Page 87

2.Sprinkler System Component Replacement

a.Resistive Temperature Device (RTD) Replacement

The sprinkler digital temperature controller is a programmable microprocessor (computer). It is used to monitor temperature via a Resistive Temperature Device (RTD).

NOTE: For RTD (Resistive Temperature Device) probe location, refer to the top illustration on page 80.

1)Discontinue water supply to the dryers' sprinkler system.

2)Discontinue electrical service to the dryer.

3)Remove probe(s) junction box cover.

4)Identify wire(s) from defective RTD probe(s).

5)Mark the position of the wire(s) in the terminal block that will be removed for proper reinstallation.

6)Remove wire(s) from terminal block.

7)Loosen compression fitting(s) and remove defective probe(s).

8)To install new probe(s), reverse Step #7 thru Step #3.

9)Reestablish electrical service to the dryer.

10)Reestablish water supply to the dryer. b. Sprinkler Valve Replacement

1)Turn the water supply to the dryer off.

2) Discontinue electric service to the dryer.

3) Disconnect compressed air supply from the dryer.

4)Loosen and remove the hose clamp.

5)Remove any residual water to the valve.

6) Remove 1/4" air tubing going to the valve.

MAN3190

7)Remove the two (2) U-bolts holding the sprinkler valve assembly.

8)Unscrew the sprinkler valve from the tubing.

9)To install new sprinkler valve, reverse Step #8 thru Step #3.

9)Reestablish electrical service to the dryer.

10)Reestablish water supply to the dryer.

83

Image 87
Contents American Dryer Corporation Important Note to Purchaser Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Section Pendant Assembly Section Sprinkler SystemSection AIR JET System Explosion could Result Safety PrecautionsNational Electric Code ANSI/NFPA no -LATEST Edition StandardsRoutine Maintenance CleaningLiquids Monthly Lubrication Days After Installation and Every 6 Months Thereafter AdjustmentsGAS Models ADG-464 SpecificationsSteam Models ADS-464 ADG-464 GAS Electrical Service SpecificationsEnclosure / AIR Supply / Exhaust Requirements Installation RequirementsElectrical Requirements and GAS Requirements Operational Service Check ProcedureTumbler Support and Drive System Component DESCRIPTION/REPLACEMENTPage Main AIR BLOWER/HEAT Reclaimer System +Z=X Compressed AIR System Filter element can be cleaned with soap and waterPage Page Page Safety Devices Safety Devices Locations/Functions/Messages Blower Squirrel Cage Fan Motor Assembly Pulley Removal Page Important do not Overtighten V-BELTS FreelyImportant do not Overtighten V-BELTS Blower Squirrel Cage Fan Electrical Components Page Tumbler Basket System Page Page Important do not Overtighten Turnbuckle Important do not Overtighten Turnbuckle Result in Damage to the Dryer and will Void the Warranty Important do not Overtighten Bolts Page Current Limiting Device is Required Rotational Sensor AssemblyPage TOP of Tumbler Basket Temperature Door Assembly Tumbler Basket Electrical Components Page PLC Programmable Logic Controller Description PLC Programmable Logic Controller SystemPage Page 111 PLC Programmable Logic Controller Component Replacement Page Page RTD Page Switch #1 Recycling Mode Page Page Page Combustion Air Damper Page Page Page Burner Air Switch Page Page Page Page Page Page Heat Reclaimer Settings Page Page Important Allow a full 72 hours for the silicone to cure Page Page Page Page Base Section Lint DRAWER/LINT Chamber SwitchesPage Page Resistive Temperature Device RTD RTD Resistive Temperature Device Locations Sprinkler System Description Sprinkler SystemPage MAN3190 Page AIR JET System AIR JET SystemPneumatic Valve Stack Valve AssemblyImportant Take Notice ... small components Page MAN4223 Internal Pilot and External Pilot Air Supply Pendant Assembly Description Pendant AssemblyADC450186 05/27/99-25 01/14/00-15