Pr. Regeneration avoidance
882 to 886 function
Pr.882 Regeneration avoidance operation selection Pr.883 Regeneration avoidance operation level
Pr.884 Regeneration avoidance at deceleration detection sensitivity Pr.885 Regeneration avoidance compensation frequency limit value Pr.886 Regeneration avoidance voltage gain
This function detects a regeneration status and increases the frequency to avoid the regeneration status.
Possible to avoid regeneration by automatically increasing the frequency and continue operation if the fan happens to rotate faster than the set speed due to the effect of another fan in the same duct.
Pr. | Setting | Description | ||||||
Number | Range | |||||||
|
|
|
|
|
| |||
| 0 |
|
|
|
|
|
| |
882 | (initial | Regeneration avoidance function invalid | ||||||
value) |
|
|
|
|
|
| ||
|
|
|
|
|
|
| ||
| 1 | Regeneration avoidance function valid | ||||||
|
| Set the bus voltage level at which regeneration | ||||||
|
| avoidance operates. When the bus voltage level | ||||||
883 | 300 to | is set to low, overvoltage error will be less apt to | ||||||
800V | occur. However, the actual deceleration time | |||||||
| ||||||||
|
| increases. The set value must be higher than the | ||||||
|
| power supply valtage × | 2 . |
|
| |||
| 0 | Regeneration avoidance by bus voltage change | ||||||
| (initial | |||||||
| ratio is invalid |
|
|
|
|
| ||
| value) |
|
|
|
|
| ||
884 |
|
|
|
|
|
| ||
| Set sensitivity to detect the bus voltage change | |||||||
|
| |||||||
| 1 to 5 | Setting | 1 |
|
| 5 | ||
|
| |||||||
|
| Detection sensitivity | low |
|
|
| high | |
|
|
|
|
| ||||
|
|
|
|
|
| |||
| 0 to 10Hz | Set the limit value of frequency which rises at | ||||||
885 | activation of regeneration avoidance function. | |||||||
| ||||||||
| 9999 | Frequency limit invalid |
|
|
|
| ||
|
| Adjust responsiveness at activation of | ||||||
|
| regeneration avoidance. A larger setting will |
8860 to 200% improve responsiveness to the bus voltage change. However, the output frequency could become unstable.
Pr. 888, 889 | Free parameter |
Pr.888 Free parameter 1 | Pr.889 Free parameter 2 |
Parameters you can use for your own purposes.
You can input any number within the setting range 0 to 9999. For example, the number can be used:
⋅As a unit number when multiple units are used.
⋅As a pattern number for each operation application when multiple units are used.
⋅As the year and month of introduction or inspection.
Pr. | 891 |
| Refer to the section about Pr. 52 and other |
| |||
| relevant parameters. | ||
|
|
|
Pr. 892 to 899 Energy saving monitor
Pr.892 Load factor
Pr.893 Energy saving monitor reference (motor capacity)
Pr.894 Control selection during commercial
Pr.896 Power unit cost
Pr.897 Power saving monitor average time Pr.898 Power saving cumulative monitor clear Pr.899 Operation time rate (estimated value)
From the power consumption estimated value during commercial power supply operation, the energy saving effect by use of the inverter can be monitored/output.
⋅The following provides the items that can be monitored by the power saving monitor (Pr. 52, Pr. 54, Pr. 158 = "50").
(Only power saving and power saving average value can be output to Pr. 54 (terminal FM) and Pr. 158 (terminal AM))
Energy |
|
|
|
|
|
|
|
|
|
|
| |
Saving |
|
|
| Description and Formula | Increments | |||||||
Monitor |
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| ||
Item |
|
|
|
|
|
|
|
|
|
|
| |
| Difference between the estimated value of |
| ||||||||||
Power | power necessary for commercial power supply | 0.01kW/ | ||||||||||
operation and the input power calculated by the | ||||||||||||
saving | inverter |
|
|
|
|
|
| 0.1kW* | ||||
| Power during commercial power supply |
| ||||||||||
| operation - input power monitor |
| ||||||||||
| Ratio of power saving on the assumption that |
| ||||||||||
| power during commercial power supply |
| ||||||||||
| operation is 100% |
|
|
|
|
|
| |||||
Power |
|
|
| Power saving |
| × 100 |
| |||||
|
| Power during commercial power supply operation | 0.1% | |||||||||
saving |
|
|
|
|
|
|
|
|
|
| ||
rate | Ratio of power saving on the assumption that |
| ||||||||||
| Pr. 893 is 100% |
|
|
|
|
|
|
| ||||
|
|
|
| Power saving | ×100 |
|
|
|
|
|
| |
|
|
|
| Pr.893 |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||||
Power | Average value of power saving amount per hour |
| ||||||||||
during predetermined time (Pr. 897) | 0.01kWh/ | |||||||||||
saving | ||||||||||||
|
|
| Σ (Power saving × ∆t) |
|
|
|
|
| ||||
average |
|
|
|
|
|
|
|
| 0.1kWh* | |||
value |
|
|
| Pr.897 |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| ||||
| Ratio of power saving average value on the |
| ||||||||||
| assumption that the value during commercial |
| ||||||||||
| power supply operation is 100% |
|
|
| ||||||||
Power |
|
|
| Σ (Power saving × ∆t) |
| ×100 |
|
|
| |||
saving |
|
|
| Pr.897 |
|
|
|
| 0.1% | |||
rate |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| |||
reference | Ratio of power saving average value on the |
| ||||||||||
value | assumption that Pr. 893 is 100% |
|
|
| ||||||||
|
|
|
| Power saving average value | ×100 |
|
| |||||
|
|
|
| Pr.893 |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| |
Power | Power saving average value represented in |
| ||||||||||
saving | 0.01/0.1* | |||||||||||
charge | terms of charge |
|
|
|
|
|
| |||||
average | Power saving average value × Pr. 896 |
| ||||||||||
value |
|
|
|
|
|
|
|
|
|
|
|
45 | Pr. indicates simple mode parameters and Pr. indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions. |