Mitsubishi Electronics FR-F700 Outline dimension drawings, External connection diagram, Cable

Page 53

Name (type)

Specifications, Structure, etc.

￿The brake unit and resistor unit are options that will fully exhibit the regenerative braking capability of the inverter. Use them as a set.

￿There are six different brake units as in the following table, from which make selection according to the deceleration time.

￿When the brake unit duty (%ED) excess and an alarm occur, errors appear in the inverter.

￿Brake unit selection table

￿%ED at short-time rating when braking torque is 100%

Motor Capacity

75

90

110

132

160

185

220

280

375

kW

kW

kW

kW

kW

kW

kW

kW

kW

Inverter

200V

75K

90K

110K

------

------

------

------

------

------

400V

75K

90K

110K

132K

160K

185K

220K

280K

375K

 

2 MT-BU5-55K

 

5

------

------

------

------

------

------

------

------

0%ED

unit

V

MT-BU5-110K

20

15

10

 

------

------

------

------

------

 

------

Brake

 

 

 

 

 

 

 

 

 

 

 

 

 

4

MT-BU5-H75K

10

5

------

------

------

------

------

------

------

 

MT-BU5-H150K

 

40

25

20

10

5

5

------

------

------

 

0

 

 

 

 

 

 

 

 

 

 

 

 

MT-BU5-H220K %ED

80

60

40

25

15

10

10

5

 

 

0

------

 

V

MT-BU5-H280K

 

------

80

65

40

30

20

15

10

5

 

 

MT-BU5-H375K

 

------

------

------

80

50

40

20

15

10

￿Braking torque (%) at short-time rating

 

 

Motor Capacity

75

90

110

132

160

185

220

280

375

 

 

kW

kW

kW

kW

kW

kW

kW

kW

kW

 

 

Inverter

200V

75K

90K

110K

------

------

------

------

------

------

 

 

400V

75K

90K

110K

132K

160K

185K

220K

280K

375K

 

 

 

 

2

MT-BU5-55K

braking

70

60

50

------

------

------

------

------

------

 

0

 

torque

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

unit

MT-BU5-110K

(%)

150

120

100

------

------

------

------

------

------

V

 

 

 

 

 

 

 

 

 

 

 

 

Brake

4

MT-BU5-H75K

 

100

80

70

55

45

40

35

25

20

MT-BU5-H150K

braking

150

150

135

110

90

80

70

50

40

0

 

 

 

 

 

 

 

 

 

 

 

0

MT-BU5-H220K

torque

150

150

150

150

135

115

100

80

55

 

V

MT-BU5-H280K

(%)

150

150

150

150

150

150

125

100

70

 

 

MT-BU5-H375K

 

150

150

150

150

150

150

150

130

100

*To obtain a large braking torque, the motor has to have a torque characteristic that meets the braking torque.

Check the torque characteristic of the motor.

￿Brake unit and resistor unit combinations and cables

Brake Unit Type

Resistor unit

Cable

type

 

 

 

200V

MT-BU5-55K

MT-BR5-55K

14mm2

MT-BU5-110K 2×MT-BR5-55K

2×14mm2

 

 

MT-BU5-H75K MT-BR5-H75K

14mm2

 

MT-BU5-

2×MT-BR5-H75K

2×14mm2

 

H150K

 

 

 

400V

MT-BU5-

3×MT-BR5-H75K

3×14mm2

H220K

 

 

 

MT-BU5-

4×MT-BR5-H75K

4×14mm2

 

H280K

 

 

 

 

MT-BU5-

5×MT-BR5-H75K

5×14mm2

 

H375K

 

 

 

(Caution 1) Be sure to select the well-ventilated place for installa- tion of the resistor unit. Ventilation is necessary when installing the resistor in a place, e.g. enclosure, where heat is not well diffused.

(Caution 2) The temperature rise of the discharging resistor is 300deg. Therefore, wire the cable so as not to touch the resistor. In addition, separate the parts with low heat resistance and the resistor by at least 40 to 50cm.

(Caution 3) The temperature of the resistor unit abnormally increases if the brake unit is operated exceeding the specified duty. Since the resistor unit may result in overheat if the temperature of the brake unit is left unchanged, switch off the inverter.

