10. Troubleshooting
Problem | Possible Cause |
|
|
Burner operates but does not cycle from | 1. Check the gas pressure reading on the gauge. Problem may be |
due to insufficient gas regulator setting. Temporarily decrease | |
| the |
| thermostat will function and cause the burner to cycle. If burner |
| will cycle at the reduced thermostat setting, it indicates that the |
| problem was due to insufficient heat to satisfy the original |
| setting. Increase the gas regulator setting for additional |
| heat output. Do not exceed the maximum pressure listed in |
| this manual. |
| 2. |
| still does not cycle to |
| the problem may be due to a broken or kinked thermostat |
| sensor tube. Observe reading on the thermometer. Replace |
| control assembly if it cannot be set to cause its switch to go |
| to the open circuit position with normally hot air plenum |
| temperatures. |
| 3. If the burner continues to operate on |
| |
| condition, or for reversed gas pipe connections. The solenoid |
| valve must not allow gas flow when its coil is not energized. |
Burner operates but does not cycle from | 1. Check for an excessive |
to | pressure setting shown on gauge, and compare reading with |
| recommended low pressure settings listed in this manual. |
| Readjust |
| 2. Check for improperly adjusted or defective |
| thermostat control. Temporarily increase the temperature |
| setting. If the heater will still not cycle, check for problem in the |
| control wire connections. The control wires should be connected |
| to terminals R and B of the thermostat, so the switch will open |
| upon temperature rise. If the burner will cycle with these two |
| wires connected together, the thermostat is faulty. |
| 3. Check for improperly connected or faulty |
| solenoid valve. Correct any poor connections or defective |
| wiring. If wiring appears proper, problem may be caused by a |
| burned out valve coil or defective valve. Replace |
| solenoid valve, or its coil, if defective. |
If the Load and Unload Auger does not start but | Check the fuse on the I/O Board in the back of the lower |
everything else seems to work. | control Box. |
60