Mitsubishi Electronics FR-F700 instruction manual Pr , 54, 158, 170, 171, 268, 563, 564, 867

Page 31

Pr. 52, 54, 158, 170, 171, 268, 563, 564, 867, 891

Change of DU/PU monitor descriptions Cumulative monitor clear

Pr.52 DU/PU main display data selection

Pr.54 FM terminal function selection

Pr.158 AM terminal function selection

Pr.170 Cumulative power meter clear

Pr.171 Operation hour meter clear

Pr.268 Monitor decimal digits selection

Pr.563 Energization time carrying-over times

Pr.564 Operating time carrying-over times

Pr.867 AM output filter

 

Pr.891 Cumulative power monitor digit shifted times

The monitor to be displayed on the main screen of the operation panel (FR-DU07) / parameter unit (FR-PU04) can be selected.

 

 

 

Pr.52 Parameter

 

Pr.54

 

 

 

 

Setting Value

 

(FM)

Full Scale

Types of Monitor

Increments

 

DU

 

 

PU main

 

Pr.158

Value

 

 

 

 

 

 

(AM)

 

 

 

LED

 

monitor

 

 

 

 

 

 

 

Setting

 

Output frequency

0.01Hz

 

0/100

1

Pr.55

Output current

0.01A/

 

0/100

2

Pr.56

0.1A*6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200V

Output voltage

0.1V

 

0/100

3

class : 400V

 

400V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

class : 800V

Alarm display

 

0/100

 

Frequency setting

0.01Hz

5

 

 

*1

5

Pr.55

 

 

 

 

 

 

 

 

 

Value of Pr. 55

Running speed

1(r/min)

6

 

 

*1

6

represented in

 

 

terms of Pr. 37

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value

Converter output

 

 

 

 

 

 

 

 

200V

0.1V

8

 

 

*1

8

class : 400V

voltage

 

 

400V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

class : 800V

Regenerative brake

 

 

 

 

 

 

 

 

Brake duty set

0.1%

 

9

 

 

*1

9

in Pr. 30 and

duty *5

 

 

 

 

 

 

 

 

 

 

 

Pr. 70

 

 

 

 

 

 

 

 

 

Electronic thermal

 

 

 

 

 

 

 

 

Electronic

 

 

 

 

 

 

 

 

thermal relay

relay function load

0.1%

 

10

 

 

*1

10

 

 

 

function

factor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation level

 

 

 

 

 

 

 

 

 

Output current peak

0.01A/

11

 

 

*1

11

Pr.56

value

0.1A*6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200V

Converter output

0.1V

12

 

 

*1

12

class : 400V

voltage peak value

 

 

400V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

class : 800V

Input power

0.01kW/

13

 

 

*1

13

Rated inverter

0.1kW*6

 

 

power × 2

 

 

 

 

 

 

 

Output power

0.01kW/

14

 

 

*1

14

Rated inverter

0.1kW*6

 

 

power × 2

 

 

 

 

 

 

 

Input terminal status

55

 

 

*1

 

Output terminal

 

 

*1

 

status

 

 

 

 

 

 

 

 

 

 

 

 

 

Option input

56

 

 

×

 

terminal status

 

 

 

 

 

 

 

 

 

 

 

 

Option output

57

 

 

×

 

terminal status

 

 

 

 

 

 

 

 

 

 

 

 

Load meter

0.1%

 

 

 

17

17

Pr.56

Reference voltage

 

 

21

output

 

 

 

 

 

 

 

 

 

 

 

Cumulative

1h

 

 

20

 

energization time *2

 

 

 

 

 

 

 

 

 

 

 

 

Actual operation

1h

 

 

23

 

time *2, 3

 

 

 

 

 

 

 

 

 

 

 

 

Motor load factor

0.1%

 

 

 

24

24

200%

*1 Selected by the parameter unit(FR-PU04)

*2 The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.

When the operation panel (FR-DU07) is used, up to 65.53 (65530h) is displayed as 1h=0.001 and then accumulated from 0.

*3 The actual operation time is not added up if the cumulative operation time before power supply-off is less than 1h.

*4 When using the parameter unit (FR-PU04), “kW” is displayed.

