Mitsubishi Electronics FR-F700 Pr. Regeneration avoidance, Free parameter, 882 to 886 function

Page 44

Pr. Regeneration avoidance

882 to 886 function

Pr.882 Regeneration avoidance operation selection Pr.883 Regeneration avoidance operation level

Pr.884 Regeneration avoidance at deceleration detection sensitivity Pr.885 Regeneration avoidance compensation frequency limit value Pr.886 Regeneration avoidance voltage gain

This function detects a regeneration status and increases the frequency to avoid the regeneration status.

￿Possible to avoid regeneration by automatically increasing the frequency and continue operation if the fan happens to rotate faster than the set speed due to the effect of another fan in the same duct.

Pr.

Setting

Description

Number

Range

 

 

 

 

 

 

 

0

 

 

 

 

 

 

882

(initial

Regeneration avoidance function invalid

value)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Regeneration avoidance function valid

 

 

Set the bus voltage level at which regeneration

 

 

avoidance operates. When the bus voltage level

883

300 to

is set to low, overvoltage error will be less apt to

800V

occur. However, the actual deceleration time

 

 

 

increases. The set value must be higher than the

 

 

power supply valtage ×

2 .

 

 

 

0

Regeneration avoidance by bus voltage change

 

(initial

 

ratio is invalid

 

 

 

 

 

 

value)

 

 

 

 

 

884

 

 

 

 

 

 

 

Set sensitivity to detect the bus voltage change

 

 

 

1 to 5

Setting

1

 

 

5

 

 

 

 

Detection sensitivity

low

 

 

 

high

 

 

 

 

 

 

 

 

 

 

 

 

0 to 10Hz

Set the limit value of frequency which rises at

885

activation of regeneration avoidance function.

 

 

9999

Frequency limit invalid

 

 

 

 

 

 

Adjust responsiveness at activation of

 

 

regeneration avoidance. A larger setting will

8860 to 200% improve responsiveness to the bus voltage change. However, the output frequency could become unstable.

Pr. 888, 889

Free parameter

Pr.888 Free parameter 1

Pr.889 Free parameter 2

Parameters you can use for your own purposes.

You can input any number within the setting range 0 to 9999. For example, the number can be used:

As a unit number when multiple units are used.

As a pattern number for each operation application when multiple units are used.

As the year and month of introduction or inspection.

Pr.

891

 

Refer to the section about Pr. 52 and other

 

 

relevant parameters.

 

 

 

Pr. 892 to 899 Energy saving monitor

Pr.892 Load factor

Pr.893 Energy saving monitor reference (motor capacity)

Pr.894 Control selection during commercial power-supply operation Pr.895 Power saving rate reference value

Pr.896 Power unit cost

Pr.897 Power saving monitor average time Pr.898 Power saving cumulative monitor clear Pr.899 Operation time rate (estimated value)

From the power consumption estimated value during commercial power supply operation, the energy saving effect by use of the inverter can be monitored/output.

The following provides the items that can be monitored by the power saving monitor (Pr. 52, Pr. 54, Pr. 158 = "50").

(Only power saving and power saving average value can be output to Pr. 54 (terminal FM) and Pr. 158 (terminal AM))

Energy

 

 

 

 

 

 

 

 

 

 

 

Saving

 

 

 

Description and Formula

Increments

Monitor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

 

 

 

 

 

 

 

 

 

Difference between the estimated value of

 

Power

power necessary for commercial power supply

0.01kW/

operation and the input power calculated by the

saving

inverter

 

 

 

 

 

 

0.1kW*

 

Power during commercial power supply

 

 

operation - input power monitor

 

 

Ratio of power saving on the assumption that

 

 

power during commercial power supply

 

 

operation is 100%

 

 

 

 

 

 

Power

 

 

 

Power saving

 

× 100

 

 

 

Power during commercial power supply operation

0.1%

saving

 

 

 

 

 

 

 

 

 

 

rate

Ratio of power saving on the assumption that

 

 

Pr. 893 is 100%

 

 

 

 

 

 

 

 

 

 

 

Power saving

×100

 

 

 

 

 

 

 

 

 

 

Pr.893

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

Average value of power saving amount per hour

 

during predetermined time (Pr. 897)

0.01kWh/

saving

 

 

 

Σ (Power saving × ∆t)

 

 

 

 

 

average

 

 

 

 

 

 

 

 

0.1kWh*

value

 

 

 

Pr.897

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ratio of power saving average value on the

 

 

assumption that the value during commercial

 

 

power supply operation is 100%

 

 

 

Power

 

 

 

Σ (Power saving × ∆t)

 

×100

 

 

 

saving

 

 

 

Pr.897

 

 

 

 

0.1%

rate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

reference

Ratio of power saving average value on the

 

value

assumption that Pr. 893 is 100%

 

 

 

 

 

 

 

Power saving average value

×100

 

 

 

 

 

 

Pr.893

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

Power saving average value represented in

 

saving

0.01/0.1*

charge

terms of charge

 

 

 

 

 

 

average

Power saving average value × Pr. 896

 

value

 

 

 

 

 

 

 

 

 

 

 

45

Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.

