ADC AD-464 service manual Combustion Air Damper

Page 61

4)Combustion Air Damper

To produce the required combustion airflow, this damper can be adjusted. Remove the screen to get access to the damper. Moving the damper closer to the blower inlet opening will reduce the combustion airflow, and moving it away from the blower inlet opening will increase the airflow. To measure the combustion airflow, attached a manometer to the air pressure tap on the burner box. The air pressure should measure 1.25- inches (31.75 mm) to 1.5-inches (38.1 mm) water column (W.C.).

e.Pilot Gas Supply Line

1)The pilot gas supply line consists of a manual shut-off valve, pressure regulator, electric solenoid valve, back-loaded pressure regulator, and an adjustable gas cock.

2)The gas pressure in this line should be approximately 3.5-inches (88.9 mm) water column (W.C.) for natural gas and 1.5-inches (38.1 mm) water column for L.P. (liquid propane) gas. This will provide a bushy pilot flame, which produces a signal through the flame rod that is converted to 3 to 11 volts DC in the burner controller module (BMC).

a)This flame can be adjusted in two (2) ways.

(1)Pilot Inlet Pressure Regulator

Remove the cap and turn the slotted adjustment screw clockwise (CW) for more gas and counterclockwise (CCW) for less gas.

(2)Adjustable Pilot Gas Cock

Remove the cap and turn the slotted adjustment screw clockwise (WC) for less gas and counterclockwise (CCW) for more gas.

b)The pilot line contains a back-loaded pressure regulator with an impulse line connected to the gas burner inlet. The regulator will maintain a constant pilot supply pressure in the burner due to an increase in temperature. DO NOT adjust this regulator.

f.Main Gas Supply Line

The main gas supply line consists of a pressure regulator, two (2) motorized shut-off valves, HI/LO gas pressure switch, manual shut-off valve.

The gas pressure at the burner should be 2.5-inches (63.5 mm) water column (W.C.) for natural gas and 1.25-inches (31.8 mm) water column for L.P. (liquid propane) gas. This pressure is measured by a manometer at the manual shut-off valve just top motorized valve.

1)Motorized Gas Valve

The two (2) 2-inch F.P.T. motorized valve are “ON/OFF” gas flow control valves. The valves motors operate on 120 VAC and are electrically “cascaded” so that upper valve will not open until lower valve has fully opened. A limit switch inside the lower motorized valve provides the signal that the valve is fully opened. These valves will open only when the burner controller module (BCM) is receiving a signal from the flame rod proving that the pilot flame is established.

57

Image 61
Contents American Dryer Corporation Important Note to Purchaser Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Section Sprinkler System Section Pendant AssemblySection AIR JET System Explosion could Result Safety PrecautionsNational Electric Code ANSI/NFPA no -LATEST Edition StandardsCleaning Routine MaintenanceLiquids Monthly Lubrication Days After Installation and Every 6 Months Thereafter AdjustmentsGAS Models ADG-464 SpecificationsSteam Models ADS-464 ADG-464 GAS Electrical Service SpecificationsEnclosure / AIR Supply / Exhaust Requirements Installation RequirementsElectrical Requirements and GAS Requirements Operational Service Check ProcedureTumbler Support and Drive System Component DESCRIPTION/REPLACEMENTPage Main AIR BLOWER/HEAT Reclaimer System +Z=X Compressed AIR System Filter element can be cleaned with soap and waterPage Page Page Safety Devices Safety Devices Locations/Functions/Messages Blower Squirrel Cage Fan Motor Assembly Pulley Removal Page Important do not Overtighten V-BELTS FreelyImportant do not Overtighten V-BELTS Blower Squirrel Cage Fan Electrical Components Page Tumbler Basket System Page Page Important do not Overtighten Turnbuckle Important do not Overtighten Turnbuckle Result in Damage to the Dryer and will Void the Warranty Important do not Overtighten Bolts Page Current Limiting Device is Required Rotational Sensor AssemblyPage TOP of Tumbler Basket Temperature Door Assembly Tumbler Basket Electrical Components Page PLC Programmable Logic Controller Description PLC Programmable Logic Controller SystemPage Page 111 PLC Programmable Logic Controller Component Replacement Page Page RTD Page Switch #1 Recycling Mode Page Page Page Combustion Air Damper Page Page Page Burner Air Switch Page Page Page Page Page Page Heat Reclaimer Settings Page Page Important Allow a full 72 hours for the silicone to cure Page Page Page Page Base Section Lint DRAWER/LINT Chamber SwitchesPage Page Resistive Temperature Device RTD RTD Resistive Temperature Device Locations Sprinkler System Description Sprinkler SystemPage MAN3190 Page AIR JET System AIR JET SystemPneumatic Valve Stack Valve AssemblyImportant Take Notice ... small components Page MAN4223 Internal Pilot and External Pilot Air Supply Pendant Assembly Description Pendant AssemblyADC450186 05/27/99-25 01/14/00-15