Section 3. INSTALLING REMOTE KEYPADS

This section lists the wired keypads that may be used and provides instructions for wiring and mounting the keypads.

A preliminary check-out procedure is also provided to ensure that the connected keypads are functioning properly in the system.

Keypads That May Be Used

Fixed-Word Display: 4127, 4137AD, 6127, 6128, 6137

Alpha Display: 5137AD, 6138, 6139

Up to 4 keypads, independent of auxiliary power considerations (you may need to use an auxiliary power supply if the 500mA aux. output is exceeded)

If you are going to use a 4285 Phone module, you MUST use addressable keypads (4137AD, 5137AD, 6128, 6137, 6138, 6139) in the system, but set to the non-addressable mode (address 31).

Wiring To The Keypads

1.Determine wire gauge by referring to the wiring length/gauge chart below.

For devices (Keypads, RF Receivers, etc.) connected to a single 4-wire run, determine the current drawn by all units connected to the single wire run, then refer to the Wiring Run chart to determine the maximum wire length that can be safely used for each wire size. Current draw for all devices can be found in the SPECIFICATIONS AND ACCESSORIES section.

Note: Refer to “Auxiliary Device Current Draw Worksheet” in theFINAL POWER UP section for current draw for all keypads.

Maximum wire lengths for any device that is homerun to the control can also be determined from the chart, based on the current draw of that device alone.

Wiring Run Chart For Devices* Drawing Aux Power From The Control (12V+ & 12V–)

 

TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN

 

 

 

 

 

Wire Size

50mA or less

100mA

300mA

500mA

#22

500 ft (152m)

250 ft (76m)

80 ft (24m)

50 ft (15m)

#20

750 ft (228.6m)

380 ft (116m)

130 ft (39.6m)

80 ft (24m)

#18

1300 ft (396m)

650 ft (198m)

220 ft (67m)

130 ft (39.6m)

#16

1500 ft (457m)

1000 ft (305m)

330 ft (100.5m)

200 ft (70m)

 

 

 

 

 

*Includes Keypads, RF Receivers, Relay Units, or 4285 Phone module.

The length of all wire runs must not exceed 1500 feet (457m) when unshielded quad conductor cable is used (750 feet if shielded cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used.

2.Run field wiring from the control to the keypads (using standard 4- conductor twisted wire cable using the wire gauge determined in step 1).

3.Connect remote Keypads to terminals 4, 5, 6, and 7 on the control board, as shown in Figure 5.

