VistaQuest N7227V5 installation instructions Programming Hard-Wired Zones

Page 19

Compatible System Sensor 4-Wire Smoke/Combustion Detectors

1412

4-wire ionization products of combustion detector.

2412

4-wire photoelectric smoke detector.

2412TH

4-wire photoelectric smoke detector w/135°F (57°C) heat

 

detector.

A77–716B

EOL relay module (supervisory module for wired 4-wire fire

 

zone).

2112/24T

Low-profile 4-wire photoelectric smoke detector w/135°F

 

(57°C) heat detector.

 

 

Programming Hard-Wired Zones

1.With at least one 2-line Alpha keypad (5137AD or 6139) connected to the keypad terminals on the control, power up the system temporarily. If you had previously connected the AC transformer to the control panel, you need only plug in the transformer (to 120VAC outlet) to power up the system.

2.Enter the programming mode by keying the following on the Alpha keypad:

INSTALLER code (4 1 1 1) + 8 + 0.

Data fields 22 RF SYSTEM, and 25 OUTPUT RELAY MODULE must be programmed as required before continuing.

3.Press 56. Note that this is an interactive programming mode. You will use it to program zone numbers, zone types, and alarm report codes for hard-wired zones (and RF zones).

Note: If you enabled the 5800 wireless system in field 22 (a “2” entry), the first screen prompt will be “Program Tool?... 0 = No 1 = Yes ”. Enter “0” (No). The next prompt will ask you to enter zone number.

Enter Zn Num.

(00 = Quit)

01

Zone Number

Typical summary display

 

 

 

 

 

 

 

 

 

Zn

ZT

RC

In

L

 

 

02

03

00

HW:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zone Number

02 Zone Type

Perimeter 03

Zone Type

Enter the first zone number that you wish to program (or [0][0] to exit zone programming). If you are starting with zone 1, leave as is and press [] to continue.

If programming another zone, enter the desired zone number, 02, 03, etc. (zone 02 is shown in the next display). Press [] to continue.

A summary display will appear, showing the present status of that zone's programming.

Zn = zone number; ZT = zone type;

RC = report code for that zone; In = input type of zone.

Values displayed are currently programmed values.

If it is programmed satisfactorily, press [#] to back up one step and enter the next zone number, if desired.

If you want to change a zone’s programming, press []. A prompt for Zone Type will appear.

Each zone must be assigned a zone type, which defines the way in which the system responds to faults in that zone. A detailed explanation of each zone type is provided in “Response Type Definitions” inthe ZONE RESPONSE TYPE DEFINITIONS section in the Programming Guide.

Enter the desired zone type code, as listed next. The example on the left shows zone type “03”, Perimeter, entered.

