VistaQuest N7227V5 Programming Output Relays, Installer code 4 1 1 1 + 8 +

Page 41

STOP (STP): The "STOP" programming determines when and under what conditions the relay will be de-activated. The following options are available:

A)1. RESTORE ZONE LIST (ZL) . If a "ZONE LIST" is used as the “Stop” event, the relay will de-activate whenall the zones in that list restore from a previous fault, trouble, or alarm condition. This will occur regardless of what is programmed to "START" the relay; therefore, a "RESTORE ZONE LIST" would normally only be used when a "ZONE LIST" is used to start the relay.

B)1. ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using a "RESTORE ZONE LIST", a specific zone (response) type or system operation action can be selected to de-activate the relay.

If a specific "ZONE TYPE" is chosen, any zone of that response type that restores from a previous alarm, trouble, or fault condition will cause the relay to de-activate.

If a "SYSTEM OPERATION" is chosen, that operation will cause the relay to de-activate. The different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in “Programming Relays” later in this section, and in the Programming Form.

If relay outputs are used, two keypad entries available to the user are included among the system operation choices (34 and 35) that may be programmed. They can manually activate or de-activate the relay(s) for starting or stopping some action, such as turning lights on or off, etc.

These entries are: Security Code + [#] + [7] and Security Code + [#] + [8]

Note: Whichever entry is used to start/stop the action cannot also be used to stop/start it. The opposite action must either be performed by the other keypad entry or by some other event or operation offered in the programming section.

If a relay is energized before a 4-wire smoke detector is reset, the relay will be stopped by the interruption of Aux. Power that resets the smoke detector. If this is not desired, the power to the relay unit should be supplied from another 12V power source (e.g., the same source that is powering ex- ternal equipment through the relay contacts).

Programming Output Relays

1.With at least one 2-line Alpha keypad (5137AD or 6139) connected to the keypad terminals on the control, power up the system temporarily. If you had previously connected the AC transformer to the control panel, you need only plug in the transformer (to 120VAC outlet) to power up the system.

2.Enter the programming mode by keying the following on the Alpha keypad:

INSTALLER code (4 1 1 1) + 8 + 0.

Field 25 OUTPUT MODULE must have been programmed for a 4204 module (enter “3”).

3Press 80. Note that this is an interactive menu programming mode. It is used to program all output relays used in the system (4204 Relay modules). Refer to the Programming Form worksheet in the separate PROGRAMMING GUIDE for 80 Interactive Mode.