*The resistor unit is provided with a thermostat (a contact) as overheat protection. If this protective device is activated under normal operation, it is assumed that the deceleration time is too short. In such a case, increase the deceleration time setting of the inverter.

Brake unit MT-BU5-(H)￿￿K Resistor unit MT-BR5-(H)￿￿K

￿Outline dimension drawings

 

 

A

 

 

 

AA

 

 

 

AB

 

 

B BA

 

 

4

7

 

LN

Mounting hole

LP

 

 

LC

 

 

 

 

 

N

 

CN8

P

X-Y

 

 

P, PR terminal

2M6 screwN

85

C

 

 

 

 

85

 

 

NP

 

 

 

 

 

 

800

 

 

 

TH2

M4

M6

 

 

 

P PR TH1 E

 

 

 

40

 

30

193

 

 

 

189

 

37

60

10 21

 

480

510

4157.5 Mounting hole

75 300 75

450

 

 

Features

 

 

Peripheral Devices

Why energy

savings?

 

Standard

Specifications

 

Outline

Dimension

Drawings

Terminal Connection

Diagram

Terminal Specification

Explanation

 

Operation

Panel

 

 

Parameter

List

 

Explanations

of

Parameters

 

Protective

Functions

 

 

 

Options

 

 

Brake Unit Type

A

AA

AB

B

BA

C

Lc

LP

LN

N

Approx.

X

Y

Z

 

 

 

 

 

 

 

 

 

 

 

 

mass

 

 

 

200V MT-BU5-55K

118

102

90

200

100

256.5

550

1740

1740

1

1.5

14

12

8

class MT-BU5-110K

188

172

160

200

100

256.5

550

2000

2000

2

3.0

22

12

8

 

MT-BU5-H75K

118

102

90

200

100

256.5

550

1740

1740

1

1.5

14

12

8

400V

MT-BU5-H150K

188

172

160

200

100

256.5

550

2000

2000

2

3.0

22

12

8

MT-BU5-H220K

258

242

230

200

100

256.5

550

2000

2000

3

4.5

38

12

8

class

 

MT-BU5-H280K

328

312

300

200

100

256.5

550

2330

2330

4

6.0

60

12

10

 

MT-BU5-H375K

398

382

370

200

100

256.5

550

2330

2330

5

7.5

60

12

10

￿External connection diagram

Resistor unit

Resistance

mass

 

type

 

value

 

200V

MT-BR5-55K

 

 

2.0

50kg

class

 

 

400V

MT-BR5-

 

 

6.5

70kg

class

H75K

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instructions

Motor

Inverter

R/L1 U

S/L2 V

T/L3 W

P/+

 

 

The wiring length should be 10m

 

 

maximum when wires are twisted

 

 

and 5m maximum when wires are

IM

 

not twisted.

 

 

 

 

 

 

TH1

TH2

 

P

P

 

 

 

 

(Caution 1) For wiring of the brake unit and inverter, use an accessory cable supplied with the brake unit. Connect the main circuit cable to the ter- minals P/+ and N/- and connect the control cir- cuit cable to the connector (CN8) inside by

Brake unit

Compatibility

N/-

CN8

PR

PR

making cuts in the rubber bush at the top of the inverter.

(Caution 2) The brake unit which uses multiple resistor

Inverter

P

P

units has terminals equal to the number of

PR

PR

resistor units. Connect one resistor unit to one pair of terminals (P, PR).

Cable provided with a brake unit

Brake unit

MT-BU5Resistor unit

MT-BR5

Warranty

 

 

Inquiry

 