– 15 –

Image 15
Contents VISTA-10SE Recommendations For Proper Intrusion Protection Recommendations For Smoke And Heat DetectorsTable of Contents Relay Output Devices For 5800 Series Wireless Transmitters Section Sequential ModeList of Figures HOW to USE this Manual Conventions Used in this Manual General Description Wireless ExpansionCommunication Formats AC Power SupplyBack-Up Battery Optional Phone module Supports the Ademco 4285 Phone moduleInstalling the Control Installing the Lock if usedMounting the Cabinet Relay Unit if installed in cabinet Standard Telephone Line Connections Standard Phone Line ConnectionsDo not Connect the Wires to the Battery YET Wiring The AC TransformerInstalling The Back-Up Battery Wiring TableInstalling Remote Keypads Wiring To The KeypadsKeypads That May Be Used Keypad Connections To The Control Board Mounting the KeypadsUsing a Supplementary Power Supply For Keypads Preliminary Check-out ProcedureWiring 4-Wire Smoke/Combustion Detectors on Zone Basic HARD-WIRED ZonesInstalling the Hard-Wired Zones Wiring Burglary and Panic Devices To ZonesProgramming Hard-Wired Zones Zone Types Check-Out Procedure For Hard-Wired Zones Special Notes on ZoneProgramming Wireless System Operation and Transmitter Supervision Wireless RF Zone Expansion 5800 RF SystemsWireless Systems Available Series Receiver Wireless ZonesReceiver Supervision Transmitter Battery LifeWireless System Installation Advisories Installation and Setup of the 4281/5881 Wireless ReceiversBoard Series Transmitter SetupTransmitters Setting the DIP SwitchesOn 5700 Series Refer to the Compatible 5700 SeriesDIP Switch Tables for 5700 RF System Wireless Devices Model Product Zone/ID # Description Compatible 5700 Series TransmittersZone Programming For 5700 Transmitters Programming the Control For a 5700 Wireless SystemUsing the House ID Sniffer Mode 5700 Systems Enter your Installer Code + # +Programming Guide Enter the Installer Code + # + Programming 5700 RFSystems Series Transmitter Setup Temp Compatible 5800 Series TransmittersGBD Programming the RF Transmitters 5800 RF SystemsRF House ID Code Enrolling 5800 Transmitters Into The SystemEnrolling Through Zone Programming ZN ZT RC In L 0 0 0 0 RF Transmitter before proceeding to the next zone Recommend that you confirm the programming of everyCheck-Out Procedure for Wireless Zones Sniffer ModeTransmitter ID Go/No Go Test Relay Output Devices Relay Device BasicsRelay Modules Alarm Programming Output Relays Choices for Zone Types Example of Output Relay Programming General Information Installing the Phone modulePhone Module Wiring Phone ModuleCaller ID Units Terminal Connects to4285 Wiring NotesDownloading Field 95 Programming Programming The Control For Phone AccessPress 95. Ring Detection Count Voice Answering ModuleChecking the Operation of the 4285 Phone module To Check Phone module Operation From an On-Premises PhoneTo Check Phone module Operation From an Off-Premises Phone External Sounders Press 51. Confirmation of Arming Ding Press 30. Alarm Bell TimeoutTesting the Sounder Sounder ConnectionsLong Range Radio General InformationConnection Audio Alarm Verification AAV Wiring ConnectionsProgramming Connection Of AAV Unit When Not Using a 4285 Phone module Example Final Power UPTo bypass this delay, press # + Calculating the Battery Size NeededTotal = Making the BatteryConnections Device Current # Units Total CurrentPress Entering Zone Descriptors program menu modeSection Programming the DescriptorsO R Press 6 to accept the selected word Press 8 to save all words in memoryAlternate Method For Programming Zone Descriptors Method For Adding Custom Words Alpha Vocabulary ListSequential Mode For 5800 Series Wireless Transmitters Serial # ↑ Page Following describes each format in greater detail System Communication+1/4+1 Report Standard Expanded Ademco Contact ID Reporting takes the following formatTable of Contact ID Event Codes Communication ProgrammingTo Primary Phone No To Secondary Phone No Press 45 Phone System Select Enter 1 digit default =Press 46 Report FORMAT, PRIMARY/SECONDARY Press 47 SPLIT/DUAL ReportingPress 62 AC Loss Report Code To Program System Status and Restore Report Codes 60 68, 70Press 60 Trouble Report Code Press 61 Bypass Report CodePress 70 Alarm Restore Report CODE, 1st Digit Press65 OPEN/EXIT Alarm Report CODE, 1st DigitsPress 67 RF XMTR. LOW Battery Report Code Press 68 Cancel Report CodePress 94 Download Phone Number Press 74 LOW BAT Restore Report CodePress 75 RF XMTR. LOW Battery Restore Code Press 92 Number of Reports in Armed PeriodTest Procedure Testing the SystemTo the Installer To delete the Duress code System OperationTo program a Duress code To change the Duress codeForced Quick Bypass Features for Each Arming ModeKeypad Functions Disarmed, Not ReadySecurity Code + # + Keys Displayed as ZoneIf used Relay OutputsTrouble Conditions See Troubleshooting Guide also System including Wireless Troubleshooting GuideControl Please Before you call Technical Support, be sure youRead the Instructions Remote Keypads Specifications & AccessoriesSpecifications VISTA-10SE Security Control Remote KeypadTransmitter Module Relay Module Phone ModuleZones With the Ademco VISTA-10SE Siren Accessories Compatible DevicesNo CN Ademco 702 OutdoorFederal Communications Commission FCC Part 68 Statement Federal Communications Commission FCC Part 15 StatementUL Notices Canadian Department of Communications DOC Statement Limitations of this Alarm System ADT VISTA-10SE Summary of Connections Ademco Limited Warranty