– 19 –

Image 19
Contents VISTA-10SE Recommendations For Proper Intrusion Protection Recommendations For Smoke And Heat DetectorsTable of Contents Relay Output Devices For 5800 Series Wireless Transmitters Section Sequential ModeList of Figures HOW to USE this Manual Conventions Used in this Manual General Description Wireless ExpansionCommunication Formats AC Power SupplyBack-Up Battery Optional Phone module Supports the Ademco 4285 Phone moduleInstalling the Lock if used Installing the ControlMounting the Cabinet Relay Unit if installed in cabinet Standard Telephone Line Connections Standard Phone Line ConnectionsDo not Connect the Wires to the Battery YET Wiring The AC TransformerInstalling The Back-Up Battery Wiring TableWiring To The Keypads Installing Remote KeypadsKeypads That May Be Used Keypad Connections To The Control Board Mounting the KeypadsUsing a Supplementary Power Supply For Keypads Preliminary Check-out ProcedureWiring 4-Wire Smoke/Combustion Detectors on Zone Basic HARD-WIRED ZonesInstalling the Hard-Wired Zones Wiring Burglary and Panic Devices To ZonesProgramming Hard-Wired Zones Zone Types Special Notes on Zone Check-Out Procedure For Hard-Wired ZonesProgramming Wireless System Operation and Transmitter Supervision Wireless RF Zone Expansion 5800 RF SystemsWireless Systems Available Series Receiver Wireless ZonesReceiver Supervision Transmitter Battery LifeWireless System Installation Advisories Installation and Setup of the 4281/5881 Wireless ReceiversBoard Series Transmitter SetupTransmitters Setting the DIP SwitchesOn 5700 Series Refer to the Compatible 5700 SeriesDIP Switch Tables for 5700 RF System Wireless Devices Model Product Zone/ID # Description Compatible 5700 Series TransmittersZone Programming For 5700 Transmitters Programming the Control For a 5700 Wireless SystemUsing the House ID Sniffer Mode 5700 Systems Enter your Installer Code + # +Programming Guide Programming 5700 RF Enter the Installer Code + # +Systems Series Transmitter Setup Temp Compatible 5800 Series TransmittersGBD Programming the RF Transmitters 5800 RF SystemsEnrolling 5800 Transmitters Into The System RF House ID CodeEnrolling Through Zone Programming ZN ZT RC In L 0 0 0 0 RF Transmitter before proceeding to the next zone Recommend that you confirm the programming of everySniffer Mode Check-Out Procedure for Wireless ZonesTransmitter ID Go/No Go Test Relay Device Basics Relay Output DevicesRelay Modules Alarm Programming Output Relays Choices for Zone Types Example of Output Relay Programming General Information Installing the Phone modulePhone Module Wiring Phone ModuleCaller ID Units Terminal Connects to4285 Wiring NotesDownloading Field 95 Programming Programming The Control For Phone AccessPress 95. Ring Detection Count Voice Answering ModuleTo Check Phone module Operation From an On-Premises Phone Checking the Operation of the 4285 Phone moduleTo Check Phone module Operation From an Off-Premises Phone External Sounders Press 51. Confirmation of Arming Ding Press 30. Alarm Bell TimeoutTesting the Sounder Sounder ConnectionsGeneral Information Long Range RadioConnection Wiring Connections Audio Alarm Verification AAVProgramming Connection Of AAV Unit When Not Using a 4285 Phone module Example Final Power UPTo bypass this delay, press # + Calculating the Battery Size NeededTotal = Making the BatteryConnections Device Current # Units Total CurrentPress Entering Zone Descriptors program menu modeSection Programming the DescriptorsO R Press 8 to save all words in memory Press 6 to accept the selected wordAlternate Method For Programming Zone Descriptors Method For Adding Custom Words Alpha Vocabulary ListSequential Mode For 5800 Series Wireless Transmitters Serial # ↑ Page Following describes each format in greater detail System Communication+1/4+1 Report Standard Expanded Ademco Contact ID Reporting takes the following formatTable of Contact ID Event Codes Communication ProgrammingTo Primary Phone No To Secondary Phone No Press 45 Phone System Select Enter 1 digit default =Press 46 Report FORMAT, PRIMARY/SECONDARY Press 47 SPLIT/DUAL ReportingPress 62 AC Loss Report Code To Program System Status and Restore Report Codes 60 68, 70Press 60 Trouble Report Code Press 61 Bypass Report CodePress 70 Alarm Restore Report CODE, 1st Digit Press65 OPEN/EXIT Alarm Report CODE, 1st DigitsPress 67 RF XMTR. LOW Battery Report Code Press 68 Cancel Report CodePress 94 Download Phone Number Press 74 LOW BAT Restore Report CodePress 75 RF XMTR. LOW Battery Restore Code Press 92 Number of Reports in Armed PeriodTest Procedure Testing the SystemTo the Installer To delete the Duress code System OperationTo program a Duress code To change the Duress codeForced Quick Bypass Features for Each Arming ModeKeypad Functions Disarmed, Not ReadySecurity Code + # + Keys Displayed as ZoneIf used Relay OutputsTrouble Conditions See Troubleshooting Guide also System including Wireless Troubleshooting GuideControl Before you call Technical Support, be sure you PleaseRead the Instructions Remote Keypads Specifications & AccessoriesSpecifications VISTA-10SE Security Control Remote KeypadRelay Module Phone Module Transmitter ModuleZones With the Ademco VISTA-10SE Siren Accessories Compatible DevicesNo CN Ademco 702 OutdoorFederal Communications Commission FCC Part 68 Statement Federal Communications Commission FCC Part 15 StatementUL Notices Canadian Department of Communications DOC Statement Limitations of this Alarm System ADT VISTA-10SE Summary of Connections Ademco Limited Warranty