Image 44
Contents FR-F700 Energy savings for buildings and factories as a whole Outline Dimension Drawings Warranty InquiryConnection with Peripheral Devices Inverter FR-F700Why Can the Inverter Save Energy? Damper control discharge sideAmount Inverter controlStandard Specifications RatingType FR-F720-K Type FR-F740-KCommon specifications Can be selectedOperating status Open collectorOutline Dimension Drawings Inverter TypeFR-F720-0.75K 110 FR-F720-1.5K 125 FR-F740-0.75K to 2K are not provided With a cooling fanWiring cover FR-F740-15K, 18.5KFR-F720-30K is Not provided with aInverter Type Mass FR-F740-75K 140 120295 185 FR-HEL-H75K FR-F740-90K 150 130 310 190 FR-HEL-H90KDC reactor supplied FR-F740-110KFR-HEL-H110KMass kg MassRemove the eye nut after installation of the product MassRemove the eye nut after installation of the product FR-F740-400KFR-HEL-H400KFR-F740-450KFR-HEL-H450K Parameter ListPanel cutting dimension drawing Outline drawingPanel FR-DU07 M3 screw CableTerminal Connection Diagram Option connectorMain circuit Control circuitTerminal Name Description Terminal Specification ExplanationType Relay output 1 alarm Preset detected frequency. *1Relay OutputExplanation of the Operation Panel FR-DU07 Basic operation Operation mode switchoverSetting Name Setting Range Increments Initial Value Parameter ListRemarks Function24 to Jump100 101102 103135 139143 144178 179180 181261 262263 264867 872882 883Frequency Explanations of ParametersMaximum/minimum Jog operation Starting frequencySpeed and remote setting Stall prevention operationInput compensation of multi Pr , 23, 48, 49, 66, 148, 149, 154, 156Speed display and speed SettingPr , 70 Selection of regeneration unit Pr , 54, 158, 170, 171, 268, 563, 564, 867 Pr Remote setting function Connection diagramPr.59 Setting Description Pr , 58, 162 to 165, 299Retry function at alarm Pr Energy saving control selectionOccurrence Use the constant torque motorCarrier frequency and SoftPWM selection Analog input selectionPr , 240 Pr , 242, 243, 252, 253Pr. Reset selection, disconnected PU 75 detection Pr Output function of alarm codePr. Noise elimination at the analog 74 input Pr Prevention of parameter rewritePr Pr Operation mode selection Pr. Simple magnetic flux vector 80, 90 controlOff LED IndicationAdjustable 5 points V/F Communication initial settingPr to Pr to 124, 331 to 337, 341 to 343Pr Pr Pr , C2902 to C7905 Pr to 134, 575 to 577 PID controlAnalog input bias/gain calibration Analog input display unit changing PrSecond function signal RT Pr. Parameter unit display language 145 selectionSelection of action conditions Pr Pr toPr. Operation selection of the 161 operation panel Terminal assignmentPr to 196 output terminal Function assignmentPr. Selection of motor stopping 250 method and start signal Input/output phase failurePr Increase cooling fan life Pr to 247 Slip compensation261 to 266 power failure Power failure stop mode Pr.261 =Pr Parameter for manufacturer setting. Do not set Operation at instantaneousTo determine Maintenance time of parts Pr to 497 REM signalPr to 557 monitor signal Remote output functionPr. Regeneration avoidance Free parameterPr to 899 Energy saving monitor 882 to 886 functionPr PU contrast adjustment Pr. C0900, C1901 Adjustment of terminal FM AM calibrationParameter clear, parameter copy Pr , CL, ALLC, Er.CL, PcpyError message *2 Minor fault *4 Major failures *5 Protective FunctionsFunction Name Description Indication Regenerative overvoltage shutSupply short circuit RS-485 terminals power Was shorted Options Instructions MotorOption and Peripheral Devices OptionsController/Speed SeriesOthers ManualName type Specifications, Structure, etcStand-alone option Name type Specifications, Structure, etc Connection example FR-BU-HKFR-BR-HK Outline dimension drawings External connection diagramCable Resistor unit Resistance Mass Type ValueHigh power factor Converter Outline dimension Unit mm FR-HC- HKCircuit configuration and connection Application of the sine wave filterApplication condition Capacitor for sine wave filterPeripheral devices list On mA Standard BreakerEMC Filter Precautions for Operation/Selection Precautions for Peripheral Device Selection Noise reduction examples NoiseLeakage currents Input Target Measures Power Three 7kW Reference materials PhaseInput Target Measures Power Capacity Connect the AC reactor or DC reactorApplication to Motor 60Hz torque reference50Hz torque reference Suppressing the surge voltage on the inverter sideFR-F500 L FR-F700 Warranty FA Center in North America FA Center in TaiwanFA Center in Asean FA Center in Korea