5.Hi-Limit Controller

The dryer utilizes six (6) channel controller (HLC-1) to monitor various locations on the dryer for over temperature faults. The hi-limit controller enables the dryer to continually monitor up to six (6) Resistive Temperature Devices (RTD's) at one time. Each channel is individual with set points. The hi-limit controller scans each channel, and in the event of an alarm, the scanning will halt (stop), and the Single-Pole-Double- Throw (SPDT) will change states signaling a fault. The hi-limit controller will remain in alarm until the reset button is pushed and the temperature has fallen below the set-point temperature. The scan rate can be adjusted from 4 to 12-seconds per channel.

Channel #1 is used to monitor the exhaust for an over temperature situation.

Channel #2 is used as an over burner monitor (for Gas Models Only).

Channel #3 is used to monitor intake temperature (for Gas Models Only).

The remaining channels are spares that can be used for future expansion. a. Hi-Limit Controller Replacement

1)Discontinue electrical service to the dryer.

2)Loosen the four (4) screws hold the hi-limit mounting bracket.

3)Slide the mounting bracket off of the screws through the keyhole.

4)Disconnect the plug going to the hi-limit controller.

Current

Production

5) Remove the two (2) screws holding the mounting slides.

Past

Production

6) Remove the two (2) slides.

7) To install new hi-limit controller, reverse Step #6 thru Step #2.

8) Reestablish electrical service to the dryer.

HI-LIMIT CONTROLLER TEMPERATURE SPECIFICATIONS

 

 

 

GAS

 

 

STEAM

 

ºF

ºC

HI-LIMIT NAME

ºF

ºC

HI-LIMIT NAME

RTD 1

225

107

Exhaust Temp. Limit

225

107

Exhaust Temp. Limit

RTD 2

200

93

Over Burner Temp.

650

343

Intake Temperature

RTD 3

650

343

Intake Temperature

500

260

N/A*

RTD 4

500

260

N/A*

500

260

N/A*

RTD 5

500

260

N/A*

500

260

N/A*

RTD 6

500

260

N/A*

500

260

N/A*

* Not applicable...controller channels must be set to 500º F (260 ºC).

51

Image 55
Contents American Dryer Corporation Important Note to Purchaser Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Section Sprinkler System Section Pendant AssemblySection AIR JET System Explosion could Result Safety PrecautionsNational Electric Code ANSI/NFPA no -LATEST Edition StandardsCleaning Routine MaintenanceLiquids Monthly Lubrication Days After Installation and Every 6 Months Thereafter AdjustmentsGAS Models ADG-464 SpecificationsSteam Models ADS-464 ADG-464 GAS Electrical Service SpecificationsEnclosure / AIR Supply / Exhaust Requirements Installation RequirementsElectrical Requirements and GAS Requirements Operational Service Check ProcedureTumbler Support and Drive System Component DESCRIPTION/REPLACEMENTPage Main AIR BLOWER/HEAT Reclaimer System +Z=X Compressed AIR System Filter element can be cleaned with soap and waterPage Page Page Safety Devices Safety Devices Locations/Functions/Messages Blower Squirrel Cage Fan Motor Assembly Pulley Removal Page Important do not Overtighten V-BELTS FreelyImportant do not Overtighten V-BELTS Blower Squirrel Cage Fan Electrical Components Page Tumbler Basket System Page Page Important do not Overtighten Turnbuckle Important do not Overtighten Turnbuckle Result in Damage to the Dryer and will Void the Warranty Important do not Overtighten Bolts Page Current Limiting Device is Required Rotational Sensor AssemblyPage TOP of Tumbler Basket Temperature Door Assembly Tumbler Basket Electrical Components Page PLC Programmable Logic Controller Description PLC Programmable Logic Controller SystemPage Page 111 PLC Programmable Logic Controller Component Replacement Page Page RTD Page Switch #1 Recycling Mode Page Page Page Combustion Air Damper Page Page Page Burner Air Switch Page Page Page Page Page Page Heat Reclaimer Settings Page Page Important Allow a full 72 hours for the silicone to cure Page Page Page Page Base Section Lint DRAWER/LINT Chamber SwitchesPage Page Resistive Temperature Device RTD RTD Resistive Temperature Device Locations Sprinkler System Description Sprinkler SystemPage MAN3190 Page AIR JET System AIR JET SystemPneumatic Valve Stack Valve AssemblyImportant Take Notice ... small components Page MAN4223 Internal Pilot and External Pilot Air Supply Pendant Assembly Description Pendant AssemblyADC450186 05/27/99-25 01/14/00-15