*5 Setting can be made for the 75K or more.

*6 The setting depends on the inverter capacity.(55K or less/75K or more)⋅

The cumulative power monitor value digit can be shifted to the right by the number set in Pr. 891.

By setting “0” in Pr. 170, the cumulative power monitor can be cleared.

You can check the numbers of cumulative energization time monitor exceeded 65535h with Pr. 563 and the numbers of actual operation time monitor exceeded 65535h with Pr. 564.

Writing "0" in Pr. 171 clears the actual operation time monitor.

Pr. 268 Setting

Description

9999 (initial value)

No function

 

When 1 or 2 decimal places (0.1 increments or 0.01

 

increments) are monitored, the decimal places are

0

dropped and the monitor displays an integer value (1

 

increments).

 

The monitor value of 0.99 or less is displayed as 0.

 

When 2 decimal places (0.01 increments) are

 

monitored, the 0.01 decimal place is dropped and the

1

monitor displays the first decimal place (0.1

increments).

 

When the monitor display digit is originally in 1

 

increments, it is displayed unchanged in 1

 

increments.

When Pr. 52 is set to "100", the set frequency monitor is displayed during a stop and the output frequency monitor is displayed during operation. (LED of Hz flickers during stop and is lit during operation.)

 

 

Pr.52

 

 

 

0

 

100

 

During

During stop

 

During

 

operation/stop

 

running

 

 

 

Output

Output frequency

Set frequency

 

Output frequency

frequency

 

 

 

 

 

Output

 

Output current

 

 

current

 

 

 

 

 

 

 

Output

 

Output voltage

 

 

voltage

 

 

 

 

 

 

 

Alarm

 

Alarm display

 

 

display

 

 

 

 

 

 

 

Using Pr. 867 , the output voltage response of the terminal AM can be adjusted within the range 0 to 5s.

Pr. Change of the monitor output

55, 56 from terminal FM and AM

Pr.55 Frequency monitoring reference Pr.56 Current monitoring reference

Set the full-scale value to output the output frequency monitor value to terminal FM and AM.

Set the full-scale value to output the output current monitor value to terminal FM and AM in Pr. 56.

 

 

Features

 

 

 

 

 

 

 

 

Peripheral Devices

Why energy

savings?

 

 

 

 

 

 

 

Standard

Specifications

 

 

 

 

 

 

 

Outline

Dimension

Drawings

 

 

 

 

 

 

 

 

 

 

 

 

Terminal Connection

Diagram

Terminal Specification

Explanation

 

 

 

 

 

 

 

Operation

Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

List

 

 

 

 

 

 

 

 

 

 

 

 

 

Explanations

of

Parameters

 

 

 

 

 

 

 

Protective

Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Options

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compatibility

 

 

Cumulative power

0.01kWh/

25

0.1kWh *4, *6

 

 

 

 

Power saving effect

Variable

50

50

Inverter

according

capacity

 

 

 

 

to

 

 

 

Cumulative saving

51

power

parameters

 

 

 

PID set point

0.1%

52

52

100%

PID measured value

0.1%

53

53

100%

PID deviation value

0.1%

54

Pulse speed(terminal FM)

2400

pulse/s

1440

pulse/s

Output frequency

Pr.55

400Hz

reference

 

 

Output current

Pr.56

500A

reference

 

 

Output voltage(terminal AM)

10VDC

 

Pr.55

400Hz

Pr.56

500A

Warranty

 

 

Inquiry

 

Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.

