5.
The dryer utilizes six (6) channel controller
•Channel #1 is used to monitor the exhaust for an over temperature situation.
•Channel #2 is used as an over burner monitor (for Gas Models Only).
•Channel #3 is used to monitor intake temperature (for Gas Models Only).
•The remaining channels are spares that can be used for future expansion. a.
1)Discontinue electrical service to the dryer.
2)Loosen the four (4) screws hold the
3)Slide the mounting bracket off of the screws through the keyhole.
4)Disconnect the plug going to the
Current
Production
5) Remove the two (2) screws holding the mounting slides. | Past |
Production |
6) Remove the two (2) slides.
7) To install new
8) Reestablish electrical service to the dryer.
|
|
| GAS |
|
| STEAM |
| ºF | ºC | ºF | ºC | ||
RTD 1 | 225 | 107 | Exhaust Temp. Limit | 225 | 107 | Exhaust Temp. Limit |
RTD 2 | 200 | 93 | Over Burner Temp. | 650 | 343 | Intake Temperature |
RTD 3 | 650 | 343 | Intake Temperature | 500 | 260 | N/A* |
RTD 4 | 500 | 260 | N/A* | 500 | 260 | N/A* |
RTD 5 | 500 | 260 | N/A* | 500 | 260 | N/A* |
RTD 6 | 500 | 260 | N/A* | 500 | 260 | N/A* |
* Not applicable...controller channels must be set to 500º F (260 ºC).
51