54

Image 53
Contents FR-F700 Energy savings for buildings and factories as a whole Warranty Inquiry Outline Dimension DrawingsInverter FR-F700 Connection with Peripheral DevicesDamper control discharge side Why Can the Inverter Save Energy?Amount Inverter controlRating Standard SpecificationsType FR-F720-K Type FR-F740-KCan be selected Common specificationsOperating status Open collectorInverter Type Outline Dimension DrawingsFR-F720-0.75K 110 FR-F720-1.5K 125 FR-F740-0.75K to 2K are not provided With a cooling fanFR-F740-15K, 18.5K Wiring coverFR-F720-30K is Not provided with aFR-F740-75K 140 120 Inverter Type Mass295 185 FR-HEL-H75K FR-F740-90K 150 130 310 190 FR-HEL-H90KFR-F740-110KFR-HEL-H110K DC reactor suppliedMass kg MassMass Remove the eye nut after installation of the productFR-F740-400KFR-HEL-H400K Remove the eye nut after installation of the productFR-F740-450KFR-HEL-H450K Parameter ListOutline drawing Panel cutting dimension drawingPanel FR-DU07 M3 screw CableOption connector Terminal Connection DiagramMain circuit Control circuitTerminal Name Description Terminal Specification ExplanationType Preset detected frequency. *1 Relay output 1 alarmRelay OutputExplanation of the Operation Panel FR-DU07 Basic operation Operation mode switchoverSetting Parameter List Name Setting Range Increments Initial ValueRemarks FunctionJump 24 to101 100102 103139 135143 144179 178180 181262 261263 264872 867882 883Frequency Explanations of ParametersMaximum/minimum Starting frequency Jog operationStall prevention operation Speed and remote settingInput compensation of multi Pr , 23, 48, 49, 66, 148, 149, 154, 156Speed display and speed SettingPr , 70 Selection of regeneration unit Pr , 54, 158, 170, 171, 268, 563, 564, 867 Connection diagram Pr Remote setting functionPr.59 Setting Description Pr , 58, 162 to 165, 299Pr Energy saving control selection Retry function at alarmOccurrence Use the constant torque motorAnalog input selection Carrier frequency and SoftPWM selectionPr , 240 Pr , 242, 243, 252, 253Pr Output function of alarm code Pr. Reset selection, disconnected PU 75 detectionPr. Noise elimination at the analog 74 input Pr Prevention of parameter rewritePr. Simple magnetic flux vector 80, 90 control Pr Pr Operation mode selectionOff LED IndicationCommunication initial setting Adjustable 5 points V/FPr to Pr to 124, 331 to 337, 341 to 343Pr to 134, 575 to 577 PID control Pr Pr Pr , C2902 to C7905Analog input bias/gain calibration Analog input display unit changing PrPr. Parameter unit display language 145 selection Second function signal RTSelection of action conditions Pr Pr toTerminal assignment Pr. Operation selection of the 161 operation panelPr to 196 output terminal Function assignmentInput/output phase failure Pr. Selection of motor stopping 250 method and start signalPr Increase cooling fan life Pr to 247 Slip compensationPower failure stop mode Pr.261 = 261 to 266 power failurePr Parameter for manufacturer setting. Do not set Operation at instantaneousPr to 497 REM signal To determine Maintenance time of partsPr to 557 monitor signal Remote output functionFree parameter Pr. Regeneration avoidancePr to 899 Energy saving monitor 882 to 886 functionPr. C0900, C1901 Adjustment of terminal FM AM calibration Pr PU contrast adjustmentParameter clear, parameter copy Pr , CL, ALLC, Er.CL, PcpyProtective Functions Error message *2 Minor fault *4 Major failures *5Function Name Description Indication Regenerative overvoltage shutOptions Instructions Motor Supply short circuit RS-485 terminals power Was shortedOptions Option and Peripheral DevicesSeries Controller/SpeedOthers ManualName type Specifications, Structure, etcStand-alone option Name type Specifications, Structure, etc Connection example FR-BU-HKFR-BR-HK External connection diagram Outline dimension drawingsCable Resistor unit Resistance Mass Type ValueConverter Outline dimension Unit mm FR-HC- HK High power factorApplication of the sine wave filter Circuit configuration and connectionApplication condition Capacitor for sine wave filterPeripheral devices list On mA Standard BreakerEMC Filter Precautions for Operation/Selection Precautions for Peripheral Device Selection Noise reduction examples NoiseLeakage currents Three 7kW Reference materials Phase Input Target Measures PowerInput Target Measures Power Capacity Connect the AC reactor or DC reactor60Hz torque reference Application to Motor50Hz torque reference Suppressing the surge voltage on the inverter sideFR-F500 L FR-F700 Warranty FA Center in Taiwan FA Center in North AmericaFA Center in Asean FA Center in Korea