Remote KeypadZones With the Ademco VISTA-10SE Transmitter ModuleRelay Module Phone Module Siren Accessories Compatible DevicesNo CN Ademco 702 OutdoorFederal Communications Commission FCC Part 68 Statement Federal Communications Commission FCC Part 15 StatementUL Notices Canadian Department of Communications DOC Statement Limitations of this Alarm System ADT VISTA-10SE Summary of Connections Ademco Limited Warranty