VistaQuest N7227V5 Basic HARD-WIRED Zones, Installing the Hard-Wired Zones

Page 18

Section 4. BASIC HARD-WIRED ZONES 1–6

This section provides general information for the hard-wired zones in the system, plus specific instructions for installing 4-wire smoke/combustion detectors.

Also included is a procedure for programming the hard-wired zones.

Installing the Hard-Wired Zones

Common Characteristics for Zones 1–6

Response time from 300 –500 milliseconds (400 milliseconds nominal).

Zone 3 can be programmed (in field 52) for normally closed sensor fast response (10 msec max) to an open (suitable for vibration type contacts). Default response is 400 msec nominal, which should be used for most standard contacts.

EOLR supervised zones support both open-circuit & closed-circuit devices.

As many 4-wire smoke detectors as can be powered from Aux Power on the control (on zone 5).

Wiring Burglary and Panic Devices To Zones 1–6

1.Connect sensors/contacts to the hard-wired zone terminals (8 through 16). See the Summary of Connections diagram .

2.Connect closed circuit devices in series in the high (+) side the loop. The EOL resistor must be connected in series with the devices, following the last device. See the Summary of Connections diagram.

3.Connect open circuit devices in parallel across the loop. The 1,000 ohm EOLR must be connected across the loop wires at the last device.

If the EOLR is not at the end of the loop, the zone will not be properly supervised, and the system may not respond to an open circuit on the zone.

Wiring 4-Wire Smoke/Combustion Detectors on Zone 5.

The system will support as many 4-wire detectors as can be powered from Auxiliary Power on the control on zone 5. Refer to the detector’s instructions for complete details regarding its proper installation and operation.

1.Connect 12 volt power for the detectors from Auxiliary Power terminals 4 and 5, (which will interrupt power for fire alarm reset). Observe proper polarity when connecting detectors. See Figure 7.

2.Connect detectors (including heat detectors, if used) across terminals of zone 5. All detectors must be wired in parallel.

Remove 1000 ohm EOL resistor if connected across the zone terminals. You must connect the EOL resistor across the loop wires at the last detector.

3.To meet NFPA 72 requirements, you must use a supervisory module to supervise power (e.g., System Sensor No. A77-716B Relay module).

AUX PWR

 

+

 

 

 

 

 

 

 

-

 

 

-

 

 

 

OUTPUT

 

 

BLK

 

 

+

TERMINALS

 

 

 

 

 

4-WIRE SMOKE

 

 

 

 

EOL

 

 

 

 

 

POWER

 

 

+

DETECTORS

+

 

 

 

SUPERVISION

 

 

-

 

VIOLET

RELAY

 

 

 

-

 

 

 

MODULE

 

 

 

 

 

 

A77-716B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

 

 

 

OHMS

TO HI SIDE

 

 

 

 

 

 

EOLR

OF ZONE 5

+

 

 

 

 

 

 

(TERM 14)

HEAT

 

HEAT

 

 

 

 

 

-

 

 

 

 

 

TO LO SIDE

DETECTOR

 

DETECTOR

 

 

 

 

OF ZONE 5

 

 

 

 

 

 

 

(TERM 15)

 

 

 

 

 

 

 

 

Figure 7. 4-wire Smoke Detector Connections (Zone 5.)

