This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances.

Temporal pulse sounding for a fire alarm consists of the following:

3 pulses – pause – 3 pulses – pause – 3 pulses. . . repeated.

Sounder Connections

The VISTA–10SE provides a 12 VDC output which can power external alarm sounders (bells or sirens, see compatible sounders listed previously). This output will activate a sounder when an alarm occurs.

Make connections to alarm output terminals 3 (+) and 4 (). See Figure 11.

CONTROL BOARD

No. 702

 

 

SIREN

3

+

 

 

+

ALARM

 

OUTPUT

 

 

 

4

Figure 11. Typical Sounder Wiring

Programming for External Sounders

1.With at least one 2-line Alpha keypad (5137AD or 6139) connected to the keypad terminals on the control, power up the system temporarily. If you had previously connected the AC transformer to the control panel, you need only plug in the transformer (to 120VAC outlet) to power up the system.

2.Enter the programming mode by keying the following on the Alpha keypad:

INSTALLER code (4 1 1 1) + 8 + 0.

3.Press 28. Single Alarm Sounding per Zone/Armed Period . Enter “1” for yes, “0” for no (default).

4.Press 29. Fire Sounder Timeout.

Enter “1” for no timeout, “0” for timeout (default).

5.Press 30. Alarm Bell Timeout.

Enter 0 for no timeout, 1 for 4 min (default), 2 for 8 min, 3 for 12 min, 4 for 16 min.

6.Press 51. Confirmation of Arming Ding.

Enter “0” for no (default), “1” for yes, “2” for yes, but with RF arming only.

7.Exit the programming mode by entering 99.

Testing the Sounder

After installation of the sounder is completed, the Security System should be carefully tested, as follows.

1.Connect the battery wires from the control board to the battery, observing correct polarity.

2.Enter the INSTALLER code (4 1 1 1) and press the TEST key on the wired keypad.

The external sounder should sound for 1 second if the sounder is good and proper connections have been made. Note that if the backup battery is discharged, the sounder will not turn on.

3.To turn off the test mode, enter the INSTALLER code (4 1 1 1) and press the OFF key.

