Input 0,9 is used to sense if the burner doors are closed. This is accomplished through DS4A and DS5A (Door Switch 4, A and Door Switch 5 , A) contact sets. If a drying cycle is attempted, the XBT unit will display "DOOR OPEN."

Input 0,10 is used to monitor a stopped tumbler (basket) condition. An inductive proximity sensor is located in the left wrapper of the tumbler (basket) section. Behind one of the ribs on the front side of the tumbler (basket), a steel target is mounted. As the target passes the proximity switch, it turns its output on (110 VAC), turning on Input 0,10. If the target does not pass the proximity switch with- in 12-seconds the output turns off, shutting the heat off and the XBT unit will display "DRUM FAULT."

Input 0,11 and Input 0,12 are used to determine that the dryer is in a level position before a drying cycle can be initiated (started/run). Each set of tilting pistons has a level switch in conjunction with it. If a drying cycle is attempted with a level switch in the normally open position, the XBT unit will display "LEVEL FAULT."

Input 0,13 is used as a Visual Display Only for dryers manufactured prior to January 31, 1997. On dryers manufactured as of January 31, 1997, Input 0,13 still has no direct control and is used only as a display. However, on dryers manufactured as of January 31, 1997, there is a proximity switch used to sense that the exhaust probe access door is closed. If the door is open, the dryer will shut down and a "DOOR OPEN" message will be displayed via the TSX17 Programmable Logic Controller (PLC) Input 0,9.

Input 0,14 is used to sense that the burner controller has turned on the incoming gas valve during a heat cycle, which in turn activates the heat reclaimer.

Input 0,15 and Input 0,16 are used as an operator interface in conjunction with the pendent. With 110 VAC on, Input 0,15 the dryer will prepare for loading. The load door will open and depending on options and programming, the dryer may tilt (Front Up). With Input 0,15 or Input 0,16 on, the dryer will level, close door, and a drying cycle can be initiated (started). Input 0,16 is used for unloading, open door, and if applicable, the rear will tilt up.

Input 0,17 is used for Jog Forward. It turns/spins the tumbler (basket) in a clockwise (CW) rotation while in a load or unload condition.

Input 0,18 is used for Jog Reverse. It turns/spins the tumbler (basket) in a counterclockwise (CCW) rotation while in a load or unload condition.

Input 0,19 is only used on dryers manufactured with Rear Doors. When Input 0,19 is on, the rear doors will open and the front of the dryer will tilt to unload if the pistons as well as the software are configured for this operation. If Input 0,15 or Input 0,16 are on, then Input 0,19, will have no affect on the dryer

Input 0,20 (Drum Reverse) and Input 0,21 (Drum Forward) are used to jog the load during a rear panel un- load (Input 0,19 on).

45

Image 49
Contents American Dryer Corporation Important Note to Purchaser Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Section Sprinkler System Section Pendant AssemblySection AIR JET System Explosion could Result Safety PrecautionsNational Electric Code ANSI/NFPA no -LATEST Edition StandardsCleaning Routine MaintenanceLiquids Monthly Lubrication Days After Installation and Every 6 Months Thereafter AdjustmentsGAS Models ADG-464 SpecificationsSteam Models ADS-464 ADG-464 GAS Electrical Service SpecificationsEnclosure / AIR Supply / Exhaust Requirements Installation RequirementsElectrical Requirements and GAS Requirements Operational Service Check ProcedureTumbler Support and Drive System Component DESCRIPTION/REPLACEMENTPage Main AIR BLOWER/HEAT Reclaimer System +Z=X Compressed AIR System Filter element can be cleaned with soap and waterPage Page Page Safety Devices Safety Devices Locations/Functions/Messages Blower Squirrel Cage Fan Motor Assembly Pulley Removal Page Important do not Overtighten V-BELTS FreelyImportant do not Overtighten V-BELTS Blower Squirrel Cage Fan Electrical Components Page Tumbler Basket System Page Page Important do not Overtighten Turnbuckle Important do not Overtighten Turnbuckle Result in Damage to the Dryer and will Void the Warranty Important do not Overtighten Bolts Page Current Limiting Device is Required Rotational Sensor AssemblyPage TOP of Tumbler Basket Temperature Door Assembly Tumbler Basket Electrical Components Page PLC Programmable Logic Controller Description PLC Programmable Logic Controller SystemPage Page 111 PLC Programmable Logic Controller Component Replacement Page Page RTD Page Switch #1 Recycling Mode Page Page Page Combustion Air Damper Page Page Page Burner Air Switch Page Page Page Page Page Page Heat Reclaimer Settings Page Page Important Allow a full 72 hours for the silicone to cure Page Page Page Page Base Section Lint DRAWER/LINT Chamber SwitchesPage Page Resistive Temperature Device RTD RTD Resistive Temperature Device Locations Sprinkler System Description Sprinkler SystemPage MAN3190 Page AIR JET System AIR JET SystemPneumatic Valve Stack Valve AssemblyImportant Take Notice ... small components Page MAN4223 Internal Pilot and External Pilot Air Supply Pendant Assembly Description Pendant AssemblyADC450186 05/27/99-25 01/14/00-15