Mitsubishi Electronics FR-F700 Relay output 1 alarm, Output, 30VDC 0.3A, Permissible load 24VDC

Page 17

Type

Terminal Symbol

Terminal Name

 

Description

 

 

 

 

 

Relay output 1 (alarm

Changeover contact output indicates that the inverter protective function has activated and the

 

Relay

A1, B1, C1

output stopped. Abnormal: No conduction across B-C (Across A-C Continuity), Normal: Across

 

output)

B-C Continuity (No conduction across A-C) Contact capacity: 230VAC 0.3A (Power factor=0.4)

 

 

 

 

 

 

 

30VDC 0.3A

 

 

 

 

 

 

 

 

 

 

 

A2, B2, C2

Relay output 2

1 changeover contact output Contact capacity: 230VAC 0.3A (Power factor=0.4) 30VDC 0.3A

 

 

 

RUN

Inverter running

Switched low when the inverter output frequency is equal to or

 

 

 

 

higher than the starting frequency (initial value 0.5Hz). Switched

 

 

 

 

 

 

high during stop or DC injection brake operation.*1

 

 

 

 

SU

Up to frequency

Switched low when the output frequency reaches within the range

Permissible load 24VDC

 

 

 

of ±10% (initial value) of the set frequency. Switched high during

0.1A

 

Open collector

 

 

 

acceleration/deceleration and at a stop.*1

(a voltage drop is 3.4V

 

 

 

 

Switched low when stall prevention is activated by the stall

maximum when the signal

circuitoutput signal

 

OL

Overload alarm

prevention function. Switched high when stall prevention is

is on)

 

 

 

cancelled. *1

 

Alarm code (4bit) output

 

IPF

Instantaneous power

Switched low when an instantaneous power failure and under

 

failure

voltage protections are activated. *1

(Refer to page 36)

 

 

 

FU

Frequency detection

Switched low when the inverter output frequency is equal to or

 

 

higher than the preset detected frequency and high when less than

 

 

 

 

the preset detected frequency. *1

 

Control

 

 

SE

Open collector output

Common terminal for terminals RUN, SU, OL, IPF, FU

 

 

 

common

 

 

 

 

 

 

 

 

 

 

 

 

 

Output item:

 

Pulse

 

 

 

 

 

Output frequency (initial

 

 

FM

For meter

 

 

setting)

 

 

 

 

Permissible load current

 

 

 

 

 

 

 

2mA

 

 

 

 

 

Select one e.g. output frequency from monitor items. *2

1440 pulses/s at 60Hz

 

 

 

 

 

Output item:

 

 

 

 

 

The output signal is proportional to the magnitude of the

 

 

 

 

 

Output frequency (initial

 

 

 

 

 

corresponding monitoring item.

 

 

 

 

 

setting)

 

Analog

 

 

 

 

 

 

 

AM

Analog signal output

 

 

Output signal 0 to 10VDC

 

 

 

 

Permissible load current

 

 

 

 

 

 

 

 

 

 

 

 

1mA (load impedance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10kΩ or more) Resolution

 

 

 

 

 

 

 

8 bit

 

 

 

 

 

With the PU connector, communication can be made through RS-485.

 

 

 

 

 

(for connection on a 1:1 basis only)

 

Communication

PU connector

PU connector

. Conforming standard

: EIA-485(RS-485)

 

. Transmission format

: Multidrop

 

 

 

 

 

 

 

 

. Communication speed

: 4800 to 38400bps

 

 

 

 

. Overall length

: 500m

 

 

TXD+

Inverter transmission

With the RS-485 terminal, communication can be made through RS-485.

RS-485

TXD-

terminal

Conforming standard

: EIA-485 (RS-485)

 

RXD+

Inverter reception

Transmission format

: Multidrop link

 

 

 

terminal

 

 

 

RXD-

terminal

Communication speed

: 300 to 38400bps

 

 

 

 

 

 

 

 

SG

Earth (Ground)

Overall length

: 500m

 

CAUTION

The inverter will be damaged if power is applied to the inverter output terminals (U, V, W). Never perform such wiring.

indicates that terminal functions can be selected fromPr. 178 to Pr. 196 (I/O terminal function selection)

*1. Low indicates that the open collector output transistor is on (conducts). High indicates that the transistor is off (does not conduct).

*2. Not output during inverter reset.

 

 

Features

 

 

 

 

 

 

 

 

Peripheral Devices

Why energy

savings?

