Mitsubishi Electronics FR-F700 Pr PU contrast adjustment, Parameter clear, parameter copy

Page 45

The following gives the items which can be monitored by the cumulative saving power monitor (Pr. 52 = "51").

(The cumulative power monitor data digit can be shifted to the right by the number set in Pr. 891 Cumulative power monitor digit shifted times.)

Energy

 

 

 

 

 

 

Saving

 

Description and Formula

 

 

Increments

Monitor

 

 

 

 

 

 

 

 

 

Item

 

 

 

 

 

 

Power

Power saving is added up per hour.

 

 

0.01kWh/

saving

 

 

Σ (Power saving × ∆t)

 

 

 

0.1kWh*

amount

 

 

 

 

 

 

 

 

 

Power

Power saving amount represented in terms of

 

saving

0.01/0.1*

charge

 

 

 

amount

 

 

 

Power saving amount × Pr. 896

 

 

 

charge

 

 

 

 

 

 

 

 

 

Annual

Estimated value of annual power saving amount

 

 

Power saving amount

 

Pr.899

0.01kWh/

power

 

× 24 × 365 ×

saving

 

Operation time during

100

 

0.1kWh*

amount

 

power saving totalization

 

 

 

 

 

 

 

 

 

 

 

Annual

Annual power saving amount represented in

 

power

0.01/0.1*

saving

terms of charge

 

 

 

amount

Annual power saving amount × Pr. 896

 

charge

 

 

 

 

 

 

*The increments vary according to the inverter capacity. (55K or less/75K or more)

Pr. C0(900), C1(901)

Adjustment of terminal FM

and AM (calibration)

C0(Pr.900) FM terminal calibration

C1(Pr.901) AM terminal calibration

The operation panel and parameter unit can be used to calibrate the full scales of the terminals FM and AM.

(1)FM terminal calibration (C0(Pr.900))

The terminal FM is preset to output pulses. By setting the

Calibraton parameter C0 (Pr. 900), the meter connected to the inverter can be calibrated by parameter setting without use of a calibration resistor.

Using the pulse train output of the terminal FM, a digital display can be provided by a digital counter. The monitor value is 1440 pulses/s output at the full-scale value of Pr. 54 FM terminal function selection.

Indicator

 

 

 

1mA full-scale

 

(Digital indicator)

analog meter

 

 

(-)

1mA

 

1440 pulse/s(+)

FM

(-)

FM

 

(+)

T1

 

Calibration

 

 

 

resistor*1

 

8VDC

 

 

 

 

SD

SD

T2

Pulse width T1: Adjust using calibration parameter C0

Pulse cycle T2: Set with Pr. 55 (frequency monitor)

Set with Pr.56 (current monitor)

*1 Not needed when the operation panel (FR-DU07) or parameter unit (FR- PU04) is used for calibration.

Used when calibration must be made near the frequency meter for such a reason as a remote frequency meter.

However, the frequency meter needle may not deflect to full-scale if the calibration resistor is connected. In this case, use this resistor and operation panel or parameter unit together.

(2)AM terminal calibration (C1(Pr.901))

The AM terminal is factory-set to output 10VDC in the full- scale state of each monitor item. By setting the calibration parameter C1 (Pr. 901), the ratio (gain) of the output voltage can be adjusted to the meter scale. Note that the maximum output voltage is 10VDC.

Pr. C2(902) to C7(905) Refer to the section about Pr. 125, Pr. 126

Pr. 989 Parameter for manufacturer setting. Do not set.

Pr. 990 Buzzer control of the operation panel

Pr.990 PU buzzer control

You can make the buzzer "beep" when you press key of the operation panel (FR-DU07) and parameter unit (FR-PU04).

Pr.990 Setting

Description

0

Without buzzer

1(initial value)

With buzzer

Pr. 991 PU contrast adjustment

Pr.991 PU contrast adjustment

Contrast adjustment of the LCD of the parameter unit (FR- PU04) can be performed.

Decreasing the setting value makes contrast light.

Pr.991 Setting

Description

0 to 63

0 : Light

 

63 : Dark

Pr. 989, CL, ALLC, Er.CL, PCPY

Parameter clear, parameter copy

Pr.989 Parameter copy alarm release

 

Pr.CL Parameter clear

ALLC All parameter clear

Er.CL Alarm history clear

PCPY Parameter copy

￿Set “1” in Pr.CL Parameter clear to initialize all parameters. (Calibration parameters are not cleared.)*

￿Set “1” in ALLC All parameter clear to initialize all parameters. *

￿Set “1” in Er.CL Alarm history clear to clear alarm history. *

￿Parameter settings can be copied to multiple inverters by using

PCPY.

When parameters are copied to the 75K or more inverter from

the 55K or less inverter or vice versa, an alarm appears on the operation panel.

For the parameters whose setting range differ, set Pr.989 as below after reset.

 

55K or less

 

75K or more

 

Pr.989 setting

10

 

100

 

 

 

 

 

 

PCPY

Description

 

 

Setting

 

 

 

 

 

 

0Cancel

1Copy the source parameters in the operation panel.

2Write the parameters copied to the operation panel to the destination inverter.

3Verify parameters in the inverter and operation panel.

*Parameters are not cleared when "1" is set in Pr.77 Parameter write selection.

 

 

Features

 

 

 

 

 

 

 

 

Peripheral Devices

Why energy

savings?