– 41 –

Image 41
Contents VISTA-10SE Recommendations For Proper Intrusion Protection Recommendations For Smoke And Heat DetectorsTable of Contents Relay Output Devices For 5800 Series Wireless Transmitters Section Sequential ModeList of Figures HOW to USE this Manual Conventions Used in this Manual General Description Wireless ExpansionBack-Up Battery AC Power SupplyOptional Phone module Supports the Ademco 4285 Phone module Communication FormatsMounting the Cabinet Installing the ControlInstalling the Lock if used Relay Unit if installed in cabinet Standard Telephone Line Connections Standard Phone Line ConnectionsInstalling The Back-Up Battery Wiring The AC TransformerWiring Table Do not Connect the Wires to the Battery YETKeypads That May Be Used Installing Remote KeypadsWiring To The Keypads Keypad Connections To The Control Board Mounting the KeypadsUsing a Supplementary Power Supply For Keypads Preliminary Check-out ProcedureInstalling the Hard-Wired Zones Basic HARD-WIRED ZonesWiring Burglary and Panic Devices To Zones Wiring 4-Wire Smoke/Combustion Detectors on ZoneProgramming Hard-Wired Zones Zone Types Programming Check-Out Procedure For Hard-Wired ZonesSpecial Notes on Zone Wireless Systems Available Wireless RF Zone Expansion 5800 RF SystemsSeries Receiver Wireless Zones Wireless System Operation and Transmitter SupervisionWireless System Installation Advisories Transmitter Battery LifeInstallation and Setup of the 4281/5881 Wireless Receivers Receiver SupervisionBoard Series Transmitter SetupOn 5700 Series Setting the DIP SwitchesRefer to the Compatible 5700 Series TransmittersDIP Switch Tables for 5700 RF System Wireless Devices Model Product Zone/ID # Description Compatible 5700 Series TransmittersUsing the House ID Sniffer Mode 5700 Systems Programming the Control For a 5700 Wireless SystemEnter your Installer Code + # + Zone Programming For 5700 TransmittersProgramming Guide Systems Enter the Installer Code + # +Programming 5700 RF Series Transmitter Setup Temp Compatible 5800 Series TransmittersGBD Programming the RF Transmitters 5800 RF SystemsEnrolling Through Zone Programming RF House ID CodeEnrolling 5800 Transmitters Into The System ZN ZT RC In L 0 0 0 0 RF Transmitter before proceeding to the next zone Recommend that you confirm the programming of everyTransmitter ID Check-Out Procedure for Wireless ZonesSniffer Mode Go/No Go Test Relay Modules Relay Output DevicesRelay Device Basics Alarm Programming Output Relays Choices for Zone Types Example of Output Relay Programming Phone Module Wiring Installing the Phone modulePhone Module General InformationCaller ID Units Terminal Connects to4285 Wiring NotesPress 95. Ring Detection Count Programming The Control For Phone AccessVoice Answering Module Downloading Field 95 ProgrammingTo Check Phone module Operation From an Off-Premises Phone Checking the Operation of the 4285 Phone moduleTo Check Phone module Operation From an On-Premises Phone External Sounders Testing the Sounder Press 30. Alarm Bell TimeoutSounder Connections Press 51. Confirmation of Arming DingConnection Long Range RadioGeneral Information Programming Audio Alarm Verification AAVWiring Connections Connection Of AAV Unit When Not Using a 4285 Phone module To bypass this delay, press # + Final Power UPCalculating the Battery Size Needed ExampleConnections Making the BatteryDevice Current # Units Total Current Total =Section Entering Zone Descriptors program menu modeProgramming the Descriptors PressO R Alternate Method For Programming Zone Descriptors Press 6 to accept the selected wordPress 8 to save all words in memory Method For Adding Custom Words Alpha Vocabulary ListSequential Mode For 5800 Series Wireless Transmitters Serial # ↑ Page Following describes each format in greater detail System Communication+1/4+1 Report Standard Expanded Ademco Contact ID Reporting takes the following formatTable of Contact ID Event Codes Communication ProgrammingPress 46 Report FORMAT, PRIMARY/SECONDARY Press 45 Phone System Select Enter 1 digit default =Press 47 SPLIT/DUAL Reporting To Primary Phone No To Secondary Phone NoPress 60 Trouble Report Code To Program System Status and Restore Report Codes 60 68, 70Press 61 Bypass Report Code Press 62 AC Loss Report CodePress 67 RF XMTR. LOW Battery Report Code Press65 OPEN/EXIT Alarm Report CODE, 1st DigitsPress 68 Cancel Report Code Press 70 Alarm Restore Report CODE, 1st DigitPress 75 RF XMTR. LOW Battery Restore Code Press 74 LOW BAT Restore Report CodePress 92 Number of Reports in Armed Period Press 94 Download Phone NumberTest Procedure Testing the SystemTo the Installer To program a Duress code System OperationTo change the Duress code To delete the Duress codeKeypad Functions Features for Each Arming ModeDisarmed, Not Ready Forced Quick BypassIf used Keys Displayed as ZoneRelay Outputs Security Code + # +Trouble Conditions See Troubleshooting Guide also System including Wireless Troubleshooting GuideControl Read the Instructions PleaseBefore you call Technical Support, be sure you Specifications Specifications & AccessoriesVISTA-10SE Security Control Remote Keypad Remote KeypadsZones With the Ademco VISTA-10SE Transmitter ModuleRelay Module Phone Module No CN Accessories Compatible DevicesAdemco 702 Outdoor SirenFederal Communications Commission FCC Part 68 Statement Federal Communications Commission FCC Part 15 StatementUL Notices Canadian Department of Communications DOC Statement Limitations of this Alarm System ADT VISTA-10SE Summary of Connections Ademco Limited Warranty