32

Image 31
Contents FR-F700 Energy savings for buildings and factories as a whole Warranty Inquiry Outline Dimension DrawingsInverter FR-F700 Connection with Peripheral DevicesInverter control Why Can the Inverter Save Energy?Damper control discharge side AmountType FR-F740-K Standard SpecificationsRating Type FR-F720-KOpen collector Common specificationsCan be selected Operating statusFR-F740-0.75K to 2K are not provided With a cooling fan Outline Dimension DrawingsInverter Type FR-F720-0.75K 110 FR-F720-1.5K 125Not provided with a Wiring coverFR-F740-15K, 18.5K FR-F720-30K is310 190 FR-HEL-H90K Inverter Type MassFR-F740-75K 140 120 295 185 FR-HEL-H75K FR-F740-90K 150 130Mass DC reactor suppliedFR-F740-110KFR-HEL-H110K Mass kgMass Remove the eye nut after installation of the productParameter List Remove the eye nut after installation of the productFR-F740-400KFR-HEL-H400K FR-F740-450KFR-HEL-H450KM3 screw Cable Panel cutting dimension drawingOutline drawing Panel FR-DU07Control circuit Terminal Connection DiagramOption connector Main circuitType Terminal Specification ExplanationTerminal Name Description Output Relay output 1 alarmPreset detected frequency. *1 RelayExplanation of the Operation Panel FR-DU07 Setting Operation mode switchoverBasic operation Function Name Setting Range Increments Initial ValueParameter List RemarksJump 24 to103 100101 102144 135139 143181 178179 180264 261262 263883 867872 882Maximum/minimum Explanations of ParametersFrequency Starting frequency Jog operationPr , 23, 48, 49, 66, 148, 149, 154, 156 Speed and remote settingStall prevention operation Input compensation of multiPr , 70 Selection of regeneration unit SettingSpeed display and speed Pr , 54, 158, 170, 171, 268, 563, 564, 867 Pr , 58, 162 to 165, 299 Pr Remote setting functionConnection diagram Pr.59 Setting DescriptionUse the constant torque motor Retry function at alarmPr Energy saving control selection OccurrencePr , 242, 243, 252, 253 Carrier frequency and SoftPWM selectionAnalog input selection Pr , 240Pr Prevention of parameter rewrite Pr. Reset selection, disconnected PU 75 detectionPr Output function of alarm code Pr. Noise elimination at the analog 74 inputLED Indication Pr Pr Operation mode selectionPr. Simple magnetic flux vector 80, 90 control OffPr to 124, 331 to 337, 341 to 343 Adjustable 5 points V/FCommunication initial setting Pr toAnalog input display unit changing Pr Pr Pr Pr , C2902 to C7905Pr to 134, 575 to 577 PID control Analog input bias/gain calibrationPr Pr to Second function signal RTPr. Parameter unit display language 145 selection Selection of action conditionsFunction assignment Pr. Operation selection of the 161 operation panelTerminal assignment Pr to 196 output terminalPr to 247 Slip compensation Pr. Selection of motor stopping 250 method and start signalInput/output phase failure Pr Increase cooling fan lifeOperation at instantaneous 261 to 266 power failurePower failure stop mode Pr.261 = Pr Parameter for manufacturer setting. Do not setRemote output function To determine Maintenance time of partsPr to 497 REM signal Pr to 557 monitor signal882 to 886 function Pr. Regeneration avoidanceFree parameter Pr to 899 Energy saving monitorPr , CL, ALLC, Er.CL, Pcpy Pr PU contrast adjustmentPr. C0900, C1901 Adjustment of terminal FM AM calibration Parameter clear, parameter copyRegenerative overvoltage shut Error message *2 Minor fault *4 Major failures *5Protective Functions Function Name Description IndicationOptions Instructions Motor Supply short circuit RS-485 terminals power Was shortedOptions Option and Peripheral DevicesManual Controller/SpeedSeries OthersStand-alone option Specifications, Structure, etcName type Name type Specifications, Structure, etc FR-BR-HK FR-BU-HKConnection example Resistor unit Resistance Mass Type Value Outline dimension drawingsExternal connection diagram CableConverter Outline dimension Unit mm FR-HC- HK High power factorCapacitor for sine wave filter Circuit configuration and connectionApplication of the sine wave filter Application conditionPeripheral devices list EMC Filter Standard BreakerOn mA Precautions for Operation/Selection Precautions for Peripheral Device Selection Leakage currents NoiseNoise reduction examples Connect the AC reactor or DC reactor Input Target Measures PowerThree 7kW Reference materials Phase Input Target Measures Power CapacitySuppressing the surge voltage on the inverter side Application to Motor60Hz torque reference 50Hz torque referenceFR-F500 L FR-F700 Warranty FA Center in Korea FA Center in North AmericaFA Center in Taiwan FA Center in Asean