VistaQuest N7227V5 Making the Battery, Connections, Device Current # Units Total Current, Total =

Page 55

Making the Battery

1. Use the battery standby formula (shown on previous page) to select the

Connections

appropriate battery for the installation.

 

 

Remember, when calculating the battery size needed, you must add the

 

 

100mA drawn by the control itself to the total Auxiliary current draw in the

 

 

worksheet below.

 

 

 

 

 

Do not connect the battery until all devices have been wired to the control.

 

 

 

2.Attach the Red and Black wires on the battery connector cable as follows:

a)Red to the positive (+) battery tab on the control board.*

b)Black to the negative () battery tab on the control board.*

*This not required if wires are already connected to the battery tabs on the control.

3.Attach the Red and Black wires at the other end of the battery connector cable to the battery, as follows:

a)Red to the positive (+) terminal on the battery.

b)Black to the negative (–) terminal on the battery.

AUXILIARY DEVICE CURRENT DRAW WORKSHEET

DEVICE

CURRENT

# UNITS

TOTAL CURRENT

 

 

 

(device mA x # of units)

 

 

 

 

4127 Keypad

20mA

 

 

 

 

 

 

4137AD Keypad

60mA

 

 

 

 

 

 

5137AD/ADR Keypad

90mA

 

 

 

 

 

 

6127 Keypad

20mA

 

 

 

 

 

 

6128 Keypad

30mA

 

 

 

 

 

 

6137 Keypad

85mA

 

 

 

 

 

 

6138 Keypad

100mA

 

 

 

 

 

 

6139/6139R Keypad

100mA

 

 

 

 

 

 

4281/5881/5882 Type RF Receiver

35mA

 

 

 

 

 

 

4204 Relay Unit

15/180mA

 

 

4285 Phone module

160mA

 

 

 

 

 

 

Long Range Radio

Depends on type

 

 

 

of Radio used (see

 

 

 

its instructions).

 

 

 

 

 

 

*

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

TOTAL =

 

(Current available from Aux. terminals = 500mA max.) **

 

 

*If using hard-wire devices such as PIRs, refer to the specifications for that particular unit's current draw, and include on worksheet.

Figures are for relays OFF/relays ON.

**In UL installations, maximum current draw from the Auxiliary Output and the Alarm Output combined must not exceed 600mA.