 

 

 

 

 

 

 

Standard

Specifications

 

 

 

 

 

 

 

Outline

Dimension

Drawings

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Connection

Diagram

Terminal Specification

Explanation

 

 

 

 

 

 

 

Operation

Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

List

 

 

 

 

 

 

 

 

 

 

 

 

 

Explanations

of

Parameters

 

 

 

 

 

 

 

Protective

Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compatibility

 

 

 

 

 

 

 

 

 

 

Warranty

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inquiry

 

 

 

 

 

 

 

 

18

Image 17
Contents FR-F700 Energy savings for buildings and factories as a whole Warranty Inquiry Outline Dimension DrawingsInverter FR-F700 Connection with Peripheral DevicesDamper control discharge side Why Can the Inverter Save Energy?Amount Inverter controlRating Standard SpecificationsType FR-F720-K Type FR-F740-KCan be selected Common specificationsOperating status Open collectorInverter Type Outline Dimension DrawingsFR-F720-0.75K 110 FR-F720-1.5K 125 FR-F740-0.75K to 2K are not provided With a cooling fanFR-F740-15K, 18.5K Wiring coverFR-F720-30K is Not provided with aFR-F740-75K 140 120 Inverter Type Mass295 185 FR-HEL-H75K FR-F740-90K 150 130 310 190 FR-HEL-H90KFR-F740-110KFR-HEL-H110K DC reactor suppliedMass kg MassMass Remove the eye nut after installation of the productFR-F740-400KFR-HEL-H400K Remove the eye nut after installation of the productFR-F740-450KFR-HEL-H450K Parameter List Outline drawing Panel cutting dimension drawing Panel FR-DU07 M3 screw CableOption connector Terminal Connection DiagramMain circuit Control circuitTerminal Name Description Terminal Specification ExplanationType Preset detected frequency. *1 Relay output 1 alarmRelay OutputExplanation of the Operation Panel FR-DU07 Basic operation Operation mode switchoverSetting Parameter List Name Setting Range Increments Initial ValueRemarks FunctionJump 24 to101 100102 103139 135143 144179 178180 181262 261263 264872 867882 883Frequency Explanations of ParametersMaximum/minimum Starting frequency Jog operationStall prevention operation Speed and remote settingInput compensation of multi Pr , 23, 48, 49, 66, 148, 149, 154, 156Speed display and speed SettingPr , 70 Selection of regeneration unit Pr , 54, 158, 170, 171, 268, 563, 564, 867 Connection diagram Pr Remote setting functionPr.59 Setting Description Pr , 58, 162 to 165, 299Pr Energy saving control selection Retry function at alarmOccurrence Use the constant torque motorAnalog input selection Carrier frequency and SoftPWM selectionPr , 240 Pr , 242, 243, 252, 253Pr Output function of alarm code Pr. Reset selection, disconnected PU 75 detectionPr. Noise elimination at the analog 74 input Pr Prevention of parameter rewritePr. Simple magnetic flux vector 80, 90 control Pr Pr Operation mode selectionOff LED IndicationCommunication initial setting Adjustable 5 points V/FPr to Pr to 124, 331 to 337, 341 to 343Pr to 134, 575 to 577 PID control Pr Pr Pr , C2902 to C7905Analog input bias/gain calibration Analog input display unit changing PrPr. Parameter unit display language 145 selection Second function signal RTSelection of action conditions Pr Pr toTerminal assignment Pr. Operation selection of the 161 operation panelPr to 196 output terminal Function assignmentInput/output phase failure Pr. Selection of motor stopping 250 method and start signalPr Increase cooling fan life Pr to 247 Slip compensationPower failure stop mode Pr.261 = 261 to 266 power failurePr Parameter for manufacturer setting. Do not set Operation at instantaneousPr to 497 REM signal To determine Maintenance time of partsPr to 557 monitor signal Remote output functionFree parameter Pr. Regeneration avoidancePr to 899 Energy saving monitor 882 to 886 functionPr. C0900, C1901 Adjustment of terminal FM AM calibration Pr PU contrast adjustmentParameter clear, parameter copy Pr , CL, ALLC, Er.CL, PcpyProtective Functions Error message *2 Minor fault *4 Major failures *5Function Name Description Indication Regenerative overvoltage shutOptions Instructions Motor Supply short circuit RS-485 terminals power Was shortedOptions Option and Peripheral DevicesSeries Controller/SpeedOthers ManualName type Specifications, Structure, etcStand-alone option Name type Specifications, Structure, etc Connection example FR-BU-HKFR-BR-HK External connection diagram Outline dimension drawingsCable Resistor unit Resistance Mass Type ValueConverter Outline dimension Unit mm FR-HC- HK High power factorApplication of the sine wave filter Circuit configuration and connectionApplication condition Capacitor for sine wave filterPeripheral devices list On mA Standard BreakerEMC Filter Precautions for Operation/Selection Precautions for Peripheral Device Selection Noise reduction examples NoiseLeakage currents Three 7kW Reference materials Phase Input Target Measures PowerInput Target Measures Power Capacity Connect the AC reactor or DC reactor60Hz torque reference Application to Motor50Hz torque reference Suppressing the surge voltage on the inverter sideFR-F500 L FR-F700 Warranty FA Center in Taiwan FA Center in North AmericaFA Center in Asean FA Center in Korea