 

 

 

 

 

 

 

Standard

Specifications

 

 

 

 

 

 

 

Outline

Dimension

Drawings

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Connection

Diagram

Terminal Specification

Explanation

 

 

 

 

 

 

 

Operation

Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

List

 

 

 

 

 

 

 

 

 

 

 

 

 

Explanations

of

Parameters

 

 

 

 

 

 

 

Protective

Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compatibility

 

 

 

 

 

 

 

 

 

 

Warranty

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inquiry

 

 

 

 

 

 

 

 

Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.

46

Image 45
Contents FR-F700 Energy savings for buildings and factories as a whole Warranty Inquiry Outline Dimension DrawingsInverter FR-F700 Connection with Peripheral DevicesDamper control discharge side Why Can the Inverter Save Energy?Amount Inverter controlRating Standard SpecificationsType FR-F720-K Type FR-F740-KCan be selected Common specificationsOperating status Open collectorInverter Type Outline Dimension DrawingsFR-F720-0.75K 110 FR-F720-1.5K 125 FR-F740-0.75K to 2K are not provided With a cooling fanFR-F740-15K, 18.5K Wiring coverFR-F720-30K is Not provided with aFR-F740-75K 140 120 Inverter Type Mass295 185 FR-HEL-H75K FR-F740-90K 150 130 310 190 FR-HEL-H90KFR-F740-110KFR-HEL-H110K DC reactor suppliedMass kg MassMass Remove the eye nut after installation of the productFR-F740-400KFR-HEL-H400K Remove the eye nut after installation of the productFR-F740-450KFR-HEL-H450K Parameter ListOutline drawing Panel cutting dimension drawingPanel FR-DU07 M3 screw CableOption connector Terminal Connection DiagramMain circuit Control circuitTerminal Specification Explanation TypeTerminal Name Description Preset detected frequency. *1 Relay output 1 alarmRelay OutputExplanation of the Operation Panel FR-DU07 Operation mode switchover SettingBasic operation Parameter List Name Setting Range Increments Initial ValueRemarks FunctionJump 24 to101 100102 103139 135143 144179 178180 181262 261263 264872 867882 883Explanations of Parameters Maximum/minimumFrequency Starting frequency Jog operationStall prevention operation Speed and remote settingInput compensation of multi Pr , 23, 48, 49, 66, 148, 149, 154, 156Setting Pr , 70 Selection of regeneration unitSpeed display and speed Pr , 54, 158, 170, 171, 268, 563, 564, 867 Connection diagram Pr Remote setting functionPr.59 Setting Description Pr , 58, 162 to 165, 299Pr Energy saving control selection Retry function at alarmOccurrence Use the constant torque motorAnalog input selection Carrier frequency and SoftPWM selectionPr , 240 Pr , 242, 243, 252, 253Pr Output function of alarm code Pr. Reset selection, disconnected PU 75 detectionPr. Noise elimination at the analog 74 input Pr Prevention of parameter rewritePr. Simple magnetic flux vector 80, 90 control Pr Pr Operation mode selectionOff LED IndicationCommunication initial setting Adjustable 5 points V/FPr to Pr to 124, 331 to 337, 341 to 343Pr to 134, 575 to 577 PID control Pr Pr Pr , C2902 to C7905Analog input bias/gain calibration Analog input display unit changing PrPr. Parameter unit display language 145 selection Second function signal RTSelection of action conditions Pr Pr toTerminal assignment Pr. Operation selection of the 161 operation panelPr to 196 output terminal Function assignmentInput/output phase failure Pr. Selection of motor stopping 250 method and start signalPr Increase cooling fan life Pr to 247 Slip compensationPower failure stop mode Pr.261 = 261 to 266 power failurePr Parameter for manufacturer setting. Do not set Operation at instantaneousPr to 497 REM signal To determine Maintenance time of partsPr to 557 monitor signal Remote output functionFree parameter Pr. Regeneration avoidancePr to 899 Energy saving monitor 882 to 886 functionPr. C0900, C1901 Adjustment of terminal FM AM calibration Pr PU contrast adjustmentParameter clear, parameter copy Pr , CL, ALLC, Er.CL, PcpyProtective Functions Error message *2 Minor fault *4 Major failures *5Function Name Description Indication Regenerative overvoltage shutOptions Instructions Motor Supply short circuit RS-485 terminals power Was shortedOptions Option and Peripheral DevicesSeries Controller/SpeedOthers ManualSpecifications, Structure, etc Stand-alone optionName type Name type Specifications, Structure, etc FR-BU-HK FR-BR-HKConnection example External connection diagram Outline dimension drawingsCable Resistor unit Resistance Mass Type ValueConverter Outline dimension Unit mm FR-HC- HK High power factorApplication of the sine wave filter Circuit configuration and connectionApplication condition Capacitor for sine wave filterPeripheral devices list Standard Breaker EMC FilterOn mA Precautions for Operation/Selection Precautions for Peripheral Device Selection Noise Leakage currentsNoise reduction examples Three 7kW Reference materials Phase Input Target Measures PowerInput Target Measures Power Capacity Connect the AC reactor or DC reactor60Hz torque reference Application to Motor50Hz torque reference Suppressing the surge voltage on the inverter sideFR-F500 L FR-F700 Warranty FA Center in Taiwan FA Center in North AmericaFA Center in Asean FA Center in Korea