– 55 –

Image 55
Contents VISTA-10SE Recommendations For Proper Intrusion Protection Recommendations For Smoke And Heat DetectorsTable of Contents Relay Output Devices For 5800 Series Wireless Transmitters Section Sequential ModeList of Figures HOW to USE this Manual Conventions Used in this Manual General Description Wireless ExpansionCommunication Formats AC Power SupplyBack-Up Battery Optional Phone module Supports the Ademco 4285 Phone moduleInstalling the Lock if used Installing the ControlMounting the Cabinet Relay Unit if installed in cabinet Standard Telephone Line Connections Standard Phone Line ConnectionsDo not Connect the Wires to the Battery YET Wiring The AC TransformerInstalling The Back-Up Battery Wiring TableWiring To The Keypads Installing Remote KeypadsKeypads That May Be Used Keypad Connections To The Control Board Mounting the KeypadsUsing a Supplementary Power Supply For Keypads Preliminary Check-out ProcedureWiring 4-Wire Smoke/Combustion Detectors on Zone Basic HARD-WIRED ZonesInstalling the Hard-Wired Zones Wiring Burglary and Panic Devices To ZonesProgramming Hard-Wired Zones Zone Types Special Notes on Zone Check-Out Procedure For Hard-Wired ZonesProgramming Wireless System Operation and Transmitter Supervision Wireless RF Zone Expansion 5800 RF SystemsWireless Systems Available Series Receiver Wireless ZonesReceiver Supervision Transmitter Battery LifeWireless System Installation Advisories Installation and Setup of the 4281/5881 Wireless ReceiversBoard Series Transmitter SetupTransmitters Setting the DIP SwitchesOn 5700 Series Refer to the Compatible 5700 SeriesDIP Switch Tables for 5700 RF System Wireless Devices Model Product Zone/ID # Description Compatible 5700 Series TransmittersZone Programming For 5700 Transmitters Programming the Control For a 5700 Wireless SystemUsing the House ID Sniffer Mode 5700 Systems Enter your Installer Code + # +Programming Guide Programming 5700 RF Enter the Installer Code + # +Systems Series Transmitter Setup Temp Compatible 5800 Series TransmittersGBD Programming the RF Transmitters 5800 RF SystemsEnrolling 5800 Transmitters Into The System RF House ID CodeEnrolling Through Zone Programming ZN ZT RC In L 0 0 0 0 RF Transmitter before proceeding to the next zone Recommend that you confirm the programming of everySniffer Mode Check-Out Procedure for Wireless ZonesTransmitter ID Go/No Go Test Relay Device Basics Relay Output DevicesRelay Modules Alarm Programming Output Relays Choices for Zone Types Example of Output Relay Programming General Information Installing the Phone modulePhone Module Wiring Phone ModuleCaller ID Units Terminal Connects to4285 Wiring NotesDownloading Field 95 Programming Programming The Control For Phone AccessPress 95. Ring Detection Count Voice Answering ModuleTo Check Phone module Operation From an On-Premises Phone Checking the Operation of the 4285 Phone moduleTo Check Phone module Operation From an Off-Premises Phone External Sounders Press 51. Confirmation of Arming Ding Press 30. Alarm Bell TimeoutTesting the Sounder Sounder ConnectionsGeneral Information Long Range RadioConnection Wiring Connections Audio Alarm Verification AAVProgramming Connection Of AAV Unit When Not Using a 4285 Phone module Example Final Power UPTo bypass this delay, press # + Calculating the Battery Size NeededTotal = Making the BatteryConnections Device Current # Units Total CurrentPress Entering Zone Descriptors program menu modeSection Programming the DescriptorsO R Press 8 to save all words in memory Press 6 to accept the selected wordAlternate Method For Programming Zone Descriptors Method For Adding Custom Words Alpha Vocabulary ListSequential Mode For 5800 Series Wireless Transmitters Serial # ↑ Page Following describes each format in greater detail System Communication+1/4+1 Report Standard Expanded Ademco Contact ID Reporting takes the following formatTable of Contact ID Event Codes Communication ProgrammingTo Primary Phone No To Secondary Phone No Press 45 Phone System Select Enter 1 digit default =Press 46 Report FORMAT, PRIMARY/SECONDARY Press 47 SPLIT/DUAL ReportingPress 62 AC Loss Report Code To Program System Status and Restore Report Codes 60 68, 70Press 60 Trouble Report Code Press 61 Bypass Report CodePress 70 Alarm Restore Report CODE, 1st Digit Press65 OPEN/EXIT Alarm Report CODE, 1st DigitsPress 67 RF XMTR. LOW Battery Report Code Press 68 Cancel Report CodePress 94 Download Phone Number Press 74 LOW BAT Restore Report CodePress 75 RF XMTR. LOW Battery Restore Code Press 92 Number of Reports in Armed PeriodTest Procedure Testing the SystemTo the Installer To delete the Duress code System OperationTo program a Duress code To change the Duress codeForced Quick Bypass Features for Each Arming ModeKeypad Functions Disarmed, Not ReadySecurity Code + # + Keys Displayed as ZoneIf used Relay OutputsTrouble Conditions See Troubleshooting Guide also System including Wireless Troubleshooting GuideControl Before you call Technical Support, be sure you PleaseRead the Instructions Remote Keypads Specifications & AccessoriesSpecifications VISTA-10SE Security Control Remote KeypadRelay Module Phone Module Transmitter ModuleZones With the Ademco VISTA-10SE Siren Accessories Compatible DevicesNo CN Ademco 702 OutdoorFederal Communications Commission FCC Part 68 Statement Federal Communications Commission FCC Part 15 StatementUL Notices Canadian Department of Communications DOC Statement Limitations of this Alarm System ADT VISTA-10SE Summary of Connections Ademco Limited Warranty