– 50 –

Image 50
Contents VISTA-10SE Recommendations For Smoke And Heat Detectors Recommendations For Proper Intrusion ProtectionTable of Contents Relay Output Devices Sequential Mode For 5800 Series Wireless Transmitters SectionList of Figures HOW to USE this Manual Conventions Used in this Manual Wireless Expansion General DescriptionOptional Phone module Supports the Ademco 4285 Phone module AC Power SupplyBack-Up Battery Communication FormatsMounting the Cabinet Installing the ControlInstalling the Lock if used Relay Unit if installed in cabinet Standard Phone Line Connections Standard Telephone Line ConnectionsWiring Table Wiring The AC TransformerInstalling The Back-Up Battery Do not Connect the Wires to the Battery YETKeypads That May Be Used Installing Remote KeypadsWiring To The Keypads Mounting the Keypads Keypad Connections To The Control BoardPreliminary Check-out Procedure Using a Supplementary Power Supply For KeypadsWiring Burglary and Panic Devices To Zones Basic HARD-WIRED ZonesInstalling the Hard-Wired Zones Wiring 4-Wire Smoke/Combustion Detectors on ZoneProgramming Hard-Wired Zones Zone Types Programming Check-Out Procedure For Hard-Wired ZonesSpecial Notes on Zone Series Receiver Wireless Zones Wireless RF Zone Expansion 5800 RF SystemsWireless Systems Available Wireless System Operation and Transmitter SupervisionInstallation and Setup of the 4281/5881 Wireless Receivers Transmitter Battery LifeWireless System Installation Advisories Receiver SupervisionSeries Transmitter Setup BoardRefer to the Compatible 5700 Series Setting the DIP SwitchesOn 5700 Series TransmittersDIP Switch Tables for 5700 RF System Wireless Devices Compatible 5700 Series Transmitters Model Product Zone/ID # DescriptionEnter your Installer Code + # + Programming the Control For a 5700 Wireless SystemUsing the House ID Sniffer Mode 5700 Systems Zone Programming For 5700 TransmittersProgramming Guide Systems Enter the Installer Code + # +Programming 5700 RF Series Transmitter Setup Compatible 5800 Series Transmitters TempProgramming the RF Transmitters 5800 RF Systems GBDEnrolling Through Zone Programming RF House ID CodeEnrolling 5800 Transmitters Into The System ZN ZT RC In L 0 0 0 0 RF Recommend that you confirm the programming of every Transmitter before proceeding to the next zoneTransmitter ID Check-Out Procedure for Wireless ZonesSniffer Mode Go/No Go Test Relay Modules Relay Output DevicesRelay Device Basics Alarm Programming Output Relays Choices for Zone Types Example of Output Relay Programming Phone Module Installing the Phone modulePhone Module Wiring General InformationTerminal Connects to Caller ID UnitsWiring Notes 4285Voice Answering Module Programming The Control For Phone AccessPress 95. Ring Detection Count Downloading Field 95 ProgrammingTo Check Phone module Operation From an Off-Premises Phone Checking the Operation of the 4285 Phone moduleTo Check Phone module Operation From an On-Premises Phone External Sounders Sounder Connections Press 30. Alarm Bell TimeoutTesting the Sounder Press 51. Confirmation of Arming DingConnection Long Range RadioGeneral Information Programming Audio Alarm Verification AAVWiring Connections Connection Of AAV Unit When Not Using a 4285 Phone module Calculating the Battery Size Needed Final Power UPTo bypass this delay, press # + ExampleDevice Current # Units Total Current Making the BatteryConnections Total =Programming the Descriptors Entering Zone Descriptors program menu modeSection PressO R Alternate Method For Programming Zone Descriptors Press 6 to accept the selected wordPress 8 to save all words in memory Method Alpha Vocabulary List For Adding Custom WordsSequential Mode For 5800 Series Wireless Transmitters Serial # ↑ Page System Communication Following describes each format in greater detailAdemco Contact ID Reporting takes the following format +1/4+1 Report Standard ExpandedCommunication Programming Table of Contact ID Event CodesPress 47 SPLIT/DUAL Reporting Press 45 Phone System Select Enter 1 digit default =Press 46 Report FORMAT, PRIMARY/SECONDARY To Primary Phone No To Secondary Phone NoPress 61 Bypass Report Code To Program System Status and Restore Report Codes 60 68, 70Press 60 Trouble Report Code Press 62 AC Loss Report CodePress 68 Cancel Report Code Press65 OPEN/EXIT Alarm Report CODE, 1st DigitsPress 67 RF XMTR. LOW Battery Report Code Press 70 Alarm Restore Report CODE, 1st DigitPress 92 Number of Reports in Armed Period Press 74 LOW BAT Restore Report CodePress 75 RF XMTR. LOW Battery Restore Code Press 94 Download Phone NumberTesting the System Test ProcedureTo the Installer To change the Duress code System OperationTo program a Duress code To delete the Duress codeDisarmed, Not Ready Features for Each Arming ModeKeypad Functions Forced Quick BypassRelay Outputs Keys Displayed as ZoneIf used Security Code + # +Trouble Conditions See Troubleshooting Guide also Troubleshooting Guide System including WirelessControl Read the Instructions PleaseBefore you call Technical Support, be sure you VISTA-10SE Security Control Remote Keypad Specifications & AccessoriesSpecifications Remote KeypadsZones With the Ademco VISTA-10SE Transmitter ModuleRelay Module Phone Module Ademco 702 Outdoor Accessories Compatible DevicesNo CN SirenFederal Communications Commission FCC Part 15 Statement Federal Communications Commission FCC Part 68 StatementUL Notices Canadian Department of Communications DOC Statement Limitations of this Alarm System ADT VISTA-10SE Summary of Connections Ademco Limited Warranty