– 18 –

Image 18
Contents VISTA-10SE Recommendations For Smoke And Heat Detectors Recommendations For Proper Intrusion ProtectionTable of Contents Relay Output Devices Sequential Mode For 5800 Series Wireless Transmitters SectionList of Figures HOW to USE this Manual Conventions Used in this Manual Wireless Expansion General DescriptionOptional Phone module Supports the Ademco 4285 Phone module AC Power SupplyBack-Up Battery Communication FormatsInstalling the Control Installing the Lock if usedMounting the Cabinet Relay Unit if installed in cabinet Standard Phone Line Connections Standard Telephone Line ConnectionsWiring Table Wiring The AC TransformerInstalling The Back-Up Battery Do not Connect the Wires to the Battery YETInstalling Remote Keypads Wiring To The KeypadsKeypads That May Be Used Mounting the Keypads Keypad Connections To The Control BoardPreliminary Check-out Procedure Using a Supplementary Power Supply For KeypadsWiring Burglary and Panic Devices To Zones Basic HARD-WIRED ZonesInstalling the Hard-Wired Zones Wiring 4-Wire Smoke/Combustion Detectors on ZoneProgramming Hard-Wired Zones Zone Types Check-Out Procedure For Hard-Wired Zones Special Notes on ZoneProgramming Series Receiver Wireless Zones Wireless RF Zone Expansion 5800 RF SystemsWireless Systems Available Wireless System Operation and Transmitter SupervisionInstallation and Setup of the 4281/5881 Wireless Receivers Transmitter Battery LifeWireless System Installation Advisories Receiver SupervisionSeries Transmitter Setup BoardRefer to the Compatible 5700 Series Setting the DIP SwitchesOn 5700 Series TransmittersDIP Switch Tables for 5700 RF System Wireless Devices Compatible 5700 Series Transmitters Model Product Zone/ID # DescriptionEnter your Installer Code + # + Programming the Control For a 5700 Wireless SystemUsing the House ID Sniffer Mode 5700 Systems Zone Programming For 5700 TransmittersProgramming Guide Enter the Installer Code + # + Programming 5700 RFSystems Series Transmitter Setup Compatible 5800 Series Transmitters TempProgramming the RF Transmitters 5800 RF Systems GBDRF House ID Code Enrolling 5800 Transmitters Into The SystemEnrolling Through Zone Programming ZN ZT RC In L 0 0 0 0 RF Recommend that you confirm the programming of every Transmitter before proceeding to the next zoneCheck-Out Procedure for Wireless Zones Sniffer ModeTransmitter ID Go/No Go Test Relay Output Devices Relay Device BasicsRelay Modules Alarm Programming Output Relays Choices for Zone Types Example of Output Relay Programming Phone Module Installing the Phone modulePhone Module Wiring General InformationTerminal Connects to Caller ID UnitsWiring Notes 4285Voice Answering Module Programming The Control For Phone AccessPress 95. Ring Detection Count Downloading Field 95 ProgrammingChecking the Operation of the 4285 Phone module To Check Phone module Operation From an On-Premises PhoneTo Check Phone module Operation From an Off-Premises Phone External Sounders Sounder Connections Press 30. Alarm Bell TimeoutTesting the Sounder Press 51. Confirmation of Arming DingLong Range Radio General InformationConnection Audio Alarm Verification AAV Wiring ConnectionsProgramming Connection Of AAV Unit When Not Using a 4285 Phone module Calculating the Battery Size Needed Final Power UPTo bypass this delay, press # + ExampleDevice Current # Units Total Current Making the BatteryConnections Total =Programming the Descriptors Entering Zone Descriptors program menu modeSection PressO R Press 6 to accept the selected word Press 8 to save all words in memoryAlternate Method For Programming Zone Descriptors Method Alpha Vocabulary List For Adding Custom WordsSequential Mode For 5800 Series Wireless Transmitters Serial # ↑ Page System Communication Following describes each format in greater detailAdemco Contact ID Reporting takes the following format +1/4+1 Report Standard ExpandedCommunication Programming Table of Contact ID Event CodesPress 47 SPLIT/DUAL Reporting Press 45 Phone System Select Enter 1 digit default =Press 46 Report FORMAT, PRIMARY/SECONDARY To Primary Phone No To Secondary Phone NoPress 61 Bypass Report Code To Program System Status and Restore Report Codes 60 68, 70Press 60 Trouble Report Code Press 62 AC Loss Report CodePress 68 Cancel Report Code Press65 OPEN/EXIT Alarm Report CODE, 1st DigitsPress 67 RF XMTR. LOW Battery Report Code Press 70 Alarm Restore Report CODE, 1st DigitPress 92 Number of Reports in Armed Period Press 74 LOW BAT Restore Report CodePress 75 RF XMTR. LOW Battery Restore Code Press 94 Download Phone NumberTesting the System Test ProcedureTo the Installer To change the Duress code System OperationTo program a Duress code To delete the Duress codeDisarmed, Not Ready Features for Each Arming ModeKeypad Functions Forced Quick BypassRelay Outputs Keys Displayed as ZoneIf used Security Code + # +Trouble Conditions See Troubleshooting Guide also Troubleshooting Guide System including WirelessControl Please Before you call Technical Support, be sure youRead the Instructions VISTA-10SE Security Control Remote Keypad Specifications & AccessoriesSpecifications Remote KeypadsTransmitter Module Relay Module Phone ModuleZones With the Ademco VISTA-10SE Ademco 702 Outdoor Accessories Compatible DevicesNo CN SirenFederal Communications Commission FCC Part 15 Statement Federal Communications Commission FCC Part 68 StatementUL Notices Canadian Department of Communications DOC Statement Limitations of this Alarm System ADT VISTA-10SE Summary of Connections Ademco Limited Warranty