Section 4. BASIC HARD-WIRED ZONES 1–6
This section provides general information for the
Also included is a procedure for programming the
Installing the Hard-Wired Zones
Common Characteristics for Zones 1–6
•Response time from 300
•Zone 3 can be programmed (in field ✱52) for normally closed sensor fast response (10 msec max) to an open (suitable for vibration type contacts). Default response is 400 msec nominal, which should be used for most standard contacts.
•EOLR supervised zones support both
•As many
Wiring Burglary and Panic Devices To Zones 1–6
1.Connect sensors/contacts to the
2.Connect closed circuit devices in series in the high (+) side the loop. The EOL resistor must be connected in series with the devices, following the last device. See the Summary of Connections diagram.
3.Connect open circuit devices in parallel across the loop. The 1,000 ohm EOLR must be connected across the loop wires at the last device.
If the EOLR is not at the end of the loop, the zone will not be properly supervised, and the system may not respond to an open circuit on the zone.
Wiring 4-Wire Smoke/Combustion Detectors on Zone 5.
The system will support as many
1.Connect 12 volt power for the detectors from Auxiliary Power terminals 4 and 5, (which will interrupt power for fire alarm reset). Observe proper polarity when connecting detectors. See Figure 7.
2.Connect detectors (including heat detectors, if used) across terminals of zone 5. All detectors must be wired in parallel.
Remove 1000 ohm EOL resistor if connected across the zone terminals. You must connect the EOL resistor across the loop wires at the last detector.
3.To meet NFPA 72 requirements, you must use a supervisory module to supervise power (e.g., System Sensor No.
AUX PWR |
| + |
|
|
|
|
|
|
| - |
|
| - |
|
|
| |
OUTPUT |
|
| BLK |
|
| + | ||
TERMINALS |
|
| • | • | ||||
|
|
|
|
|
|
| EOL | |
|
|
|
|
| • | • | POWER | |
|
| + | DETECTORS | + |
|
|
| SUPERVISION |
|
| - |
| ➔ VIOLET ➔ | RELAY | |||
|
|
| - |
|
|
| MODULE | |
|
|
|
|
|
| |||
|
|
|
|
|
|
| • |
|
|
|
|
|
|
|
|
| 1000 |
|
|
|
|
|
|
|
| OHMS |
TO HI SIDE |
|
|
|
|
|
| • | EOLR |
OF ZONE 5 | + |
|
|
|
|
|
| |
(TERM 14) | HEAT |
| HEAT |
|
|
|
| |
| - |
|
|
|
|
| ||
TO LO SIDE | DETECTOR |
| DETECTOR |
|
|
|
| |
OF ZONE 5 |
|
|
|
|
|
|
| |
(TERM 15) |
|
|
|
|
|
|
|
|
Figure 7. 4-wire Smoke Detector Connections (Zone 5.)
– 18 –